| 1 | Maintenance |
| 2 | OD86134/2025-2026:General servicing of the 500 KVA indoor type 11KV/415V transformer ( installed at vikas bhavan) checking the connections, meggering the coil resistances, checking the earth resistance value etc as required including other charges |
| 3 | OD86133/2025-2026:Charges for servicing and maintenance of existing LBS in the existing transformer / Metering panel and making good the unit in working condition as required. |
| 4 | OD86131/2025-2026:supply and fixing of multi function meter to read VA,PF,KW,KWh, accuracy class-1 LCD with necessary connected item as required |
| 5 | 1.17.1:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.1 x 1.5 sq. mm |
| 6 | OD89652/2025-2026:Testing , commissioning , servicing/ overhauling of L&T make 800A ACB -Take out the ACB from the panel board/ USS compartment, dismantling and cleaning with CRC/ suitable solution, replace the worn out parts, regreasing , refitting, tightening all fasteners, adjusting the contact settings and required necessary work for proper functioning. |
| 7 | OD86135/2025-2026:supply and fixing of Three Phase Voltmeter accuracy class 1 with necessary connected item as required |
| 8 | OD86129/2025-2026:supply and fixing of Single Phase Ammeter accuracy class 1 with necessary connected item as required |
| 9 | OD86136/2025-2026:Supply and fixing of Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia and its connected accessories as required |
| 10 | OD86138/2025-2026:Supply and fixing of Blue colour LED indicator, AC/DC, 22.5 mm cut out dia and its connected accessories as required |
| 11 | OD86127/2025-2026:Charges for Service, cleaning, checking and tightening of all bus bars , switches, cable/ wire terminations of the existing main / sub main panel board installed at transformer room of PSC office and making good condition as required. |
| 12 | OD86132/2025-2026:Supply and installation, testing and commissioning of CO2 type fire extinguisher with 4.5 kg. Capacity complete with installation brackets confirming to IS15683 with ISI mark as required. |
| 13 | OD86128/2025-2026:Painting letters or figures of the following sizes with enamel paint as identification mark to the Panels boars etc. as required. 2.5 cm, 4 cm, 5 cm height |
| 14 | OD89813/2025-2026:Charges for scrubbing rust ,cleaning, applying one coat of metallic primer and two coat of metallic paint on the surface of the panel board and making good condition as required. |
| 15 | OD89808/2025-2026:Charges for supply and installation of new temperature Indicator Or temperature sensor for 500KVA transformer |
| 16 | OD89814/2025-2026:Service charges for APFC Panel-50kVAR. Attending petty repairs, rectifying minor defects, renewing damaged control wires, Properly insulate the all terminals etc. as required. |
| 17 | OD263864/2025-2026:Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength. Please Enable Macros to View BoQ information |