| 1 | Supply, Installation, Testing & Commisioning of Micropresssor controlled Addressable OPC complied Multisensor Detector (VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 2 | Supply, Installation, Testing & Commisioning of OPC complied Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 3 | Supply, Installation, Testing & Commissioning of Addressable OPC complied Loop Powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 4 | Supply, Installation, Testing & Commisioning of Micropresssor controlled Addressable OPC complied Heat detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 5 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make : Finolex/ Gloster/ RR Kable/ Polycab/ KEI ) through S & F of 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall. |
| 6 | Supplying, Installation, Testing and Commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire/System Sensor/Agni Suraksha ) |
| 7 | Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. |
| 8 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. |
| 9 | The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software.(Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 10 | NOTE :- 1) The Fire Alarm system shall comply with latest requirements of --(i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 ,(iii) NFPA 70 National Electric Code,(iv) NFPA 72 National Fire Alarm & Signaling Code ,(v) Local Statutory Regulations ,(vi) Manufacturer Recommendation.vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module etc. and all these components should be of same brand. |
| 11 | TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system.2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done. |
| 12 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 13 | Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. Please Enable Macros to View BoQ information |