| 1 | [13.27]Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 2 | [13.32]Providing and fixing bolts including nuts and washers complete. |
| 3 | [24.1.1]EARTHING AND LIGHTENING ARRESTOR Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. |
| 4 | [24.1.2]EARTHING AND LIGHTENING ARRESTOR. Extra for using salt and char coal/coke for pipe earth electrode as required. |
| 5 | [24.1.8]EARTHING AND LIGHTENING ARRESTOR. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. |
| 6 | [24.2.1]LT CABLE. Supply & erection of LT phase separator on LT line complete in all respect up to entire satisfaction of the Engineer-in-charge of the work. |
| 7 | [24.2.8.14]LT CABLE. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work.300 sqmm |
| 8 | [24.5.2.3]MISCELLANEOUS ITEMS. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 63/50 mm outer dia/inner dia |
| 9 | [23.22.1.10]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 125 to 160 amp, 25 KA |
| 10 | [23.22.5.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. Single Pole |
| 11 | [23.26.2]SAFETY ITEMS Supply and erection of High Tension Voltage caution notice plate of size 250*200 mm in three languages. |
| 12 | [23.27.2]Supply and erection of Godrej Almirah typeM.S. pedestal made of 50 mm x 50 mm x 6 mm angle iron frame with 3.00 mm thick M.S. sheet covering including shutters with suitable hinges and locking arrangement with Godrej type handle including round bars . The top covering should have downward overhang of 75 mm on all sides of pedestal , having two sets of water proof ventilation holes of suitable size on the sides , at top and bottom , each set containing four Nos. holes to discharge the heat produced by the current . The shutters fixed with rubber gasket of superior quality and of suitable size to make it water proof . The pedestal duly painted both inside and outside with two coats of approved paint and primary coat and its legs are embeded upto the entire depth in 1:2:4 cement concrete block , projected 75 mm all around the pedestal and and 200 mm above the ground level including the cost of all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work:- M.S. pedestal of size 750 mm wide , 900 mm high , 300 mm deep and bottom totally open , duly embeded in cement concrete block of size 900 mm x 450 mm x 200 mm above ground level , having a base of size 1050 mm x 600 mm x 250 mm below ground level . |
| 13 | [34.29.3]GI barbed wire fencing. Fencing With Welded Steel Wire Fabric 75 mm x 50 mm Providing 1.20 metre high fencing with angle iron posts 50 mm x 50 mm x 6 mm at 3 metre centre to centre with 0.40 metre embedded in M15 grade cement concrete, corner, end and every 10th post to be strutted, provided with welded steel wire fabric of 75 mm x 50 mm mesh or 75 mm x 25 mm mesh and fixed to iron posts by flat iron 50 x 5 mm and bolts etc. complete in all respects. i) Adopt any one type of welded steel wire fabric 75 x 50 mm or 75 x 25 mm as per approved design. ii) The item of excavation and cement concrete in foundation shall be measured and paid separately |
| 14 | [24.13.24]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK . 16 Sq mm 4 core (Arm.) |
| 15 | NS) Supply and erection of 300 sqmm x 1 core alum. Conductor PVC insulated cable as per ISS : 1554/P-I complete in all respect upto the entire satisfaction of engineer-in charge of work.(.Make Havells,Polycab.Grandly ) |
| 16 | NS) Supply and erection of ACSR conductor conforming to IS 398 (Part-II) 1976/1996, IS 4826-1976 IS 1521-1972 and IS 1778-1980 with latest amendments and erection of the same with accessories including stringing and sagging of conductor of various sizes i.e. 100mm2 as well as jointing and binding with insulator at supports in all respect up to the entire satisfaction of Engineer-in-Charge. |
| 17 | NS) Supply and erection of ACSR conductor conforming to IS 398 (Part-II) 1976/1996, IS 4826-1976 IS 1521-1972 and IS 1778-1980 with latest amendments and erection of the same with accessories including stringing and sagging of conductor of various sizes i.e. 80mm2 as well as jointing and binding with insulator at supports in all respect up to the entire satisfaction of Engineer-in-Charge. |
| 18 | NS) Supply and erection of ACSR conductor conforming to IS 398 (Part-II) 1976/1996, IS 4826-1976 IS 1521-1972 and IS 1778-1980 with latest amendments and erection of the same with accessories including stringing and sagging of conductor of sizes i.e. 30mm2 PVC insulated as well as jointing and binding with insulator at supports in all respect up to the entire satisfaction of Engineer-in-Charge. |
| 19 | NS) Supply and erection of H.T. Stay Set for HT Line complete in all respect with G.I. stay wire( rope of 7 wires of 8 SWG G.I. Wire), egg/Disc insulator , G.I. rod of 20mm dia, 8’ long threaded up-to 250mm long with nut (weight 6.224 kg) with cross of angle of 450mm each made out angle of size 65x65x6 mm(weight 5.33 kg), elbow (weight 2.24 kg ) complete with clamps , nuts and bolts complete in all respect up-to the entire satisfaction to Engineer-in-Charge of the work. |
| 20 | NS) Supply and erection of L.T. stay set for LT Line complete in all respect with G.I. stay wire( rope of 7 wires of 8 SWG G.I. Wire), egg/Disc insulator , G.I. rod of 20mm dia, 8’ long threaded up-to 250mm long with nut (weight 6.224 kg) with cross of angle of 450mm each made out angle of size 65x65x6 mm(weight 5.33 kg), elbow (weight 2.24 kg ) complete with clamps , nuts and bolts complete in all respect up-to the entire satisfaction to Engineer-in-Charge of the work. |
| 21 | NS) Supply and erection of Fuse unit of L.T. side suitable for 25 KVA to 200 KVA transformer complete with wooden board, aluminum strips, MS clamps and nut and bolts including all petty material required up-to the entire satisfaction of Engineer-in-Charge. |
| 22 | NS) Supply and Erection of 11 KV G.O. Switch vertical mounted with heavy duty 9 Nos. post insulators suitable, for copper male and female contacts fixed on GI angle frame with G.I. Nut and Bolts including G.I. pipe and operating handle complete in all respect |
| 23 | NS) Supply and erection of 11 KV lighting arrestor set (L.A. Set) as per relevant ISS specification. |
| 24 | NS) Supply and erection of top hamper suitable for 11 Mtr. long PCC pole and 11KV system made out of MS flat size 50x6mm (A shapes) having approx weight 2.5 kg as per approved design and drawing including primer and alum paint complete all respect. |
| 25 | NS) Supply and erection of 11 KV pin insulator polymeric type 10 KN with GI pin as per specification and approved make by DHBVN. |
| 26 | NS) Supply and erection of 11 KV Disc insulator polymer type with fitting on PCC pole of approved make of State Electricity Nigam requirement to complete in all respect to confirming to ISS 731/1971 latest amendment thereto. |
| 27 | NS) Supply and erection of cradle guard For HT 11 KV Line made of 8 S.W.G. confirming to ISS 280/1978/1973 with latest amendments complete in all respect up to the entire satisfaction of Engineer-in-Charge. |
| 28 | NS) Supply and erection of Anti climbing barbed wire of size 12x12 gauge (6.33 Mtr. = 1.00 kg) for 11 KV/33KV Poles complete in all respect. |
| 29 | NS) Supply and Erection of P.G Clamp suitable for 50/80/100 Sqmm ACSR conductor made out of aluminium die cast with nut and bolts complete in all respect upto the entire satisfaction of the Engineer-in-charge of the work. |
| 30 | NS) Supply and erection of PCC pole 11 mtr long as per IS: 1678-1960 specifications, 140mm x 200mm at top and 140mm x 400mm at bottom with working load of 400Kg buried 2.20M in ground or as per DHBVNL specification |
| 31 | NS) Supply, Stringing and Sagging 8 SWG G.I. Earth wire complete in all respect to the entire satisfaction of Engineer-in-charge conforming to IS 298/1978 and 7807/1973 and with latest amendment thereof. |
| 32 | NS) Supply and Erection of M.S. D-strap made out of M.S Flat of size 40 x 6mm suitable for LT insulator 90mm x75mm with latest amendments complete in all respect up to the entire satisfaction of Engineer-In-Charge. |
| 33 | NS) Supply and erection of 32 mm dia G.I. pipe bracket 1.0 mtr long made out of 32mm nominal dia (B-class) suitable for street light fitting including 2 nos. Clamps of M.S. Flat size 50x6mm, 6 nos. Nutt and Bolts of size 50x16mm with application of primer and painting complete in all respect up to the entire satisfaction of Engineer-in-Charge. |
| 34 | NS) Supply, installation, testing, commissioning of 200 KVA Transformer, 3 Phase 11KV/0.433 KV, Oil immersed, naturally cooled, Aluminum Wound Outdoor type Distribution Transformers with CSP (Completely self protected) features with external micro-processor based four pole MCCB 300Amp. To 400 Amp, 50kA strictly conforming to Nigam’s technical specification No. CSC-V/R-I/DH/UH/P and D/2010-2011 read with amendment thereof and as per relevant ISS as amended from time to time and losses conforming to 4 stars rating of BEE as per Approved Specification of DHBVN/UHBVN including installation of transformer on existing platform up-to the entire satisfaction of Engineer-in-Charge.Voltage Rated Frequency Permitted at 75ºCi) Maximum load looses at 50% load at 75ºC = 780 Watt ii) Maximum losses at 100% load at 75ºC = 2300 Wattiii) Warranty = 78/72 Months shall be one time The above losses are maximum allowable and there would not be any positive tolerance. |
| 35 | NS) Supply and erection of L.T. Aerial bunched cable of size 120 Sqmm X 4 core with messenger conductor of size 95 Sqmm single core including making of necessary connection complete in all respect up to the entire satisfaction of Engineer-in-charge. |
| 36 | NS) S/E of 25 Watt LED Street Light Luminaries with multiple highly efficient LED’s, with individual lens, with reflector, Pressure die cast aluminum housing, heat resistant, enclosed in Poly carbonate/toughened glass IP-66, having light efficacy 120 Lumens/watt of complete in all respect as per specifications attached complete up to the entire satisfaction of Engineer -in-charge of the work. (With 3 years free replacement warranty at site including labour charges free of costMake:-Bajaj/Philips/ LT |
| 37 | NS) Supply and erection of 25 mm dia G.I. pipe bracket 1.0 mtr long made out of 32mm nominal dia (B-class) suitable for street light fitting including 2 nos. Clamps of M.S. Flat size 50x6mm, 6 nos. Nutt and Bolts of size 50x16mm with application of primer and painting complete in all respect up to the entire satisfaction of Engineer-in-Charge. |
| 38 | NS) S/E of 72 Watt LED Street LightLuminaries with multiple highly efficient LED’s, with individual lens, with reflector, Pressure die cast aluminum housing, heat resistant, enclosed in Poly carbonate/toughened glass IP-66, having light efficacy 120 Lumens/watt of complete in all respect as per specifications attached complete up to the entire satisfaction of Engineer -in-charge of the work. (With 3 years free replacement warranty at site including labour charges free of cost).Make:-Bajaj/Philips/ LT |
| 39 | NS) Supply and erection of wooden cleats made out of good quality of wood complete with 4 Nos. grooves suitable to pass through 300/400sqmm single core cable complete in all respect up to the entire satisfaction of Engineer-in-charge. |
| 40 | NS) Supply and erection of PCC pole 9 mtr long as per IS: 1678-1960 specifications, 105mm x 115mm at top and 105mm x 315mm at bottom with working load of 200 Kg. buried 1.80m in ground or as per DHBVNL specification |
| 41 | NS) S/E of shackle insulator brown glazed of size 90 mm x 75 mm suitable for 415 /240 Volt confirming to IS 1545/1977 with latest amendment thereofcomplete in all respect up to the entire satisfaction of Engineer-In-Charge. |
| 42 | NS) Supply and erection of Cradle guard for L.T. Line made out of 8 S.W.G. G.I. wire and guard reel complete in all respect up to the entire satisfaction of Engineer-in-Charge |
| 43 | NS) Supply and erection of 2.5sqmm 3 core aluminum flexible cable PVC insulated and sheathed core round/flat cable 1100 volts each core having single solid aluminium conductor as per IS: 694, complete in all respect up to entire satisfaction of the Engineer-in-Charge of the work. Make – Havells/ polycab/ grandlay or make approved by DHBVN |
| 44 | NS) Supply and erection of V-shape cross arm suitable for 11KV system made of out of 1650mm long MS channel of size 100x50x50x6mm as per design and drawing 2 Nos. 18mm dia holes provided in the base for fixing of half clamp made of MS flat of size 50x6mm and 2 Nos. holes 22mm dia for GI Pin on the flange plate of MS Flat of size 50x6mm shall be provided on the top and bottom flanges of both end of V-shape X-arm with 22mm hole in the plate complete in all respect including primer and aluminum paint. |
| 45 | NS) Supply and erection of 50 Sqmm single core aluminum cable, PVC insulated,unsheathed, 1100 volt grade loose in existing pipe or trenches complete in all respect up to entire satisfaction of the Engineer-in-Charge of the work. Please Enable Macros to View BoQ information |