| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Colour Coding of wires RYB should be maintain)Havells/Polycab/RR Kabel/Finolex |
| 2 | Group C |
| 3 | Wiring for Light/Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required. (Colour Coding of wires RYB should be maintain)Havells/Polycab/RR Kabel/Finolex |
| 4 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required. (Colour Coding of wires RYB should be maintain)Havells/Polycab/RR Kabel/Finolex |
| 5 | 2 X 1.5 sq. mm 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 8 | 4 X 10.0 sq. mm + 2 X 6.0 sq. mm earth wire |
| 9 | 4 X 16.0 sq. mm + 2 X 6.0 sq. mm earth wire |
| 10 | Supplying and fixing of following size medium class PVC condute along with assories in surface/recess including cutting the wall and making good the same in case of recessed condute as required |
| 11 | 20 mm |
| 12 | 25 mm |
| 13 | 32 mm |
| 14 | 40 mm |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 16 | Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 5/6 and 15/16 amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required. |
| 17 | Supplying and Fixing following modular switch and socket on the existing modular & switch box including connections but excluding modular plate etc as required. |
| 18 | 5/6 Amp Switch |
| 19 | 3 pin 5/6 Amp Socket |
| 20 | Light indicator |
| 21 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 22 | Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required |
| 23 | Supplying and fixing following way, horizontal type three poleand neutral, sheet steel, MCB distribution board, 415 V, onsurface/ recess, complete with tinned copper bus bar, neutralbus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But withoutMCB/RCCB/Isolator) |
| 24 | 6 way (4 + 18), Double door |
| 25 | 4 way (4 + 12), Double door |
| 26 | Supplying and fixing 5 amps. to 32 amps.rating 240 volts 'C' series, miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 27 | Single Pole |
| 28 | Double pole |
| 29 | Supply and Fixing of following rating 4 Pole, 415 V, TPN MCB in the Existing MCB DB with connections, testing and commissioning complete as Required |
| 30 | Chemical Earthing Supply, installation, testing and commissioning of 75 mm GI Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. |
| 31 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 32 | Supply installation testing and commissioning of IP:20 Aluminium Batten 20W-22 W +- 1 W LED Surface Mounted 4 ftThe input voltage shall be 150 V to 270 V.The fixture should have inbuit surge protection of 2KV. |
| 33 | Supply installation testing and commissioning of IP20 led downlighter 15 W-18 W +/- 1 W LED Surface downlighter round shape with minimum system lumen efficacy of 100 lm/W. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. |
| 34 | Supply installation testing and commissioning of BLDC Ceiling Fan 1200 mm 230V 28 W with Speed RPM 350 with miimum Air delivery 220 CMM including wiring the down rods of standard length(Upto 30 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. |
| 35 | Supplying and fixing Stepped Type Electronic Fan Regulator on the existing Modular Plate Switch Box including Connections but Excluding Modular Plate etc. as Required |
| 36 | Supply,Installation,Testing and Commissioning 320 Cu.m/Hr. AC 220-240 Volts, 50 Hz exhaust fan made out of ABS Plastic Material with inbuilt thermo cutoff Protection and Noise Level not exceeding 37 dB of Following Sizes including connection etc. complete as required . |
| 37 | 300 mm |
| 38 | Supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42) (Main L.T Panel) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.5x6x1 = 1 Nos (Main Panel) |
| 39 | INCOMER |
| 40 | MCCB 125 A F.P 36 Ka with Adj. Thermal & Adj. magnetic release with Extendable ROH Icu=Ics=100% |
| 41 | Digital Metering Devices,comprising Voltmeter,Ammeter,Selector Switch,Indicating Lamps,C.T Set,Bus Bar(150 Amps) and MCB Strip of suitable size as Required. |
| 42 | OUTGOINGS |
| 43 | Manual Changeover 125 A F.P 415 V AC-23 Duty. |
| 44 | MCCB 63 A F.P 36 Ka \\"C\\" Curve |
| 45 | TPN MCB 63 A |
| 46 | TPN MCB 40 A, |
| 47 | MCB 32/20/16 A D.P 10 Ka \\"C\\" Curve |
| 48 | Size of wiring for CTS:- 2.5 sqmm |
| 49 | Size of wiring for voltage sensing Metering :-4.0 Sq.mm |
| 50 | Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm |
| 51 | Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5 sqmm.green copper flexible wire . |
| 52 | The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc. |
| 53 | Gland Plates to be 3.0 mm Thick. |
| 54 | Supplying,Installation,Testing and Commissioning of Cubical Type Outdoor Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System, Indicating Lamps as per the Following Description.2x2x1= 1 Nos (X-Ray Room)The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc. Gland Plates to be 3.0 mm Thick. |
| 55 | INCOMER/OUTGOINGS |
| 56 | MCCB 63 A F.P 36 Ka \\"C\\" Curve |
| 57 | Supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description. (1st Floor Panel) .4x3x1 = 1 Nos (Main Panel) |
| 58 | INCOMER |
| 59 | MCCB 63 A F.P 36 Ka with Adj. Thermal & Adj. magnetic release with Extendable ROH Icu=Ics=100% |
| 60 | Digital Metering Devices,comprising Voltmeter,Ammeter,Selector Switch,Indicating Lamps, C.T Set,Bus Bar and MCB Strip of suitable size as Required. |
| 61 | OUTGOINGS |
| 62 | TPN MCB 63 A |
| 63 | TPN MCB 40 A |
| 64 | MCB 32/20/16 A D.P 10 Ka \\"C\\" Curve |
| 65 | Size of wiring for CTS:- 2.5 sqmm |
| 66 | Size of wiring for voltage sensing Metering :-4.0 Sq.mm |
| 67 | Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm |
| 68 | Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5 sqmm.green copper flexible wire . |
| 69 | The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc. |
| 70 | Gland Plates to be 3.0 mm Thick. |
| 71 | Supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description. (2nd Floor Panel) .4x3x1 = 1 Nos |
| 72 | INCOMER |
| 73 | MCCB 63 A F.P 36 Ka with Adj. Thermal & Adj. magnetic release with Extendable ROH Icu=Ics=100% |
| 74 | Digital Metering Devices,comprising Voltmeter,Ammeter,Selector Switch,Indicating Lamps, C.T Set,Bus Bar and MCB Strip of suitable size as Required. |
| 75 | OUTGOINGS |
| 76 | TPN MCB 63 A, F.P |
| 77 | TPN MCB 40 A, F.P |
| 78 | MCB 32/20/16 A D.P 10 Ka \\"C\\" Curve |
| 79 | Size of wiring for CTS:- 2.5 sqmm |
| 80 | Size of wiring for voltage sensing Metering :-4.0 Sq.mm |
| 81 | Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm |
| 82 | Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5 sqmm.green copper flexible wire . |
| 83 | The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc. |
| 84 | Gland Plates to be 3.0 mm Thick. |
| 85 | Supplying and Laying of 1 No. DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refelling the Trench Etc.as Required . |
| 86 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 87 | Supplying and Laying of 1 No. PVC/XLPE insulated and PVC Sheathed /XLPE Power Cable of 1.1 KV Grade of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 88 | 3.5 C X 95 Sq.mm Aluminium Armoured |
| 89 | 3.5 C X 50 Sq.mm Aluminium Armoured |
| 90 | 3.5 C X 35 Sq.mm Aluminium Armoured |
| 91 | Supplying,Testing and Commissioning of 50 W LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt). |
| 92 | Supplying,Testing and Commissioning of 24 V 2.0 KVA Sine Wave Inverter paired with 2 Nos of Tall tubular inverter battery 160 Ah.Luminous/Exide/Microtek Please Enable Macros to View BoQ information |