| 1 | Supply and installation of glass protection cover of existing Addressable Manual Call Point with in built fault isolator in replacement of old damaged one. |
| 2 | Heating and Photo Electric Chamber rectification of dismelted detector and re-installation. |
| 3 | Supply, Installation, Testing & Commisioning of Micropresssor controlled Addressable Multisensor Detector IP-42 ( UL/EN approved ) with inbuilt twin angle optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : As existing Detector point approved by EIC) |
| 4 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded Copper Cable (For Loop) ( Make. Finolex / Gloster / Ampree/RR Kable / Polycab ) through 20 mm dia PVC 'FR' MMS type Rigid Conduit pipe & shaddles with all necessary arrangement as per G.S. (Make : Precision/AKG) on the surface of the wall. |
| 5 | Checking, Tessting, Re-programming and Re-commissioning of existing Microprocessor based Intelligent, addressable existing 2 / 4 / 6 / 8 loop fire alarm control panel ( UL/EN approved ) and done total system healthy with all detector and hooter of Burdwan Medical College & Hospital, Purba Bardhaman. (Make of FD Panel : Securiton/Edward Make |
| 6 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point complete with in built short circuit fault isolator as per NFPA style 7 wiring complete as required (UL/EN approved ). (Approved Make : As existing Hooter brand approved by EIC ) |
| 7 | Supply, Installation,Testing & Commisioning of Addressable Loop Powered Hooter (sound output of minimum 90 dB) cum strobe (strength of light 10 cd) complete with in built short circuit fault isolator as per NFPA style 7 wiring complete as required (UL/EN approved ). (Approved Make : As existing Hooter brand approved by EIC ) |
| 8 | Supply, Installation,Testing & Commisioning of Addressable Input/Output Module for Hooter as required (UL /EN approved ). (Approved Make : As existing Hooter brand approved by EIC ) |
| 9 | Supply and installation of 12 Volt 7Ah capacity VRLA Battery of Lead Acid, Sealed Maintenance Free (SMF) and conforming to relevant IS Specification with Low / High Battery Voltage and Weak Battery warning [ Make- Exide or equivalent model of Amaron / Luminous ] for the existing fire alarm control panel in replacement of old defective one. |
| 10 | SITC of offline UPS 1KVA, with inbuilt battery, 800 Watt for the whole system (APC/Microtek/VERTIV). |
| 11 | Supply & Installation of Control Module with 24V SMPS for hooter with all other necessary accessories. Wattage ratting as per existing. (Compatible with Same as existing hooter : brand approved by EIC ) |
| 12 | Checking, Testing, Re-programming and Re-commissioning of existing Microprocessor based intelligent, addressable and network connected Repeater Panel ( VDS / UL /ERTL/ LPCB/ FM approved) and done total system healthy incl all accessories. (Make of Repeater Panel : Siemens Make or same as existing detector brand approved by EIC ) |
| 13 | Cost for periodical checking & maintenance arrangement by deputing 3 Technician Round-O-clock through day/night per month through-out the year for cleaning of all detector MCP and trobleshooot the fault if anything happened throughout the year under of supervision of agency, as & when informed by concerned AE / JE should be carried out for 1 (one) year after the date of completion of the total Cleaning, Checking, Testing, Re-programming and Re-commissioning job at different buildings in the campus of Burdwan Medical College & Hospital, Purba Bardhaman. |
| 14 | Cost of Half yearly Re-checking of Faulty or damage device and Re-commissioning the in of All panels in provision of AMC. Total panel quantity 8 Nos. |
| 15 | NOTE : The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Original Equipment Manufacturer (OEM) Recommendation. |
| 16 | TESTS:1.The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer /OEM of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done. |
| 17 | Scope of Testing, checking, commissioning of Fire alarm panel (As per Sl. No. 5 & 11 ) should cover the following, |
| 18 | i) To provide detail schematic network diagram along with IP address, position of the detectors, manual call points etc. connected with fire alarm panel. |
| 19 | ii) To provide operation manual, method of trouble shooting, fetching the log record of fire alarm monitoring from the e-prom of the fire alarm panel. |
| 20 | iii) To provide intrinsic training to the JE and AE to make them well conversant about the installation. |
| 21 | iv)To provide login credentials of the executable program for replacing a faulty fire detector or making changes in IP address. |
| 22 | v) To provide suggestion to upgrade the fire alarm system, method of public announcing for evacuation and recommendation for awareness in general. |
| 23 | vi) Checking and testing of network cables for its continuity and insulation and transmission as well as receiving data. Please Enable Macros to View BoQ information |