| 1 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.d) Suitable cement concrete foundation duly plastered with anti vibration pads.2280 lpm at 56 m Head |
| 2 | Supplying, installation, testing and commissioning of Diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 2280 lpm at 56 m Head |
| 3 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325.M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 56 m Head |
| 4 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :INCOMING250A, 50kA 4 Pole MCCB, Ics=100% Icu ratingDigital Voltmeter 0-500V with selector switchDigital Ammeter (0-250 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, trip indicating lampsSet of Copper Bus Bar 300AOUTGOING( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)Main Fire Pump125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 5 | Jockey Pump63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.DIESEL ENGINE CONTROLControl for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller.Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification. |
| 6 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 7 | 25 mm dia |
| 8 | 32 mm dia |
| 9 | 40 mm dia |
| 10 | 50 mm dia |
| 11 | 80 mm dia |
| 12 | 100 mm dia |
| 13 | 150 mm dia |
| 14 | 200 mm dia (wall thickness 6.3 mm) |
| 15 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 16 | 150 mm. Dia |
| 17 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : |
| 18 | Single headed Stainless steel |
| 19 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 20 | 80 mm dia |
| 21 | 100 mm dia |
| 22 | 150 mm dia |
| 23 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/ gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required. |
| 24 | 150mm dia |
| 25 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange |
| 26 | 150mm dia |
| 27 | 100 mm dia |
| 28 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 29 | 100mm dia |
| 30 | 150 mm dia |
| 31 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
| 32 | Providing fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : |
| 33 | Pendent Sprinkler |
| 34 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 35 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc. as required.100mm dia |
| 36 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required:Stainless Steel (Grade 304) |
| 37 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585(b) 20 mm nominal internal dia gun metal globe valve & nozzle.(c) Drum and brackets for fixing the equipmets on wall.(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. a) 30 M |
| 38 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required. |
| 39 | Stainless Steel (Grade 304) |
| 40 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internalhydrants to reduce pressure at the outlet to the level of 3.5 kg /cm2 complete as required. |
| 41 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required:4 way - 150 mm dia M.S. Pipe |
| 42 | Providing and fixing weather proof lockable cabinet of size not less than size 750mm x 600mm x 250mm made out of MS sheet of 1.6 mm thickness having central opening and 4 mm thick glazed glass doors (Two nos.) suitably marked on the outside with the letters \\"FIRE HOSE\\" including necessary locking arrangement and shall be painted with duly painted with one coat of primer and 2 coats of synthetic enamel paint of post office red externally and white internally.The cabinet shall be suitable to accommodate 2 nos. 15 mtr long Hose pipe & 1 No branch pipe nozzle etc. complete as required. |
| 43 | Providing and fixing of photoluminescent signages of various matters/sizes in Aluminium sheet of 3mm thick with super extra glow based AUTOGLOW in-dark rigid sheet with high intensity luminous properties in a weatherproof UV stabilized coated aluminium sheet with UV screen printed by imported inks. Thickness 3 mm (+/-10%) service temp. -40c to +120c, visible up to more than 24hrs in total dark fungistatic, non-radioactive, contain no lead or phosphorous, no health or environmental problem, non-flammable, fixed on wall/ suspended with SS chain link complete as required. (matters & size as approved by Engineer-in-charge). |
| 44 | Single Sided |
| 45 | Double Sided |
| 46 | Providing and supplying arrow type signage/name board made of ACP (Aluminium Composite Panel) 3 mm thick sheet of approved colour and make, cut to required shape and size i/c surface preparation and application of self-adhesive vinyl /printed sticker lettering in English of approved colour and make etc. complete and all as per direction of Engineer-in-Charge. |
| 47 | Supplying & making end termination with brass compression gland and aluminium lugs for following sizes PVC Insulated & PVC sheathed XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 48 | 3 x 10 sq. mm (22 mm) |
| 49 | 3 x 35 sq. mm (28mm) |
| 50 | 3.5 x 25 sq. mm (28mm) |
| 51 | 3.5 x 50 sq. mm (32mm) |
| 52 | Supplying & laying of following sizes XLPE (cross linked polyethylene) insulated PVC sheathed, armoured with galvanised steel strip/galvanized round steel wire U.G. Cable with suitable for rated voltage of 1.1 KV grade and conforming to IS:7098 (Part-1) & having ISI marking as required. |
| 53 | 3 x 35 sq.mm (Aluminium) on surface |
| 54 | 6 x 2.5 sq. mm (copper) on surface |
| 55 | 3 x 6 sq. mm (Aluminium) on surface |
| 56 | 4 x 6 sq. mm (copper) on cable tray |
| 57 | Providing & fixing of 0.5 HP Priming Pump including connection & testing etc complete as required. |
| 58 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 59 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 60 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 61 | LIFT PRESSURITATION SYSTEM |
| 62 | Supply, installation, testing & commissioning of Tube Axial fan confirming to IS-3588 (revised) complete with tube casing in MS/GI standard construction epoxy painted, impeller with adjustable blade angles, bird screen, gravity louvers, fire retardent double fold moisture and fire proof with flame retardent fabric confirming to IS-206 (revised) fire retardent flexible connection, necessary nut bolts and directly coupled TEFC Sq. cage induction motor (F-class insulation & B-class Temp. rise) suitable for 415V±10%, 50 Hz, 3 Phase electric supply complete with required hardware, suitable starter panel with cabling between panel and fans etc. Static Pressure: 50 – 75 PaFan Type: Axial pressurization fanPower Supply: 415V, 3 Phase, 50 HzMotor Protection: IP55 / F ClassMotor Protection: IP55 / F ClassNoise Level: ≤ 75 dB at 3 mtr. distanceAirflow: 9000-10000 CFMRPM 1440 (or lower depending on capacity)(AMCA certified for air and sound performance) |
| 63 | Supply and installation of 22Gauge GI ducting from fan to lift shaft including supports. |
| 64 | Supply and installation of Vibration isolators /spring mounts for fan. |
| 65 | Supply and Installation of Electrical panel Electrical Panels for Smoke Evacuation System with Potential free contacts for Fire signal and complete with A meter, Volt meter etc. as per Electrical Specifications. As per drawings and design supplied by architect and instruction given by authority and E.I.CIncoming- 100 AmpOutgoing5 KW X 02 Nos. Starters for Exhaust fan (all Working in case of Fire on receipt of Fire Signal through potential free contact). Exhaust air fan and feeder for PLC Panel complete with protection MCB's and other required accessories etc. as reqd. |
| 66 | Supply & laying of XLPE armoured copper conductor twisted shielded control cables 3C X 1.5 Sq.mm twisted shielded cables for controlling fire panel to PLC panel. |
| 67 | Supply and Installation of PVC insulated FRLS Copper Flexible Wire - 2.5 Sq.mm for earthing. |
| 68 | Supply and installation of MS base frame form mounting the Fan Rectangular frame with cross bracing ISA 50×50×6 mm angles complete with pcc and other required material Please Enable Macros to View BoQ information |