| 1 | 1. Electrification. |
| 2 | 90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture |
| 3 | 90.3.20.4:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 2X20W LED Lamp with box type fixture |
| 4 | 90.3.22.3:Supply & installation of light fittings on flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made of CRCA sheet of .5mm thickness complete with all accessories and lamps etc. directly on wall using 2 nos. flat iron brackets made from 25x6mm flat iron, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture |
| 5 | 90.3.24.3:Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture |
| 6 | 90.3.10:Supplying and providing extra H.G conduit down rod of 19 mm dia 2 x 1.00 m long with 16/0.20 mm 3 core copper conductor flex wire conforming to relevant ISS or with the extended original wiring and giving connection etc. as required. |
| 7 | OD452768/2025-2026:Supply and fixing polyster powder coated hexagon shaped pressure die cast aluminium housing in metallic grey finish bulk head back -lit LED luminaire comprising high brightness 10w high efficiency long life LED module with SMD LED package mounted on MCPCB, powered by integral electronic LED drive with APFC with low THD out put short/open circuit protection and 4kV inbuilt surge protection. Lumen efficacy of LED >_ 140 lm/w, high quality polycarbonate UV protected diffuser in opel finish for glare free light distribution. IP 66 (Havells HEXAFT10WLED857SSYMBOPC/ EQUIVELENT MAKE) to wall/ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required. |
| 8 | OD452770/2025-2026:Supply, conveyance and fixing 6w LED Energy Surface mounding Round Panel light fittings in the existing ceiling LEPSRR06 LUKER or equivalent make and giving connections etc as required including all labour charges. |
| 9 | OD452767/2025-2026:Supply Conveyance, installation, testing and commissioning of 30W LED Flood light, output 100 lumen/W 6500K with IP 66 protection with power factor 0.90 at full load, internal surge protection up to 4 KV and Aluminium pressure die-cast Powder coated housing, acrylic cover complete duly wired up for use on 230 V AC supply. Driver compartment should be separately accessible for maintenance. (Bajaj GLATT MT 36L WHPOP PC SD / Equivelent make) |
| 10 | OD452772/2025-2026:Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. 200 mm sweep Light Duty Exhaust fan in plastic body with self opening lowers working on 230V single phase A/C. |
| 11 | 90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required. |
| 12 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 13 | OD452773/2025-2026:Supply and providing every additional length of down rod of 15mm heavy gauge GI / WI pipe with 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming in relevant ISS or with original wiring extended including painting as required. |
| 14 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 15 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 16 | 90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid |
| 17 | 90.9.1.7:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap |
| 18 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 19 | 1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm |
| 20 | 1.17.27:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 4 sq. mm |
| 21 | OD452490/2025-2026:Supply and fixing 2 Nos. 2 MD Metal box with 2 Nos. white front plate on 1 No. 20A modular type DP Switch with indicator and 25A shuttered socket, earthing make good the damages color washing etc as required on recess as power plug(ROHS) for A / C |
| 22 | 90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43) |
| 23 | 90.11.1.19:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 24 | OD452817/2025-2026:Supplying and fixing 40 amps to 63 amps rating,415 volts, "C" curve,10 kA breaking capacity TPN miniature circuit breaker suitable for inductive load in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 25 | 90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 26 | 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 27 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 28 | OD452771/2025-2026:Supplying and fixing 40 amps to 63 amps rating,415 volts,"C" curve,10 kA breaking capacity TP miniature circuit breaker suitable for inductive load in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 29 | 90.12.5.30:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 70 sq mm |
| 30 | 90.12.7.30:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm |
| 31 | 9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm) |
| 32 | 90.12.10.3:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation63/50 mm or nearest size |
| 33 | 2.2.14:Providing and fixing following rating and breaking capacity MCCB withthermomagnetic release and terminal spreaders in existing cubicle panel boardincluding drilling holes in cubicle panel. making connections. etc. as required.125 Amp, 36 KA |
| 34 | 2.2.16:Providing and fixing following rating and breaking capacity MCCB withthermomagnetic release and terminal spreaders in existing cubicle panel boardincluding drilling holes in cubicle panel. making connections. etc. as required.250 Amp, 36 KA |
| 35 | OD452834/2025-2026:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2 metre long etc. with charcoal/ coke as required. |
| 36 | OD452832/2025-2026:Supply and providing earth lead from the test joint to the earth electrode using 25 x 3 mm GI strip of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate,test joint etc. as required. |
| 37 | OD452833/2025-2026:Providing and fixing 2x25mmx 3mm GI strip test joint for earthing system. |
| 38 | 90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 39 | 90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class) |
| 40 | 90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG) |
| 41 | OD452840/2025-2026:Supply and providing 25 x 6 mm brass nut and bolt etc.as required. Please Enable Macros to View BoQ information |