| 1 | SITC of automatic Lift (as per manufacturer design as per detailed spectfication below and conforming to IS 17900) and putting into operation after final testing in the existing shaft complete with all accessories and reparing the damaged wall /floor if any etc to complete as required. |
| 2 | Make:- OTIS/KONE/SCHINDLER |
| 3 | Type : Passenger Lift (MRL) |
| 4 | Load : 16 Passenger /1088 Kg. |
| 5 | Control: Microprocessor based with AC Variable Voltage & Variable frequency (VVVF) |
| 6 | Machine: Energy Efficient Machine ; Gearless, without Machine Room. |
| 7 | Speed : 1.0 Mtr. /Sec. |
| 8 | Floor Served : G + 4 |
| 9 | Landing : 5(Five) lands ; All on same sides |
| 10 | Total Rise : 20 Mtr. (Approx)[Bidder should follow the CGA drawing/ Visit the site, as applicable] |
| 11 | Operation : Microprocessor based Duplex full collective with or without attenedant. |
| 12 | Signals : Digital Car postion indicator, car travels direction indicator in car and at all landing with call registration indicator.COP & LOP must have stainless steel face plate silver brushed with surface mounted button with braille.Button : All buttons on car & landing shall be luminous & encoded with braille on/off switch for Lift, fan, light, toggle switch or key switch for automatic/attendent mode of operation.Display type : Monochrome/ Colour LCD / Segmented LCD/ Scroll.Operation Push Buttom for lift maintenance & service should be on top of the car. |
| 13 | Travelling Accuracy: ± 5mm (Micro Levelling Arrangement) |
| 14 | CAR :- |
| 15 | Car Inside : 1600 mm (W) X 1600 mm (D) × 2400 mm (H) |
| 16 | Car Entrance : Clear Opening 1000 mm (W) X 2200 mm (H) protected with car door. |
| 17 | Car Encloser: Stainless Steel Sheet (20SWG) with hair line finish with hand rail. |
| 18 | Car Ceiling & Lighting : Stainless Steel with hair line finish with LED Lighting & Fan. |
| 19 | Car Ventilation : Axial fan with anodised aluminium / SS grill. |
| 20 | Car Flooring : Decorative Granite Flooring (As per direction of EIC and according to departmental order.) |
| 21 | Car Door : Stainless Steel Centre Opening (COPD) / Telescopic Opening (TSPD) automatic door provided with V3F controlled door drive system. |
| 22 | Landing Door: Stainless Steel Centre Opening (COPD) / Telescopic Opening (TSPD) automatic door provided with V3F controlled door drive system with fire rating of 120 min. |
| 23 | Door Opening: Automatic Power operated door with full length photocell assembly curtain sensor. |
| 24 | PROTECTIVE DEVICES & OTHER ACCESSORIES :- |
| 25 | ARD: Automatic rescue device complete with dry maintenance free batteries as required for automatic evacuation to the nearest floor in case of power failure / single phasing/others. |
| 26 | Overload Protection:Fully loaded with overload protection.On overloading condition the lift car will not start with door remaining open and give audio & display indication. |
| 27 | Emergency Lighting In Car: Battery operated emergency lighting in the lift car. |
| 28 | Intercom System: Battery operated Intercom System in Lift Car, Machine Room & Control Room. |
| 29 | Emergency Alarm: Battery Operated alarm bell system in Lift Car & Control Room. |
| 30 | Fireman switch : Fireman switch placed at ground floor. |
| 31 | Voice Synthesizer: Voice announcement system (Voice Synthesizer) in the car to announce the position of the elevator in the hoist way as the car passes or stops at a floor served by the lift. |
| 32 | Car Parking at top floor at idle condition. |
| 33 | Main Wire Rope/ Belt : As per manufacturer's standard conforming to IS-17900 |
| 34 | Auto fan Cut-Off |
| 35 | DIMENSION OF SHAFT & POWER SUPPLY :- |
| 36 | Available Shaft Dimension: 2300 mm (W) X 2300 mm (D) |
| 37 | Pit Depth: 1600mm ( Bidder should visit the site) |
| 38 | Overhead: 5100mm ( Bidder should visit the site) |
| 39 | Electric power supply: AC 415V, 3Phase, 50Hz terminated in machine room as per IS. |
| 40 | External Monitoring system through MOD BUS RS485. |
| 41 | MINOR MASONARY WORK :- |
| 42 | If the gap between the door frame and wall structure is up to ± 50 mm then the cost should include the required minor masonary works needed to plug the gap , if necessary, as per direction of EIC. |
| 43 | SITC of automatic Lift (as per manufacturer design as per detailed spectfication below and conforming to IS 17900) and putting into operation after final testing in the existing shaft complete with all accessories and reparing the damaged wall /floor if any etc to complete as required. |
| 44 | Make:- OTIS/KONE/SCHINDLER |
| 45 | Type : Passenger Lift (MRL) |
| 46 | Load : 8 Passenger /544 Kg. |
| 47 | Control: Microprocessor based with AC Variable Voltage & Variable frequency (VVVF) |
| 48 | Machine: Energy Efficient Machine ; Gearless, without Machine Room. |
| 49 | Speed : 1.0 Mtr. /Sec. |
| 50 | Floor Served : G + 4 |
| 51 | Landing : 5(Five) lands ; All on same sides |
| 52 | Total Rise : 20 Mtr. (Approx)[Bidder should follow the CGA drawing/ Visit the site, as applicable] |
| 53 | Operation : Microprocessor based Duplex full collective with or without attenedent. |
| 54 | Signals : Digital Car postion indicator, car travels direction indicator in car and at all landing with call registration indicator.COP & LOP must have stainless steel face plate silver brushed with surface mounted button with braille.Button : All buttons on car & landing shall be luminous & encoded with braille on/off switch for Lift, fan, light, toggle switch or key switch for automatic/attendent mode of operation.Display type : Monochrome/ Colour LCD / Segmented LCD/ Scroll.Operation Push Buttom for lift maintenance & service should be on top of the car. |
| 55 | Travelling Accuracy: ± 5mm (Micro Levelling Arrangement) |
| 56 | CAR :- |
| 57 | Car Inside : 1100 mm (W) X 1300 mm (D) × 2400 mm (H) |
| 58 | Car Entrance : Clear Opening 800 mm (W) X 2200 mm (H) protected with car door. |
| 59 | Car Encloser: Stainless Steel Sheet (20SWG) with hair line finish with hand rail. |
| 60 | Car Ceiling & Lighting : Stainless Steel with hair line finish with LED Lighting & Fan. |
| 61 | Car Ventilation : Axial fan with anodised aluminium / SS grill. |
| 62 | Car Flooring : Decorative Granite Flooring (As per direction of EIC and according to departmental order.) |
| 63 | Car Door : Stainless Steel Centre Opening (COPD) / Telescopic Opening (TSPD) automatic door provided with V3F controlled door drive system. |
| 64 | Landing Door: Stainless Steel Centre Opening (COPD) / Telescopic Opening (TSPD) automatic door provided with V3F controlled door drive system with fire rating of 120 min. |
| 65 | Door Opening: Automatic Power operated door with full length photocell assembly curtain sensor. |
| 66 | PROTECTIVE DEVICES & OTHER ACCESSORIES :- |
| 67 | ARD: Automatic rescue device complete with dry maintenance free batteries as required for automatic evacuation to the nearest floor in case of power failure / single phasing/others. |
| 68 | Overload Protection:Fully loaded with overload protection.On overloading condition the lift car will not start with door remaining open and give audio & display indication. |
| 69 | Emergency Lighting In Car: Battery operated emergency lighting in the lift car. |
| 70 | Intercom System: Battery operated Intercom System in Lift Car, Machine Room & Control Room. |
| 71 | Emergency Alarm: Battery Operated alarm bell system in Lift Car & Control Room. |
| 72 | Fireman switch : Fireman switch placed at ground floor. |
| 73 | Voice Synthesizer: Voice announcement system (Voice Synthesizer) in the car to announce the position of the elevator in the hoist way as the car passes or stops at a floor served by the lift. |
| 74 | Car Parking at top floor at idle condition. |
| 75 | Main Wire Rope/ Belt : As per manufacturer's standard conforming to IS-17900 |
| 76 | Auto fan Cut-Off |
| 77 | DIMENSION OF SHAFT & POWER SUPPLY :- |
| 78 | Available Shaft Dimension: 1900 mm (W) X 1900 mm (D) |
| 79 | Pit Depth: 1600mm ( Bidder should visit the site) |
| 80 | Overhead: 5100mm ( Bidder should visit the site) |
| 81 | Electric power supply: AC 415V, 3Phase, 50Hz terminated in machine room as per IS. |
| 82 | External Monitoring system through MOD BUS RS485. |
| 83 | MINOR MASONARY WORK :- |
| 84 | If the gap between the door frame and wall structure is up to ± 50 mm then the cost should include the required minor masonary works needed to plug the gap , if necessary, as per direction of EIC. |
| 85 | SITC of automatic Lift (as per manufacturer design as per detailed spectfication below and conforming to IS 17900) and putting into operation after final testing in the existing shaft complete with all accessories and reparing the damaged wall /floor if any etc to complete as required. |
| 86 | Make:- OTIS/KONE/SCHINDLER |
| 87 | Type : Bed-Cum-Passenger Lift (MRL) |
| 88 | Load : 15 Passenger /1020 Kg. |
| 89 | Control: Microprocessor based with AC Variable Voltage & Variable frequency (VVVF) |
| 90 | Machine: Energy Efficient Machine ; Gearless, without Machine Room. |
| 91 | Speed : 1.0 Mtr. /Sec. |
| 92 | Floor Served : G + 4 |
| 93 | Landing : 5(Five) lands ; All on same sides |
| 94 | Total Rise : 20 Mtr. (Approx)[Bidder should follow the CGA drawing/ Visit the site, as applicable] |
| 95 | Operation : Microprocessor based Duplex full collective with or without attenedent. |
| 96 | Signals : Digital Car postion indicator, car travels direction indicator in car and at all landing with call registration indicator.COP & LOP must have stainless steel face plate silver brushed with surface mounted button with braille.Button : All buttons on car & landing shall be luminous & encoded with braille on/off switch for Lift, fan, light, toggle switch or key switch for automatic/attendent mode of operation.Display type : Monochrome/ Colour LCD / Segmented LCD/ Scroll.Operation Push Buttom for lift maintenance & service should be on top of the car. |
| 97 | Travelling Accuracy: ± 5mm (Micro Levelling Arrangement) |
| 98 | CAR :- |
| 99 | Car Inside : 1100 mm (W) X 2150 mm (D) × 2400 mm (H) |
| 100 | Car Entrance : Clear Opening 900 mm (W) X 2200 mm (H) protected with car door. |
| 101 | Car Encloser: Stainless Steel Sheet (20SWG) with hair line finish with hand rail. |
| 102 | Car Ceiling & Lighting : Stainless Steel with hair line finish with LED Lighting & Fan. |
| 103 | Car Ventilation : Axial fan with anodised aluminium / SS grill. |
| 104 | Car Flooring : Decorative Granite Flooring (As per direction of EIC and according to departmental order.) |
| 105 | Car Door : Stainless Steel Centre Opening (COPD) / Telescopic Opening (TSPD) automatic door provided with V3F controlled door drive system. |
| 106 | Landing Door: Stainless Steel Centre Opening (COPD) / Telescopic Opening (TSPD) automatic door provided with V3F controlled door drive system with fire rating of 120 min. |
| 107 | Door Opening: Automatic Power operated door with full length photocell assembly curtain sensor. |
| 108 | PROTECTIVE DEVICES & OTHER ACCESSORIES :- |
| 109 | ARD: Automatic rescue device complete with dry maintenance free batteries as required for automatic evacuation to the nearest floor in case of power failure / single phasing/others. |
| 110 | Overload Protection:Fully loaded with overload protection.On overloading condition the lift car will not start with door remaining open and give audio & display indication. |
| 111 | Emergency Lighting In Car: Battery operated emergency lighting in the lift car. |
| 112 | Intercom System: Battery operated Intercom System in Lift Car, Machine Room & Control Room. |
| 113 | Emergency Alarm: Battery Operated alarm bell system in Lift Car & Control Room. |
| 114 | Fireman switch : Fireman switch placed at ground floor. |
| 115 | Voice Synthesizer: Voice announcement system (Voice Synthesizer) in the car to announce the position of the elevator in the hoist way as the car passes or stops at a floor served by the lift. |
| 116 | Car Parking at top floor at idle condition. |
| 117 | Main Wire Rope/ Belt : As per manufacturer's standard conforming to IS-17900 |
| 118 | Auto fan Cut-Off |
| 119 | DIMENSION OF SHAFT & POWER SUPPLY :- |
| 120 | Available Shaft Dimension: 1800 mm (W) X 3000 mm (D) |
| 121 | Pit Depth: 1600mm ( Bidder should visit the site) |
| 122 | Overhead: 5100mm ( Bidder should visit the site) |
| 123 | Electric power supply: AC 415V, 3Phase, 50Hz terminated in machine room as per IS. |
| 124 | External Monitoring system through MOD BUS RS485. |
| 125 | MINOR MASONARY WORK :- |
| 126 | If the gap between the door frame and wall structure is up to ± 50 mm then the cost should include the required minor masonary works needed to plug the gap , if necessary, as per direction of EIC. Defect Liability Period (DLP): 3 (Three) years from the date of Completion. |