| 1 | Recessed PVC Conduit Wiring with Non Modular accessories |
| 2 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminium round tiles, 1.2 mm thick Hot dipped Galavanized MS box with earth terminal, 6 A switch, 3 pin ceiling rose/holder / 3 way connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 3 | Short point (up to 3 mtr.) |
| 4 | Medium point (up to 6 mtr.) |
| 5 | Long point (up to 10 mtr.) |
| 6 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, 1.2 mm thick Hot dipped Galavanized MS box with earth terminal of required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 7 | On board |
| 8 | Surface PVC Conduit Wiring with Non Modular accessories |
| 9 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot dipped Galvanized MS box with earth terminal of required size , 6 A switch, 3 pin ceiling rose/holder / 3 way connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 10 | Short point (up to 3 mtr.) |
| 11 | Medium point (up to 6 mtr.) |
| 12 | Long point (up to 10 mtr.) |
| 13 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) on surface ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, 1.2 mm thick Hot dipped Galvanized MS box with earth terminal of required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 14 | On board |
| 15 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required on surface including heavy duty saddles with base at spacing of 0.60 mtr. etc as required. |
| 16 | 20 mm |
| 17 | 25 mm |
| 18 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 19 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 20 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 21 | P & F paper phenolic resin bonded laminates confirming to IS : 2036 - 1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc plated nut and bolts as required. |
| 22 | 3.0 mm thick |
| 23 | P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 24 | P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 25 | Providing & Fixing of IS:1293 marked of 3 pin 6 amp. flush type non modular socket CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 26 | Providing & Fixing of IS:1293 3/6 pin 16 amp flush type non modular socket CM/L no. printed and made out from Industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 27 | Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 28 | Providing & Fixing of single / multi tone electronic call bell / remote bell including making connection testing etc. as required. |
| 29 | Providing & Fixing of ISI marked (IS:302) ding dong/musical chime bell including making connection testing etc. as required. |
| 30 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 31 | 1/2 Module |
| 32 | Providing & Fixing of following size cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 33 | 1/2 Module |
| 34 | Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required. |
| 35 | 1-2 Module |
| 36 | S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. |
| 37 | 25 mm x 12 mm |
| 38 | 32 mm x 12 mm |
| 39 | Providing & Fixing of DLP PVC adaptable trunking system for cable management including finishing accessories like corners, tees, adjustable angles, junction etc. as required . The trunking system shall have adaptable system for modular type RJ 45 data socket/ wiring accessories/ power sockets and shall be covered with peal off plastic cover. OEM have to submit NABL accrediated /CPET lab test reports /EN 50085-2-1 complaince certificate. |
| 40 | 80mm x 50mm |
| 41 | 100/105mm x 50mm |
| 42 | Providing and fixing of power plug point with non modular accessories with Galvanized box of 1.2 mm thick with earth terminal with suitable size 3.0 mm thick phenolic laminated sheet (IS : 2036 - 1995) cover including cost of 16 amp. Switch (IS :3854) and 3/6 pin 16 amp. socket outlet making connection , testing , etc. as required. |
| 43 | Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. |
| 44 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 45 | 10.0 Sq. mm |
| 46 | 2 core |
| 47 | 70.0 Sq. mm |
| 48 | 3.5 core |
| 49 | Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 50 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 51 | 8 SWG G.I. ( Hot Dipped ) Wire |
| 52 | Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required. |
| 53 | 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) |
| 54 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required. |
| 55 | 300 mm sweep(900 RPM) |
| 56 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 57 | 1170mm(+/-10%) LED batten with min. lumen output 2200 lm |
| 58 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 59 | Recessed Mounting |
| 60 | Minimum lumen output 1950 lm |
| 61 | Surface Mounting (with extruded alumn. Housing ) |
| 62 | Minimum lumen output 1950 lm |
| 63 | SITC of IP20, 2'x2' LED Surface/ Recessed mounting backlit & SMD Mid power type LED Light fixture not less than 35 mm housing depth made from CRCA sheet steel housing, high purity / transmissivity UV stabilized Non -yellowish diffuser for uniform light distribution. operating voltage range 140-285 V, HV cutoff - LV cutoff should be 300-100V . High efficiency with 4 KV internal surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection ( input 320VAC-48 hoursprotection,input 350VAC-2 hours protection) (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 64 | Recessed Mounting |
| 65 | Minimum lumen output 4320 lm |
| 66 | Surface Mounting (Driver should be Inside the Luminaire) |
| 67 | Minimum lumen output 4320 lm |
| 68 | Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler with hermetically sealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick) and tank (0.5 mm thick) , stainless steel water tray,minimum two nos Brass Chrome plated faucets and suitable drainage system complete in all respect with required height MS fabricated and Painted Angle iron frame ( Cost of frame to be paid Extra )complete in all respect of the following capacity. |
| 69 | cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs |
| 70 | SITC of RO water system with Filteration stages = Particilate filter- Membrane life enhancer filter- sediment filter- pre carbon filter- RO membrane filter- post carbon filter. Input power rating -230V AC, 50Hz, percentage of rejection TDS-90% or better, having following features (a) Double purification by RO with ESS or latest technology with TDS indicator. (b) Spin welded RO membrane housing to prevent tempering. (c) Push fit component for leak proof performance. (d) Fully automatic operation with auto start and auto off. (e) SS/ABS construction for corrosion free lifespan. (f) Equally suitable for water from all borewells, overhead storage tanks, water tankers and even municipal taps. (g) RO membrane flushing - Auto flush@ every start, every stop and every one hour of working for one minute, complete in all respect with following capacity. |
| 71 | Purification capacity - 50LPH, duty cycle 270-500 liters/day |
| 72 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing and secondary lens on each LED/ integrated lens diffuser without cover & should be High power LED of 3 to 5 watt each . The System efficacy >=135 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required. |
| 73 | LED Street Light fixture with Minimum lumen output 9450 lm |
| 74 | Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. |
| 75 | 32 mm Dia. |
| 76 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. |
| 77 | Supply and Installation of unshielded/360 degree shielded PCB based Information outlets made of high impact plastic body with ABS, Flammability rating UL 94 V-0 with provision for protection against dust in jack or Faceplate, suitable for Cat 6/6A application complying to latest amendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat 6/6A standards at frequencies 250/ 500 MHz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have toolless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA 568 C.2 & ISO/IEC 11801 or latest standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocol (VOIP) Specifications in existing modular/MS Boxes along with necessary connections as required. All as per pre approved by Engineer in charge. |
| 78 | Cat 6, Un-sheilded Information Outlet |
| 79 | Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture with dust cover, material should be High-impact, flame retardant, thermoplastic, UL listed material, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge. |
| 80 | Single Aperture |
| 81 | Providing & Fixing of IK10/ IP66 protected pole mount LED Post top Luminarie top & bottom made of single piece construction powder coated pressure die cast alluminium housing with High purity PC diffuser, downward illumination to control light pollution. The System level Luminous efficacy ≥ 120 Lumen/W. SMD LEDs is to be used, System CRI>/=70, CCT: 4000/5700 K. Driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.95, THD<10% and with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety, driver should be Phase to phase protection of 440 V for 4 Hrs. System life of 50000 Burning hours with 70% of Initial Lumens maintained . LED driving current <750mA. Mounting pole diameter 060mm, The Luminaire dimension min Dia 450mm x 200mm(H). including making connections etc. as required. |
| 82 | Minimum lumen output 5000 lm Post top Luminaire |
| 83 | Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. |
| 84 | Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required. |
| 85 | Suitable for Two / Three / Four module for MCB |
| 86 | Providing & Fixing of 240/415 V factory fitted RCBO with overload, short-circuit and earth leakage protection with ISI marked (IS12640-2)/ conforming to IEC 61009-1, breaking capacity 10 KA, provision for pad lock, min. Electrical operation 10,000 upto 63 A rating , minimum phase termination capacity of 25 sq.mm. , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. |
| 87 | Two pole 30 mA sensitivity |
| 88 | 6A-32 A rating |
| 89 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra). |
| 90 | 50 mm |
| 91 | Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth. Please Enable Macros to View BoQ information |