| 1 | Supply, Laying ,Testing,Commisioning Of 1100V Grade With Confirmity With IS:7098 FRLS XLPE / PVC LT UG ALU Armoured Cables.The Cables Shall be Laid in Existing Constructed Trenches / Cable Trays / Hume Pipes / PVC Pipes / Directly Buried Underground.a) 4 Core X 240 Sq.mm.UG Alu Armoured Cable |
| 2 | b) 4 Core X 185 Sq.mm.UG Alu Armoured Cable |
| 3 | c) 4 Core X 95 Sq.mm.UG Alu Armoured Cable |
| 4 | d) 4 Core X 25 Sq.mm.UG Alu Armoured Cable |
| 5 | e) 4 Core X 10 Sq.mm.UG Alu Armoured Cable |
| 6 | Supply,Installation of Chrome Plated Brass Single Compression Glands in Following Sizes in Various Cables.a) 4 Core X 240 Sq.mm.UG Alu Armoured Cable |
| 7 | b) 4 Core X 185 Sq.mm.UG Alu Armoured Cable |
| 8 | c) 4 Core X 95 Sq.mm.UG Alu Armoured Cable |
| 9 | d) 4 Core X 25 Sq.mm.UG Alu Armoured Cable |
| 10 | e) 4 Core X 10 Sq.mm.UG Alu Armoured Cable |
| 11 | Supply and Installation of LT Cable end Termination for Suitable Aluminium / Copper Lugs in Following Sizes in Various Cables.a) 4 Core X 240 Sq.mm.UG Alu Armoured Cable |
| 12 | b) 4 Core X 185 Sq.mm.UG Alu Armoured Cable |
| 13 | c) 4 Core X 95 Sq.mm.UG Alu Armoured Cable |
| 14 | d) 4 Core X 25 Sq.mm.UG Alu Armoured Cable |
| 15 | e) 4 Core X 10 Sq.mm.UG Alu Armoured Cable |
| 16 | Supply, installing, testing and commissioning of GI Plate Earthing station including Excavation,back filling using 600 x 600 x 5mm GI Plate Complete with 40mm dia GI Pipe 3 Mtrs Long With funnel Arangements..Etc With Using Recommended Back Fill Compound |
| 17 | Supply, installing, testing and commissioning of Copper Plate Earthing station including Excavation,back filling using 600 x 600 x 3.15mm Copper plate Complete with 40mm dia GI Pipe 3 Mtrs Long With funnel Arangements..Etc With Using Recommended Back Fill Compound |
| 18 | Supply, installing, testing and commissioning of 80mm Copper Bonded Pipe in Pipe Tecnology Earthing For Lightning Arrestor With Recommended Back Fill Compound |
| 19 | Supply,Cutting,Bending,Welding,Laying With Tray / Trench / Wall in Necessary Hardware With Recommended Overlap Between The Two Strips.Earthing Conductor Of GI Strip / Copper Strip / Bare Copper Wires a)25x3mm Copper Flat |
| 20 | b) 25x6mm Copper Flat |
| 21 | c) 8 SWG Bare Copper Wire |
| 22 | Supply And Installation of EPOXCY Round Type Insulator With Suitable Anchor Fastners And Bolt,Nuts&Washers in Various Size & Various Places. |
| 23 | Supply and Fixing of Earthing Bridge Clamp With Suitable Hardwares in Meter Room / Lift Machine Room / Electrical Shafta) 6 Way Earth Bridge Clamp for Motor Rooms |
| 24 | b) 10 Way Earth Bridge Clamp In EB Meter Rooms |
| 25 | Supply and fixing of Early Streamer Emission Air Terminal (ESEAT) The ESEAT has corrosion resistant stainless chrome body made up of AISI 316 grade of height 0.50 metres capable of working in hazardous atmosphere. The Air terminal is non-radioactive and requires no special licensing. |
| 26 | Supply and fixing of standard / Special Mounting Structure of height 4.5 mts. Pipe, and 300 x 300 x 8mm MS plate,3 mtrs ,48mm OD Class C GI pipe,1.8mtr, 38mm OD inner pipe, for roof mounting with Suitable Anchor Fastners, Bolt, Nuts, Washers & Stay Wires |
| 27 | Supply and Laying Down Conductor Of Single Core x 70 sq mm Multistand FRLS PVC insulated unsheathed flexiable copper Wire laid in 32mm PVC rigid conduit with all accessories like Screws Supported clamps etc., |
| 28 | Supply, Erection, testing and commissioning of Test terminal block box with base FRP insulater and providing suitable holes bottom conductor with all accessories like screws,clamps for terminations of top etc., |
| 29 | Supply and Installation Cabinet Type Class 1 and 2 Combined Model SPD to Arrest Surges and Overvoltages in The Power Line Due to Lighning Switching Action Etc.They Must be Installed Com Panel,Pump Panel in Respective to the Power Circuit.Including all relevent materials in Standard Specifications. |
| 30 | Supply,Fabrication and erection Of 5mm Thick MS Chequred Plate in Various Size, Various Places Like EB Room / Duct. Including Gas Cutting, Grinding, Drilling,Welding & Painting With All Hardware Acessories |
| 31 | Supplying and erection of ISA MS ANGLE / MS CHANNEL member of Various Sizes and Various Thickness. Using in Trench,Metering Panels Bottom Support & Chequred Plate Bottom Frame Work Including Charges Of Cutting, Welding, Grinding, Suitable Holes Making, Painting With Necessary Hardware.. |
| 32 | Supply and Instalation 10 Way SPN DB Double Door With ( 63A,4-Pole MCB-1 No,16A/6A,2-Pole MCB -2 Nos ) |
| 33 | Supply and Laying With Suitable PVC Pipes in 4 Core X 2.5 Sq.mm Copper Wire. |
| 34 | Supplying and Fixing of Safety Accessories as per High Rise building Norms a) ISI Certified Tested Rubber Hand Gloves One Pair-11KV Grade |
| 35 | b) Shock Treatment Chart Fixed in Glass Frame / Lamination |
| 36 | c) LT Caution Danger Board in Meter Room |
| 37 | d) First Aid Box With Complete All First Aid Medicines |
| 38 | e) ISI Certified Tested Rubber Mat Size of 1 mtr X 2.5 mm thick |
| 39 | Supply and laying of 100mm dia GI pipes 'B' class of best approved quality with ISI mark below ground level including cost and conveyence and fixing in position etc., all complete in all respects complying with relevant standard specification and as directed by the departmental officer. |
| 40 | Supplying and Fixing of 415V,3 Phase 4 wires,50Hz Distribution system LTCT meter panel board as per Site conditions required CT coils Range.As per TNEB Standards. |
| 41 | Supply, Instalation,Testing and Commisioning of of 415V,3 Phase 4 wires, 50Hz Distribution system 400A,Consumer panel board as per TNEB Standards. |
| 42 | Supply and Erection of 250Amps Capacity Floor mounting panel board (Cubical Type) with bus bar Chamber made up of 16 SWG MS Sheet for 3 Phase 4 wires System with 50mm x 12mm Aluminium Flats for Phases and 50mm x 6mm Alumnium flats for Neutral,cable chamber,switch chamber with 2 Nos.25mm x6mm Alumnium flat for earth bus on the rear side of the panel board,necessary interconnecting earth connections to all switches / bus bar as per standards specification. |
| 43 | Supply and Erection of 250A/350Amps Capacity Floor mounting panel board (Cubical Type) with bus bar Chamber made up of 16 SWG MS Sheet for 3 Phase 4 wires System with 50mm x 12mm Aluminium Flats for Phases and 50mm x 6mm Alumnium flats for Neutral,cable chamber,switch chamber with 2 Nos.25mm x6mm Alumnium flat for earth bus on the rear side of the panel board,necessary interconnecting earth connections to all switches / bus bar as per standards specification. |
| 44 | Supply,instalation,Testing and Commisioning of 60KVAR 8 Stage APFCR Panel Suitable for 415V,3 Phase 4 wires,50Hz Distribution system.The panel shall be IP 44,free standing,floor/wall mounting,vermin Proof,CRCA sheet metel enclosed,flush front with Aluminium Bus Bars |
| 45 | Run off mains with 4 wires of 10 Sqmm FRLS Copper wire contuinuous earth by means of 1 wires of 6 Sqmm FRLS Copper wire in fully concealed 25 mm / 32 mm dia rigid PVC conduit pipe heavy duty with ISI mark including cost of all materials, specials, etc., |
| 46 | Run off mains with 4 wires of 6 Sqmm FRLS Copper wire contuinuous earth by means of 1 wires of 4 Sqmm FRLS Copper wire in fully concealed 25 mm / 32 mm dia rigid PVC conduit pipe heavy duty with ISI mark including cost of all materials, specials etc. |
| 47 | Supplying and fixing of 450 mm dia sweep AC exhaust fan of approved ISI quality including necessary wall opening, fixing and finishing the wall opening and making good including cost of material, labour for fixing, chipping and redoing necessary inter connection, scaffolding, hire charges for tools and plants etc., Please Enable Macros to View BoQ information |