| 1 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector ( VDS / UL / LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector is to be provided without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. Degree of protection as per OEM Standard. (Make: Esser/Cerberus Pro/ Bosch/Johnson Controls/Notifer /Edward /Secutron / Securiton /Apollo / Morley / System Sensor) |
| 2 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / LPCB / FM approved ) with in built short circuit fault isolator as per NFPA (Note : MCP without built-in fault isolator is also acceptable with one independent short circuit fault isolator is to be provided without extra cost). Degree of protection as per OEM Standard. (Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer/ Edward /Secutron/Securiton/Apollo/Morley/System Sensor.) |
| 3 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered /panel powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator as per NFPA (Note :Hooter without built-in fault isolator is also acceptable with one independent short circuit fault isolator is to be provided without extra cost). ( VDS / UL / LPCB / FM approved ) approved. Degree of protection as per OEM Standard.(Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward / Secutron / Securiton/Apollo/Morley/System Sensor) |
| 4 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector ( VDS / UL / LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 58 deg. C to 68 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector in the loop is to be provided without extra cost) the detectors should have built in response indicator with LED indicator.Degree of protection as per OEM Standard.(Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer/ Edward / Secutron / Securiton /Apollo/Morley/System Sensor.) |
| 5 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box with metallic cover having two LED and Degree of protection as per OEM Standard etc. complete with all connections etc as required. (Make: Esser/Cerberus Pro/ Bosch/Johnson Controls/Notifer / Edward/ Secutron/ Securiton/ Apollo/Morley /System Sensor.) |
| 6 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded Copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall. (Make: Finolex/RR Kable/Polycab) |
| 7 | Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion.Four Loop Panel.(Make: Esser/Cerberus Pro/Bosch/Johnson Controls/Notifer / Edward / Secutron Securiton/Apollo / Morley /System Sensor) |
| 8 | NOTE :- 1) The Fire Alarm system shall comply with latest requirements of --(i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 ,(iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand. |
| 9 | TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done. |
| 10 | TERMS & CONDITIONS :-1) The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products at least five (05)years from the date of installation.2) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.If any refurbished material is supplied and installed, penal action will be taken as per existing rules |