| 1 | Installation Work of New Transformer for Electric Connection of Newly Constructed Burn Unit Building of G.S.V.M. Medical College Kanpur Nagar, U.P. |
| 2 | TRANSFORMER FOUNDATION.Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.Ordinary rock |
| 3 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 4 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 5 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources)BASE + COLUMN |
| 6 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 7 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete |
| 8 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts . |
| 9 | Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform |
| 10 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 11 | ELECTRICAL WORK |
| 12 | Supplying installation testing and commissioning of 11 kV ,630 AMP ,26.3 KA ,one incomer cum outgoing VCB panel having CT ratio,PT ,instrumentation , relays , as per indian standard. |
| 13 | Supplying installation testing and commissioning of 400 kVa, 11/0.433 KV , three phase oil type , outdoor transfarmer with off load tap changer .Service: DistributionRating( kVA): 400 kVAKNAN TypeRated no load voltageHV (kV) 11 KVLV (kV) 0.433 KVTemp . rise oil/wdg : 40/45 deg.CNumber of phases :3Vector group refrence : Dyn11 |
| 14 | Making space for installation of transformer including the cost of cleaning ground , making foundation as per OEM requirement , fancing with door , etc . Scope of work Jungle cleaningMaking space for transformer.Shifting transformer etc.Shifting all power , distribution and control cabling from indoor VCB to outdoor installed transformer.LV (kV) 0.433 KV |
| 15 | Earthing with G.]. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required |
| 16 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 17 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 18 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 19 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 20 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 21 | Supplying and laying of 3 core standard aluminium XLPE insulated PVC bed galvinized flat strip armourlded cable conforming to IS 7098. 120sq.mm * 3 core |
| 22 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV 120sq.mm |
| 23 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV. 120sq.mm |
| 24 | Supplying and laying of aluminium conductor PVC insulated armour served sheated cable 1100 V grade at depth of 750 mm below ground level at cushion bed of 75 mm. 300sq.mm * 3.5 core |
| 25 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3’2 X 300 sq. mm (70mm |
| 26 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3’2 X 300 sq. mm (70mm |
| 27 | GST Extra as per applicable Please Enable Macros to View BoQ information |