Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Civil Works |
| 2 | SITE CLEARENCE |
| 3 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth upto 30 cm measured at a height of 1 m above ground level and removal of rubbish upto a distance of 50 m outside the periphery of the area cleared. |
| 4 | EARTH WORK EXCAVATION |
| 5 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 6 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m |
| 7 | Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge |
| 8 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : All kinds of soil Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia |
| 9 | PLAIN CEMENT CONCRETE |
| 10 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 11 | RCC WORK |
| 12 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durabilityand workability without impairing strength; including pumpingof concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of thespecified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level Concrete of M30 grade wwith minimum cement content of 350 kg /cum |
| 13 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durabilityand workability without impairing strength; including pumpingof concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of thespecified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level upto floor V leveConcrete of M30 grade wwith minimum cement content of 350 kg /cum |
| 14 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:5:10 ( 1 cement : 5 coarse sand : 10 graded stone aggregate 20 mm nominal size) |
| 15 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete below plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 16 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 17 | FORM WORK |
| 18 | Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 19 | Centering and shuttering including strutting, propping etc. and removal of form for Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 20 | Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform |
| 21 | Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 22 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls Under 20 cm wide |
| 23 | Centering and shuttering including strutting, propping etc. and removal of form for : Stairs, (excluding landings) except spiral-staircases |
| 24 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls Under 20 cm wide |
| 25 | Centering and shuttering including strutting, propping etc. and removal of form for : Weather shade, Chajjas, corbels etc., including edges |
| 26 | STEEL WORK |
| 27 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 28 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 29 | MASONRY WORK |
| 30 | Brick work with common burnt clay modular bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 31 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 32 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 33 | PLASTERING |
| 34 | 12 mm cement plaster finished with a floating coat of neat cement of mix : 1:4 (1 cement: 4 fine sand) |
| 35 | 6 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand) |
| 36 | DOORS & WINDOWS |
| 37 | Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame. |
| 38 | 30 mm thick Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required Colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames. |
| 39 | Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : 150x10 mm |
| 40 | Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : 200x10 mm |
| 41 | Providing and fixing bright finished brass handles with screws etc. complete: 125 mm |
| 42 | Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete. |
| 43 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm) with double speed adjustment with necessary accessories and screws etc. complete. |
| 44 | Providing and fixing ISi marked oxidised M.S. door latches conforming to IS:5930 with screws etc. complete :250x20x6 mm |
| 45 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm) |
| 46 | Providing and fixing of glass door SS Patch Lock with out handle in toughened glass door including all necessary screws etc. complete. |
| 47 | Providing and fixing Steel S.S- 304 (D) Door Pull Both Side Handle of 12 inch, one Set (2 Handles) ( best make of approved quality ) for Glass, Wooden or similar doors including necessary cutting and making good etc. complete |
| 48 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double action hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge (Door handle, lock and stopper etc.to be paid separately). |
| 49 | Providing and fixing fire resistant door frame of section 143 x 57 mm having built in rebate made out of 16 SWG G.I. sheet (zinc coating not less than 120 gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10x4 mm (minimum) alround the frame and fixing with dash fastener of approved size and make, including applying a coat of approved brand fire resistant primer etc. complete as per direction of Engineer-in-charge (Dash fastener to be paid for separately). |
| 50 | Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWG G.I.sheet (zinc coating not less than 120 gm/m2) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge (panneling to be paid for separately). |
| 51 | Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and as per direction of Engineer-in-charge with glass of required thickness having 60 minutes of fire resistance both integrity & radiation control (EW60) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm. |
| 52 | Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete. |
| 53 | Supply , Installation, testing and commissioning of Fully Automatic Double Leaf Sliding Door operator with 12 mm thick Crystal Glass, complete with future European standards and produced according to the guidelines for power-operated windows, doors and gates BGR 232, the UVV and the VDE regulations. TÜV design tested, tested according to the low voltage guidelines, production according to ISO 9001:2000 certification. Fulfils the DIN V18650 (prEN 12650). complete with all safety devices and including |
| 54 | Supplying and laying polyester, washable and stainfree cloth(Bio-Active fabric washable germfreesuitable for dialysis room) curtain system with maximum curtain cloth height 230cm(top 30cm white clour net and 200cm light blue colour as per approval) stiching with stifiner tape, pleats, ironing and laying around Each bed using sliding wheels two nylon rollers, nylon axil and tangle free nylon swivel stem with chrome-plated steel hook, curtain track should be supported in roof using 20x20mm, 2mm thick sized aluminium tubes same spec with end caps in two sides using all necessary fittings. as per the direction of engineer in charge including conveyance to site, laying in line and level, sealing all cutting in false ceiling with powder coated MS cup, all leads and lifts including all labour charges etc. complete.(unpleated length of the cloth measurement will be considered for payment also the bottom and top foldings will not be considered in cloth measurement)/ supplying and fixing powder coated 20mm dia. GI round tube hanging support of required length(app. length 1.10m) one end fixing from slab by using 6mm dia expansion bolt at a distance not more than 2m, c/c down end fixed to powder coated aluminium channel frame 45 x 20mm x 1mm thick section by using SS screw as per the direction of engineer incharge including conveyance. |
| 55 | Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc |
| 56 | GLAZING AND CLADDING WORK |
| 57 | Full height Glazed partition -Supply and Fixing of Slim Profile Glass partition of 12mm Toughened Glass using System-45 Frames to a height of maximum 2.4m or as per drawing. The Fixed glass to be fixed using BP45 Profiles at Top & Bottom, Side Profiles SP45 at sides. The profile size to be 45x25MM to be fixed on to the floor/wall/ ceiling as per the architect design. H Junction profile to be used at all Glass to Glass vertical joints, 90 Deg L Junction Profiles and T Junction profiles necessary as per design. In case of Glass overall panel MP45 & BP45 Overpanel Profile to be used. In case of Open glass edges EP45 End Profile to be used. |
| 58 | ALUMINIUM WORK |
| 59 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 60 | For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 61 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides |
| 62 | Providing and fixing glazing in door, window, ventilator shutters and partitions etc. with EPDM rubber /neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): toughened glass of 6 mm thickness. |
| 63 | Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete |
| 64 | WALL TILE |
| 65 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).Size of Tile 600x600 mm |
| 66 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 67 | FLOORING |
| 68 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm |
| 69 | Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 600x600 mm |
| 70 | Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x600 mm |
| 71 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete. |
| 72 | Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : Dark shade pigment using ordinary cement |
| 73 | FALSE CEILING & CLADDING |
| 74 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer39;s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board |
| 75 | Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main \\"T\\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \\"T\\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \\"T\\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \\"T\\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \\"T\\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece. |
| 76 | PAINTING |
| 77 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 78 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 79 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 80 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of Special primer applied @ 0.75 ltr /10 sqm |
| 81 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications :Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 82 | Providing & Applying polymer modified, flexible cementatious negative side waterproofing coating with elastic waterproofing polymers on interior wall plaster surface in three coats @14.35 kg /10 sqm. one coat of self priming of cementatious waterproofing polymer(dilution with water in the ratio of 1:1) and two coats of cementatious waterproofing polymer (dilution with water in the ratio of 3:1 ) after scrapping and properly cleaning the surface to remove pre-existing paint film & loose particles till plaster is visible, complete in all respect as per the direction of Engineer-in-Charge. |
| 83 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm |
| 84 | PLUMBING & SANITARY FITTINGS |
| 85 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 86 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour.450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 87 | Providing and fixing PTMT liquid soap container 109mm wide, 125mm high and 112mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour. weighing not less than 105 gms. |
| 88 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 25 mm dia 10 Kgf/cm2- External work - Exposed on wall |
| 89 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 32 mm dia 10 Kgf/cm2 - External work- Exposed on wall |
| 90 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed/ Concealed on wall |
| 91 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 :15mm nominal bore |
| 92 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid |
| 93 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap |
| 94 | Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour. |
| 95 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe 40 mm dia |
| 96 | Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge |
| 97 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 15 mm nominal bore |
| 98 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 15 mm nominal bore |
| 99 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :15 mm nominal bore |
| 100 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690gms. 15 mm nominal bore |
| 101 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia Pipes |
| 102 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 32 mm nominal outer dia Pipes |
| 103 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.50 mm nominal dia Pipes |
| 104 | Constructing masonry chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C.I. surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design: 18.32.1 With common burnt clay F.P.S. (non modular ) bricks of class designation 7.5 |
| 105 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 106 | Providing and fixing PTMT extension nipple for water tank pipe, fittings of approved quality and colour.20 mm nominal bore, weighing not less than 40 gms |
| 107 | Providing and fixing PTMT grating of approved quality and colour. Circular type100 mm nominal dia |
| 108 | Constructing soak pit 1.20x1.20x1.20 m filled with brickbats including S.W. drain pipe 100 mm diameter and 1.20 m long complete as per standard design. |
| 109 | Supplying and placing of 5000 Litre 1mm thick stainless steel water tank of 1750mm dia , 2600mm height, Stainless steel mounted stand around 180kg and grade of ASTM A240 gr.304/ SS316 BA/2B as per the direction of Engineer in-charge. The rate inclusive of all the transportation, Steel stand support, loading and unloading charges, fixing charges, Labour charges, etc. Nothing shall be additionally paid in this item. |
| 110 | Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall |
| 111 | Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2 |
| 112 | Supply of HDPE Pipe PE 100 (IS 4984/1995), 10kg, 200mm Outer Dia |
| 113 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed on wall |
| 114 | Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2 |
| 115 | ROAD WORK |
| 116 | Construction of granular sub- base by Providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, Carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in- Charge.With Material conforming to Grade - I ( size range 75 mm to 0.075 mm) having CBR Value- 30 |
| 117 | Providing , laying spreading and compacting graded stone aggregate ( size range 53 mm to 0.075 mm) to wet mix macadam (WMM) specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by tipper to site, for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub - base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer - in- Charge. |
| 118 | 2.5 cm premix carpet surfacing with 2.25 cum and 1.12 cum of stone chippings of 13.2 mm and 11.2 mm size respectively per 100 sqm and 52 kg and 56 kg of hot bitumen per cum of stone chippings of 13.2 mm and 11.2 mm size respectively, including a tack coat with hot straight run bitumen, including consolidation with road roller of 6 to 9 tonne capacity etc. complete ( tack coat to be paid for separately):With Refinery Modified Bitumen CRMB 55 conforming to IRC:SP:53 - 1999 |
| 119 | Tack Coat - RS Bitumen Emulsion - On W.B.M / W.M.M @ 0.4 kg/ sqm - Using Packed Bitumen Rates Providing and applying tack coat using bitumen emulsion conforming to IS : 8887, using emulsion pressure distributor including preparing the surface & cleaning with mechanical broom. 1. With Rapid Setting Bitumen Emulsion 1. On W.B.M / W.M.M @ 0.4 kg/ sqm |
| 120 | SIGNAGES |
| 121 | Design, providing and fixing Digital Printed vinyl signage boards with transparent 3mm acrylic Sheet with 4 nos. SS Studs of Size 16\\" x 10\\". Complete as per the per the direction of Engineer in charge. |
| 122 | Design, providing and fixing Acrylic LED Sign Board of 5cm Letter Thickness 20 - 30cm Letter Height. Complete as per the direction of Engineer in charge. |
| 123 | Electrical |
| 124 | Point wiring in PVC conduit with modular type switch. |
| 125 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group B |
| 126 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 127 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 128 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 129 | Wiring through PVC conduit |
| 130 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 131 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 132 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 133 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 134 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 135 | S/F PVC CONDUIT |
| 136 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm |
| 137 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm |
| 138 | Modular type blanking plate: |
| 139 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 140 | Modular boxes, bases & cover plate: |
| 141 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mmX75mm) |
| 142 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 3 Module (100mmX75mm) |
| 143 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 6 Module (200mmX75mm) |
| 144 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 145 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )1 module moulded plastic box on surface |
| 146 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface |
| 147 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant ) 6 module moulded plastic box on surface |
| 148 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 1 or 2 Module |
| 149 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 3 Module |
| 150 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 6 Module |
| 151 | Modular type switch/socket: |
| 152 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A switch |
| 153 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 A socket outlet |
| 154 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 A switch |
| 155 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 A socket outlet |
| 156 | Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator |
| 157 | Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket |
| 158 | DB ACCESSORIES |
| 159 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door |
| 160 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 8 way (4 + 24), Double door |
| 161 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A |
| 162 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker with overcurrent protection (RCBO), having a sensitivity current upto 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A-40A, 4P, 100mA |
| 163 | Supplying and fixing 40A / 63A, TP MCB, 415 Volts, \\"C\\" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc as required. |
| 164 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 165 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 166 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 167 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A |
| 168 | Supplying and fixing FP CRCA sheet steel enclosure with provision to mount MCB/Isolator/RCCB/RCBO and other modular devices on surface/ recess complete with connections, testing and commissioning etc. as required. |
| 169 | EARTHING |
| 170 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 171 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 172 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 173 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 174 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 175 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 10 SWG) |
| 176 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 177 | SUPPLY OF LT CABLES |
| 178 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4 X 25 |
| 179 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4 X 16 |
| 180 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4X10 |
| 181 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5 X 185 sq. mm |
| 182 | CABLE LAYING |
| 183 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 184 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with25/40x3mm MS flat clamp) |
| 185 | LT CABLE TERMINATION |
| 186 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (25mm) |
| 187 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm) |
| 188 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25 sq. mm (28mm) |
| 189 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 185 sq. mm (57mm) |
| 190 | CABLE TRAYS |
| 191 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 192 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 193 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 194 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 195 | LIGHT FITTINGS & FANS |
| 196 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operatingvoltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuitprotection, THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained tilllife ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum powerconsumption should not more than the specifiedrating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housingsuch that LED junction temperature shall not riseabove 90°C).Powder coated die cast /Extruded aluminiumBody (Thickness > 1.20 mm) 36 watt |
| 197 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Wattoutput . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall besubmitted. Shape size and CCT shall be as approved by Engineer-in-Charge as perrequirement. (Thermal management: heat sink of aluminium housing such that LED junctiontemperature shall not rise above 90°C) Powder coated die cast /Extruded aluminiumBody including trim Powder coated die cast /Extruded aluminiumBody including trim .18 watt |
| 198 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Wattoutput . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall besubmitted. Shape size and CCT shall be as approved by Engineer-in-Charge as perrequirement. (Thermal management: heat sink of aluminium housing such that LED junctiontemperature shall not rise above 90°C) Powder coated die cast /Extruded aluminiumBody including trim 8 - 10 watt |
| 199 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till lifeends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation 45 DELHI SCHEDULE OF RATES (E&M)-2025 Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 18- 22 Watt |
| 200 | SITC of 2 feet surface/suspended mounted LED batten type luminaire with a power consumption not more than 10 W, luminaire lumen output of 1100 lumens, luminaire efficacy > 110 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a sleek design with extruded aluminum section, white CRCA housing with optically efficient poly carbonate diffuser to provide uniform illumination and wider light distribution. The luminaire shall have a CCT of 4000K /6500 K, CRI > 80, power factor >0.95, SDCM < 5, THD <10%. The luminaire shall be EMI/ EMC compliant and shall have an internal surge protection of 3 kV with 50,000 burning hours as per L70B50 criteria. The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature, including all accessories necessary as required to complete installation. |
| 201 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 202 | SITC of 450mm sweep Wall fan having speed control, oscillation control at bottom as suitable for operation on single phase 230 volt AC supply complete with continuous duty motor and all accessories including mounting as required for complete installation. |
| 203 | SITC of 250mm sweep Exhaust Fan, 900rpm light duty exhaust fan shutter type white colour, 9\\" or 10\\" star rated as per BEE, with its all accessories including mounting as required for complete installation. |
| 204 | SITC of 250mm sweep Ceiling Exhaust Fan, 900rpm light duty exhaust fan shutter type white colour, 9\\" or 10\\" star rated as per BEE, with its all accessories including mounting as required for complete installation. |
| 205 | Online UPS- Input supply: Three Phase, Output supply: Three Phase. Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 0C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swapable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of modules required for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. . Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accessories are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f) Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding theload / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc 20 KVA |
| 206 | PANEL |
| 207 | MAIN PANEL : Fabrication, supply, erection, testing and commissioning of floor or wall mounting dust and vermin proof, cubicle type, front operated MV panel board as per IS 8623 - CPRI Certified made out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalized complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. The panel shall be with Top/bottom entry to receive incoming & outgoing, all opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all accessories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided.Incomer - 160A 36kA FP Microprocessor based MCCB having isolation duty with 3 O/C and 1 E/F release, isolation duty type 400A 433V, 36kA best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc. complete as required. Multifunction meter having multiline LED display with following parameters -Phase wise instantaneous and Average values – Voltage, Current, Power Factor, Phase wise instantaneous and Average values – Active Power, Reactive Power lead & lag, Apparent Power, Import & Export Cumulative values– Active Energy, Reactive Energy lead & lag, Apparent Energy, PF for 3 phases and average, Instantaneous Frequency, Total Harmonics Distortion – Phase wise Voltage and Phase wise Current - 1 Set RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoings: 100A 25kA 4P MCCB Microprocessor based -2 Nos, 63A 25kA 4P MCCB Microprocessor based -3Nos, 40A 25kA 4P MCCB Microprocessor based -3 Nos, |
| 208 | NETWORK |
| 209 | Supplying, Installation, Testing and commissioning of CAT6A Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/ULverification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 210 | Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non- Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required. 1 Run of cable |
| 211 | Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color, Use for 24- 26 AWG stranded wires etc. complete as required. |
| 212 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm ToughenedGlass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. 6U rack |
| 213 | Supply, Installation, Testing & Commissioning of 16 Port Network Switch with 16 No's of 10/100/1000 ports and 2 Gigabit Copper/ SFP Combo ports for uplink |
| 214 | Supplying Installation Testing and Commissioning of 2MP IP IR Dome Camera having followingspecifications, type of lens and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio:>50 dB, Camera should display Camera title, Date &Time in live & recorded video2)Image Sensor: 1/2.8\\" or better progressive ScanCMOS to get color image even at night condition(Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 3) Compression (Minimum):-Video:- H.265 or better,H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 4) Wide Dynamic Range:- WDR (120db or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming, configurable (Main stream: 2MP (1920×1080)@25/30 fps,Sub streams minimum:720P@25/30 fps).7) Image Setting: Rotate Mode, saturation, brightness,contrast, sharpness adjustable through client softwareor web browser, Edge Analytics: Tripwire, Intrusion,Motion Detection8) Cyber Security: AES 256-bit Encryption,Configuration encryption, trusted execution, Digest,security logs, account lockout, syslog, videoencryption, IP/MAC filtering, HTTPS, trusted upgrade,trusted boot.9) Onboard Storage: Camera should support built-inMicro SD/SDHC/SDXC Card slot upto 512 GB. Itshould be supplied with minimum 128GB memoryCard.280 10) Recording Management: Format SD, overwrite, storage management, video to NAS device 11) Alarm Trigger : Motion/tampering detection; audio detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,unicast13) System Capability: ONVIF, Camera shall supportopen source VMS14) Ethernet: 1 RJ 45 10/100 Ethernet port15) Audio : It should support 1 x Built-In Mic and 1/1Alarm In/ Out for External Mic. and Speakers as persite requirement.16) Power Input: The camera should supportsimultaneous dual power input—12 VDC (via poweradapter) and PoE (802.3af)—to ensure continuousoperation in the event of a failure in one power source.17) Power Requirement: 12VDC/24 VAC/PoE(802.3af)/ePoE18) Housing/ Enclosure:- IP67 weather proof, IK10, Metallic body 19) Operating Condition:- Ambient Temperature:- (- )05°C to 50°C, humidity 95% (max) (non-condensing) 20) IR life: 40000 hours or higher 21) Video Bit rate: 32 KBPS - 8 MBPS or better22) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS 2MP (@ 25/30fps@1080P (1920×1080)) IP IR Dome Camera with 2.8/ 3.6mm fixed lens |
| 215 | Supplying Installation Testing and Commissioning of 2MP Fixed Lens IP IR Outdoor Bullet Camera havingfollowing specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: >50 dB,Camera should display Camera title, Date &Time in live & recorded video 2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS to get color image even at nightcondition(Minimum Illumination: 0.006 Lux@ F1.4,AGC ON, 0 lux with IR or better) True Day & NightHigh Performance Mechanical IR cut filter with autoswitch, Integrated IR Source (Auto, Manual)- InbuiltSmart IR LED's with effective distance upto 50 meteror better and 30 meter for colour view in night,Imaging: 1/3s to 1/30000s electronic shutter support,Auto Gain Control , White Balance- Auto, Back LightCompensation, Multi zone Privacy Masking, HLC,Digital Watermarking.3) Compression (Minimum):-Video:- H.265 or better,H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726,AAC, G.7234) Wide Dynamic Range:- WDR (120db or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming, configurable(Main stream: 2MP (1920 ×1080)@25/30 fps Sub streams minimum:720P@25/30 fps).7) Image Setting: Rotate Mode, saturation, brightness,contrast, sharpness adjustable through client softwareor web browser, Edge Analytics: Tripwire, Intrusion,Motion Detection8) Cyber Security: AES 256-bit Encryption,Configuration encryption, trusted execution, Digest,security logs, account lockout, syslog, videoencryption, IP/MAC filtering, HTTPS, trusted upgrade,trusted boot.9) Onboard Storage: Camera should support built-inMicro SD/SDHC/SDXC Card slot upto 512 GB. Itshould be supplied with minimum 128GB memoryCard.10) Recording Management: Format SD, overwrite,storage management, video to NAS device,11) Alarm Trigger : Motion/tampering detection; audiodetection; network disconnection detection; IP conflictdetection; memory card state detection; memoryspace detection12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP,NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,unicast,13) System Capability: ONVIF, Camera shall supportopen source VMS 2MP @ 25/30fps@1080P (1920×1080) Outdoor Bullet Camera with 2.8/ 3.6mm fixed lens |
| 216 | 16 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16, 2nd screen: 1/4/8/9/16 |
| 217 | Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. |
| 218 | TELEPHONE |
| 219 | Supply of User Phone- Analog phone |
| 220 | Supplying and drawing following pair 0.5 mm dia FRLS/HFFR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair |
| 221 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet |
| 222 | Supply, Installation, Testing and Commissioning of aircooled VRV (Variable Refrigerant Volume) / VRF (Variable Refrigerant Flow) outdoor units (ODUs) equipped with highly efficient, full DC inverterdriven scroll compressors only, aircooled heat exchangers having internally grooved copper tubes, and lownoise condenser fans. The units shall have autoaddressing, an autocheck function for connection errors, and operate with R410A or equivalent refrigerant gas. Each unit shall be fitted with a noise filter, highpressure switch, fan motor overload protector, overcurrent relay, inverter overload protector, and other necessary protective devices. Power failure of one or more IDU shall not affect operation of other units / circuit. The units shall deliver the rated capacity in accordance with IS 18728:2024 and CPWD specifications. The efficiency of the ODUs shall meet the latest ECSBC/ASHRAE standards. Suitable vibration isolators shall be provided with the ODUs. The system shall operate at outdoor conditions up to a minimum ambient drybulb temperature of 50°C. Each unit shall be equipped with an oil recovery system to ensure stable operation with long refrigeration piping lengths, and provided with an oilbalancing circuit to prevent inadequate lubrication. Compatibility with centralized control systems such as BACnet, LonWorks, and Modbus is required. The ODUs shall be suitable for a 3phase, 415V, 50Hz power supply, with suitable interconnecting control cabling between IDUs, ODUs, and the central controller. All necessary power cabling up to the ODU electrical panel, pressure testing, additional refrigerant charging for commissioning, and all associated accessories required for commissioning shall be included in the scope of work. The VRF outdoor unit circuit schedule shall be as per the tender drawings/specifications. |
| 223 | Supply, Installation, Testing, and Commissioning of VRF/VRV 4.0TR ceilingmounted,mid/high static ductable type indoor unit along with a corded remote. Theunit shall be equipped with a washable synthetic media pre-filter, a fan section with alow-noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dxcopper coil, an electronic expansion valve, an outer cabinet, vibration isolators, adrain pan, and other necessary supports, suitable for operation on a single-phase ACsupply of 230 V ± 10%, 50 Hz.. |
| 224 | Supply, Installation, Testing, and Commissioning of VRF/VRV 11.0 TR ceiling-mounted, high static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low-noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz. |
| 225 | Supply, Installation, Testing, and Commissioning of VRF/VRV 8.5 TR ceiling-mounted, high static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low-noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz. |
| 226 | Supply and Installation of INDOOR Refnet / Y-joint separation tubes for refrigeration pipe joints and headers in appropriate orientation to enable proper distribution of refrigerant. The distribution joints should be factory insulated with pre- formed section of expended polystyrene / equivalent. |
| 227 | Supply and Installation of OUTDOOR Refnet / Y-joint separation tubes for refrigeration pipe joints and headers in appropriate orientation to enable proper distribution of refrigerant. The distribution joints should be factory insulated with pre- formed section of expended polystyrene / equivalent. |
| 228 | Supply, Installation, Testing and Commissioning of Centralized Type Remote Controller, color touch screen type with UPS battery backup, all inclusive of necessary installation supports and wiring. The controller must function as an advanced air conditioning management system, providing complete control of VRV/VRF air conditioning equipment (including connected AHUs). It should offer user-friendly operation through its touch screen, icon display, and color LCD display. Units shall be compatible with either BACnet, LonWorks or MODBUS interface. The controller is required to control up to 64 groups of indoor units with the following functions: 1. Starting/stopping of air conditioners as a zone or group or individual unit. 2. Temperature settings for each indoor unit or zone. 3. Switching between temperature control modes, fan speed adjustment, and airflow direction control, including enabling/disabling of individual remote controller operation. 4. Monitoring of operation status, such as operation mode, temperature settings of individual indoor units, maintenance information, and troubleshooting details. 5. Scheduling Indoor Unit Operating Time 6. Displaying air conditioner operation history. |
| 229 | Supply, Installation, Testing, and Commissioning of Soft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:1/4 inch (6.35 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 230 | Supply, Installation, Testing, and Commissioning of Soft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:3/8 inch (9.52 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 231 | Supply, Installation, Testing, and Commissioning of Soft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:1/2 inch (12.7 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 232 | Supply, Installation, Testing, and Commissioning of Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:5/8 inch (15.88 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 233 | Supply, Installation, Testing, and Commissioning of Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:3/4 inch (19.05 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 234 | Supply, Installation, Testing, and Commissioning of Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:7/8 inch (22.2 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 235 | Supply, Installation, Testing, and Commissioning of Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1.0 inch (25.4 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 236 | Supply, Installation, Testing, and Commissioning of Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/8 inch (28.6 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 237 | Supply, Installation, Testing, and Commissioning of Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/4 inch (31.8 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 238 | Supply, Installation, Testing, and Commissioning of Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-3/8 inch (34.9 mm) gas/liquid copper insulated piping. The insulation for copper lines shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values of pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of FACTORY LAMINATED FIBRE GLASS CLOTH. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line as per the specifications between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing on walls, etc., as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y- joints, supports, refnets, and wall clamps, etc., for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings should match the pipe thickness. PVC SLEEVES shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed in all respects as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all the refrigerant pipes installed are in accordance with the Original Equipment Manufacturers (OEM) technical/recommended specifications. |
| 239 | Supply, laying, and testing of shielded copper flexible communication/transmission cabling between VRF indoor units and outdoor units. The communication cable must be routed through PVC conduit. The sizing of the cable to be 2 Core x 1.5 SQMM (or) as per VRF-OEM's technical/recommended specification. |
| 240 | Supply, Installation, testing and commissioning of 25mm dia rigid UPVC condensate drain pipes duly insulated with 9mm thick closed cell nitrile finished with 7mils FACTORY LAMINATED GLASS CLOTH along with necessary U-trap,clamps, fittings such as bends, tees etc. adequately supported complete as required confirming to specification. |
| 241 | Supply, Installation, testing and commissioning of 32mm dia rigid UPVC condensate drain pipes duly insulated with 9mm thick closed cell nitrile finished with 7mils FACTORY LAMINATED GLASS CLOTH along with necessary U-trap,clamps, fittings such as bends, tees etc. adequately supported complete as required confirming to specification. |
| 242 | Supply, Installation, testing and commissioning of 40mm dia rigid UPVC condensate drain pipes duly insulated with 9mm thick closed cell nitrile finished with 7mils FACTORY LAMINATED GLASS CLOTH along with necessary U-trap,clamps, fittings such as bends, tees etc. adequately supported complete as required confirming to specification. |
| 243 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.63 mm sheet |
| 244 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.80 mm sheet |
| 245 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular dueling as per IS 655-2006 Thickness 1.00 mm sheet |
| 246 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. Nitrille rubber insulation - 25 mm |
| 247 | Supply and application of two coats of vapor barrier (Foster Painting ) on exposed ducts /copper refrigerant pipelines, as per the directions of the Engineer-in-Charge. The work includes surface preparation, application of vapor barrier coating and related works to ensure full coverage and protection. |
| 248 | Supply, installation, testing and commissioning of Acoustic duct lining using 10mm nitrile rubber insulation open cell type inside the ducts, antimicrobial protection at the AHU/Ductable unit outlets upto 4m distance from fan outlet (or)as instructed by Engineer in-charge |
| 249 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. Gl volume control duct damper |
| 250 | Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/ main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.Fire damper |
| 251 | Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/ main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.Actuator |
| 252 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. |
| 253 | Supplying & fixing of powder coated extruded aluminum Return Air Grills with louvers but without volume control dampers complete as required. |
| 254 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminum with aluminum volume control dampers with anti smudge ring and removable core. |
| 255 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminum without volume control dampers with anti smudge ring and removable core. |
| 256 | Supply and installation of Fresh Air/ Exhaust Air Louvre of aluminium powder coated with bird Screen as per specifications and drawings. |
| 257 | Supply, Installation and fixing- hanging of FACTORY fabricated fire retardant flexible Canvas connection of minimum 150mm width, at outlet of each Ducted Indoor unit with zipper to facilitate temperature measurement. The fabric to be made of Polyester cloth, black PVC coating on both sides along with galvanised steel seam. |
| 258 | PIPES AND ACCESSORIES |
| 259 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :25 mm dia |
| 260 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :32 mm dia |
| 261 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :40 mm dia |
| 262 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :50 mm dia |
| 263 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :65 mm dia |
| 264 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia |
| 265 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :100 mm dia |
| 266 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :150 mm dia |
| 267 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :200 mm dia (wall thickness 6.3 mm) |
| 268 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required : 80mm dia |
| 269 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required : 100mm dia |
| 270 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.150 mm. Dia |
| 271 | VALVES |
| 272 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required80 mm dia |
| 273 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required100 mm dia |
| 274 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required150 mm dia |
| 275 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :80mm dia |
| 276 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :100mm dia |
| 277 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :150mm dia |
| 278 | Supply, installation, testing and commissioning of lever operated 25mm dia Gate/ball valve conforming to IS 9890:1981 with forged body, brass/stainless steel ball and shall be internally threaded to receive pipe connections25mm dia |
| 279 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conformingto IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required:Single headed Stainless steel |
| 280 | AIR RELEASE VALVE;Supply, installation, testing and commissioning of gunmetal air release valve 25 mm with necessary fittings etc. complete. |
| 281 | SWITCHES |
| 282 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required |
| 283 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 284 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc asrequired.100mm dia |
| 285 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304) |
| 286 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.a.20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585b.20 mm nominal internal dia gun metal globe valve & nozzle. c.Drum and brackets for fixing the equipmets on wall.d.Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30 m |
| 287 | Supply, installation, testing and commissioning of hose boxes wall/pedestal type of size 600 x 250 x 400 mm made out of 18 gauge MS sheet steel with front side glass, locking arrangement and painted with approved colour completed as required and as per specifications. |
| 288 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Stainless Steel (Grade 304) |
| 289 | Providing, fixing, testing and commissioning of Ball Valve, PN-25 Forged Brass & Nickel / Chrome Plated, conforming to IS: 9890 with Screwed Female Ends to BS:21, and with non-corrosive handle / lev er, all as per Technical specification. including necessary accessories and connections. Dia - 20mm. |
| 290 | SPRINKLERS |
| 291 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Pendent Sprinkler |
| 292 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, centre bracket, stock bar of following sizes complete as required.1000mm |
| 293 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 294 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Horizontal side wall sprinkler |
| 295 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Upright Sprinkler |
| 296 | FIRE BRIGADE |
| 297 | FIRE BRIGADE INLET : Supply, installation, testing and commissioning of 3 way tank filling Inlet connection of 63 mm dia. valves instantaneous coupling type arrangement to be connected to wet riser main. |
| 298 | FIRE EXTINGUSHERS |
| 299 | SITC OF ISI marked (IS:2878) fire extinguisher CO2 type capacity 4.5kg. Flat base including valve, discharge hose of not less than 10mm dia , 1 meter long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1996 filled to filling rate of not more than 0.667 and wall bracket (fixed with anchor Fastner) or floor mounted |
| 300 | Supply and fixing of 4 Kg ABC Dry Powder (Stored Pressure) Type Fire Extinguisher. pressurized with dry nitrogen gas at 15 bar. Design, construction and testing as per IS 2171-1999 external epoxy powder coating with PO Red Shade No. 538 of IS 5, Supplied with standard accessories. |
| 301 | SIGNAGES |
| 302 | Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters FIRE in black and gold. Cost shall be inclusive of providing MS stand for 2 nos of fire buckets, duly painted over a coat of primer. |
| 303 | Providing and fixing standard fireman's axe with heavy rubber handle. |
| 304 | Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMPROOM, FIRE CONTROL ROOM, ELECTRICALROOM, FIRE LIFT, PASSENGER LIFT Etc.) standard size(500x225 mm as per conventional design / colour code on 3 mm thick aluminium composite panel, conforming to IS 9457. The signage will be either fixed on the wall with the help of chain and screws etc. complete as required as per the technical specification." |
| 305 | SIGNAGE : Supply installation of necessary Signages as per standard including " FIRE DUCT,FIRE EXIT,EXIT,NO SMOKING etc." |
| 306 | SIGNAGE : Supply installation of Signage "ASSEMBLY POINT" |
| 307 | SIGNAGE : Supply installation and testing of emergency exit system with battery backup |
| 308 | FIRE ALARM SYSTEM |
| 309 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 310 | Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass ndpush button etc. as required. |
| 311 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc.complete as required. |
| 312 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire dition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. 4 Zone |
| 313 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 314 | Civil Works |
| 315 | SITE CLEARENCE |
| 316 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth upto 30 cm measured at a height of 1 m above ground level and removal of rubbish upto a distance of 50 m outside the periphery of the area cleared. |
| 317 | EARTH WORK EXCAVATION |
| 318 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 319 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m |
| 320 | Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge |
| 321 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : All kinds of soil Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia |
| 322 | PLAIN CEMENT CONCRETE |
| 323 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 324 | RCC WORK |
| 325 | Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge.All work upto plinth level. |
| 326 | Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 400 kg/ cum.All work above plinth level upto floor V level |
| 327 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:5:10 ( 1 cement : 5 coarse sand : 10 graded stone aggregate 20 mm nominal size) |
| 328 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete below plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 329 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 330 | FORM WORK |
| 331 | Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 332 | Centering and shuttering including strutting, propping etc. and removal of form for Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 333 | Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform |
| 334 | Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 335 | Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts |
| 336 | Centering and shuttering including strutting, propping etc. and removal of form for : Stairs, (excluding landings) except spiral-staircases |
| 337 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls Under 20 cm wide |
| 338 | Centering and shuttering including strutting, propping etc. and removal of form for : Weather shade, Chajjas, corbels etc., including edges |
| 339 | STEEL WORK |
| 340 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 341 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 342 | Providing at all heights, levels and locations Aluminium profile industrial troughed sheet of Alloy 31500/31000/40800, conforming to IS 1254, IS 737, IS 2676. The sheet shall be fixed using self drilling/ self tapping SS screws of size 5.5x65 mm with EPDM seal complete upto required pitch in horizontal, vertical or curved surfaces i/c cutting to size and shape where required as per specifications, detail drawings and direction of Engineer-in-Charge. The rate shall be inclusive of all screws, seal, ridge, labour, scaffolding, machinery for fixing and approved sealent where required etc. but excluding the cost of purlins, rafters and trusses 0.71 mm thick, the profile detail width 1044/920 mm, cover width 1000/875 mm. |
| 343 | MASONRY WORK |
| 344 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 345 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 346 | PLASTERING |
| 347 | 12 mm cement plaster finished with a floating coat of neat cement of mix : 1:4 (1 cement: 4 fine sand) |
| 348 | 6 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand) |
| 349 | DOORS & WINDOWS |
| 350 | Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately). Sal wood or other similar quality wood |
| 351 | Providing 40x5 mm flat iron hold fast 400 mm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 300x100x150 mm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 352 | Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame. |
| 353 | 30 mm thick Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required Colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames. |
| 354 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 355 | Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright finished of required size with necessary screws. (Shutter area to be measured) |
| 356 | Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : 200x10 mm |
| 357 | Providing and fixing bright finished brass handles with screws etc. complete: 125 mm |
| 358 | Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete. |
| 359 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm) with double speed adjustment with necessary accessories and screws etc. complete. |
| 360 | Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in-charge. |
| 361 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm) |
| 362 | Providing and fixing of vertical/roller blinds width 100 mm regular quantity made from 100 % polyster/Fibre yarn coated with fade resistant polymer to ensure complete opaquety with zero light transmittance, having suitable coating on exterior, including all fixtures and fittings complete in all respect as per design and instruction of Engineer in-charge and as per site conditions. The colour will be approved by the competent authority Make-MAC/VISTA/NOVA or any equivalent make. |
| 363 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm |
| 364 | Providing and fixing of glass door SS Patch Lock with out handle in toughened glass door including all necessary screws etc. complete. |
| 365 | Providing and fixing Steel S.S- 304 (D) Door Pull Both Side Handle of 12 inch, one Set (2 Handles) ( best make of approved quality ) for Glass, Wooden or similar doors including necessary cutting and making good etc. complete |
| 366 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double action hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge (Door handle, lock and stopper etc.to be paid separately). |
| 367 | Providing and fixing fire resistant door frame of section 143 x 57 mm having built in rebate made out of 16 SWG G.I. sheet (zinc coating not less than 120 gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10x4 mm (minimum) alround the frame and fixing with dash fastener of approved size and make, including applying a coat of approved brand fire resistant primer etc. complete as per direction of Engineer-in-charge (Dash fastener to be paid for separately). |
| 368 | Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWG G.I.sheet (zinc coating not less than 120 gm/m2) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge (panneling to be paid for separately). |
| 369 | Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and as per direction of Engineer-in-charge with glass of required thickness having 60 minutes of fire resistance both integrity & radiation control (EW60) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm. |
| 370 | Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete. |
| 371 | Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc |
| 372 | ALUMINIUM WORK |
| 373 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 374 | WALL TILE |
| 375 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).Size of Tile 600x600 mm |
| 376 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 377 | FLOORING |
| 378 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm |
| 379 | Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x600 mm |
| 380 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete. |
| 381 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joint treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab over 0.50 sqm |
| 382 | Extra for providing opening of required size & shape for wash basins/ kitchen sink in kitchen platform, vanity counters and similar location in marble/ Granite/ stone work including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete. |
| 383 | Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : Dark shade pigment using ordinary cement |
| 384 | FALSE CEILING & CLADDING |
| 385 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer39;s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board |
| 386 | Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main \\"T\\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \\"T\\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \\"T\\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \\"T\\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \\"T\\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece. |
| 387 | PAINTING |
| 388 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 389 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 390 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 391 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of Special primer applied @ 0.75 ltr /10 sqm |
| 392 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications :Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 393 | Melamine polishing on wood work (one or more coat). |
| 394 | PLUMBING & SANITARY FITTINGS |
| 395 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 396 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour.450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 397 | Providing and fixing PTMT liquid soap container 109mm wide, 125mm high and 112mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour. weighing not less than 105 gms. |
| 398 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 25 mm dia 10 Kgf/cm2- External work - Exposed on wall |
| 399 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 32 mm dia 10 Kgf/cm2 - External work- Exposed on wall |
| 400 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed/ Concealed on wall |
| 401 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 :15mm nominal bore |
| 402 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid |
| 403 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap |
| 404 | Providing and fixing Polypropylene laboratary sink with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : 20.9 x 15.3 x 11.1 inches; 2.26 Kg |
| 405 | Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour. |
| 406 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe 40 mm dia |
| 407 | Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge |
| 408 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 15 mm nominal bore |
| 409 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 25 mm nominal bore |
| 410 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :15 mm nominal bore |
| 411 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690gms. 15 mm nominal bore |
| 412 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia Pipes |
| 413 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 32 mm nominal outer dia Pipes |
| 414 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.50 mm nominal dia Pipes |
| 415 | Constructing masonry chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C.I. surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design: 18.32.1 With common burnt clay F.P.S. (non modular ) bricks of class designation 7.5 |
| 416 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 417 | Providing and fixing PTMT extension nipple for water tank pipe, fittings of approved quality and colour.20 mm nominal bore, weighing not less than 40 gms |
| 418 | Providing and fixing PTMT grating of approved quality and colour. Circular type100 mm nominal dia |
| 419 | Constructing soak pit 1.20x1.20x1.20 m filled with brickbats including S.W. drain pipe 100 mm diameter and 1.20 m long complete as per standard design. |
| 420 | Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall |
| 421 | Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2 |
| 422 | Supplying and placing of 5000 Litre 1mm thick stainless steel water tank of 1750mm dia , 2600mm height, Stainless steel mounted stand around 180kg and grade of ASTM A240 gr.304/ SS316 BA/2B as per the direction of Engineer in-charge. The rate inclusive of all the transportation, Steel stand support, loading and unloading charges, fixing charges, Labour charges, etc. Nothing shall be additionally paid in this item. |
| 423 | Supply of HDPE Pipe PE 100 (IS 4984/1995), 10kg, 200mm Outer Dia |
| 424 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed on wall |
| 425 | ROAD WORK |
| 426 | Construction of granular sub- base by Providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, Carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in- Charge.With Material conforming to Grade - I ( size range 75 mm to 0.075 mm) having CBR Value- 30 |
| 427 | Providing , laying spreading and compacting graded stone aggregate ( size range 53 mm to 0.075 mm) to wet mix macadam (WMM) specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by tipper to site, for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub - base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer - in- Charge. |
| 428 | 2.5 cm premix carpet surfacing with 2.25 cum and 1.12 cum of stone chippings of 13.2 mm and 11.2 mm size respectively per 100 sqm and 52 kg and 56 kg of hot bitumen per cum of stone chippings of 13.2 mm and 11.2 mm size respectively, including a tack coat with hot straight run bitumen, including consolidation with road roller of 6 to 9 tonne capacity etc. complete ( tack coat to be paid for separately):With Refinery Modified Bitumen CRMB 55 conforming to IRC:SP:53 - 1999 |
| 429 | Tack Coat - RS Bitumen Emulsion - On W.B.M / W.M.M @ 0.4 kg/ sqm - Using Packed Bitumen Rates Providing and applying tack coat using bitumen emulsion conforming to IS : 8887, using emulsion pressure distributor including preparing the surface & cleaning with mechanical broom. 1. With Rapid Setting Bitumen Emulsion 1. On W.B.M / W.M.M @ 0.4 kg/ sqm |
| 430 | SIGNAGES |
| 431 | Design, providing and fixing Digital Printed vinyl signage boards with transparent 3mm acrylic Sheet with 4 nos. SS Studs of Size 16\\" x 10\\". Complete as per the per the direction of Engineer in charge. |
| 432 | Design, providing and fixing Acrylic LED Sign Board of 5cm Letter Thickness 20 - 30cm Letter Height. Complete as per the direction of Engineer in charge. |
| 433 | ELECTRICAL |
| 434 | Point wiring in PVC conduit with modular type switch. |
| 435 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group B |
| 436 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 437 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 438 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 439 | Wiring through PVC conduit |
| 440 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 441 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 442 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 443 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 444 | S/F PVC CONDUIT |
| 445 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm |
| 446 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm |
| 447 | Modular type blanking plate: |
| 448 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 449 | Modular boxes, bases & cover plate: |
| 450 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mmX75mm) |
| 451 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 3 Module (100mmX75mm) |
| 452 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 6 Module (200mmX75mm) |
| 453 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 454 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )1 module moulded plastic box on surface |
| 455 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface |
| 456 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant ) 6 module moulded plastic box on surface |
| 457 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 1 or 2 Module |
| 458 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 3 Module |
| 459 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 6 Module |
| 460 | Modular type switch/socket: |
| 461 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 A switch |
| 462 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 A socket outlet |
| 463 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 A switch |
| 464 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 A socket outlet |
| 465 | Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator |
| 466 | Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket |
| 467 | DB ACCESSORIES |
| 468 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door |
| 469 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 6 way (4 + 18), Double door |
| 470 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 8 way (4 + 24), Double door |
| 471 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A |
| 472 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A |
| 473 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker with overcurrent protection (RCBO), having a sensitivity current upto 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A-40A, 4P, 100mA |
| 474 | Supplying and fixing 40A / 63A, TP MCB, 415 Volts, \\"C\\" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc as required. |
| 475 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 476 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 477 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 478 | Supplying and fixing FP CRCA sheet steel enclosure with provision to mount MCB/Isolator/RCCB/RCBO and other modular devices on surface/ recess complete with connections, testing and commissioning etc. as required. |
| 479 | EARTHING |
| 480 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 481 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 482 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 483 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 484 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 10 SWG) |
| 485 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 486 | SUPPLY OF LT CABLES |
| 487 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4 X 25 |
| 488 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4 X 16 |
| 489 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4X10 |
| 490 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5 X 185 sq. mm |
| 491 | CABLE LAYING |
| 492 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 493 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with25/40x3mm MS flat clamp) |
| 494 | LT CABLE TERMINATION |
| 495 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (25mm) |
| 496 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm) |
| 497 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25 sq. mm (28mm) |
| 498 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 185 sq. mm (57mm) |
| 499 | CABLE TRAYS |
| 500 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 501 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 502 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 503 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 504 | LIGHT FITTINGS & FANS |
| 505 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operatingvoltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuitprotection, THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained tilllife ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum powerconsumption should not more than the specifiedrating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housingsuch that LED junction temperature shall not riseabove 90°C).Powder coated die cast /Extruded aluminiumBody (Thickness > 1.20 mm) 36 watt |
| 506 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Wattoutput . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall besubmitted. Shape size and CCT shall be as approved by Engineer-in-Charge as perrequirement. (Thermal management: heat sink of aluminium housing such that LED junctiontemperature shall not rise above 90°C) Powder coated die cast /Extruded aluminiumBody including trim Powder coated die cast /Extruded aluminiumBody including trim .18 watt |
| 507 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz,Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Wattoutput . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall besubmitted. Shape size and CCT shall be as approved by Engineer-in-Charge as perrequirement. (Thermal management: heat sink of aluminium housing such that LED junctiontemperature shall not rise above 90°C) Powder coated die cast /Extruded aluminiumBody including trim 8 - 10 watt |
| 508 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till lifeends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation 45 DELHI SCHEDULE OF RATES (E&M)-2025 Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 18- 22 Watt |
| 509 | SITC of 2 feet surface/suspended mounted LED batten type luminaire with a power consumption not more than 10 W, luminaire lumen output of 1100 lumens, luminaire efficacy > 110 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a sleek design with extruded aluminum section, white CRCA housing with optically efficient poly carbonate diffuser to provide uniform illumination and wider light distribution. The luminaire shall have a CCT of 4000K /6500 K, CRI > 80, power factor >0.95, SDCM < 5, THD <10%. The luminaire shall be EMI/ EMC compliant and shall have an internal surge protection of 3 kV with 50,000 burning hours as per L70B50 criteria. The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature, including all accessories necessary as required to complete installation. |
| 510 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 511 | SITC of 450mm sweep Wall fan having speed control, oscillation control at bottom as suitable for operation on single phase 230 volt AC supply complete with continuous duty motor and all accessories including mounting as required for complete installation. |
| 512 | SITC of 250mm sweep Exhaust Fan, 900rpm light duty exhaust fan shutter type white colour, 9\\" or 10\\" star rated as per BEE, with its all accessories including mounting as required for complete installation. |
| 513 | SITC of 250mm sweep Ceiling Exhaust Fan, 900rpm light duty exhaust fan shutter type white colour, 9\\" or 10\\" star rated as per BEE, with its all accessories including mounting as required for complete installation. |
| 514 | Online UPS- Input supply: Three Phase, Output supply: Three Phase. Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 0C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swapable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of modules required for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. . Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accessories are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f) Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding theload / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc 10KVA (Each Power module shall be < 10 KVA) Each 208893 |
| 515 | PANEL |
| 516 | SMDB-1 (8 WAY) - Supply, installation, Testing and Commissioning of factory fabricated OEM 415 V 50 Hz 4 way complying to IEC 61439 part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wire meter chamber with all meters & indicating lamps, Aluminium bus bar, neutral link, DIN bar with allaccessories etc, complete with necessary control wiring and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper. All copper joints shall be tinned. Knock outs of proper diameter shall be provided on gland plates. Theheight of the operating handle of switch gear shall be minimum 300 mm and maximum upto 1800mm from the finished floor level complete as per the directions of engineer in charge. Incomer -1 no. 160 A 36 kA TP MCCB, Outgoing: 5Nos 63A TP 25 kA MCCB,1 Nos 40A 25kA TP MCCB, 2 NOS 25A 25kA TP MCCB |
| 517 | NETWORK |
| 518 | Supplying, Installation, Testing and commissioning of CAT6A Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/ULverification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 519 | Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non- Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required. 1 Run of cable |
| 520 | Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color, Use for 24- 26 AWG stranded wires etc. complete as required. |
| 521 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm ToughenedGlass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. 6U rack |
| 522 | Supply, Installation, Testing & Commissioning of 16 Port Network Switch with 16 No's of 10/100/1000 ports and 2 Gigabit Copper/ SFP Combo ports for uplink |
| 523 | Supplying Installation Testing and Commissioning of 2MP IP IR Dome Camera having followingspecifications, type of lens and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio:>50 dB, Camera should display Camera title, Date &Time in live & recorded video2)Image Sensor: 1/2.8\\" or better progressive ScanCMOS to get color image even at night condition(Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 3) Compression (Minimum):-Video:- H.265 or better,H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 4) Wide Dynamic Range:- WDR (120db or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming, configurable (Main stream: 2MP (1920×1080)@25/30 fps,Sub streams minimum:720P@25/30 fps).7) Image Setting: Rotate Mode, saturation, brightness,contrast, sharpness adjustable through client softwareor web browser, Edge Analytics: Tripwire, Intrusion,Motion Detection8) Cyber Security: AES 256-bit Encryption,Configuration encryption, trusted execution, Digest,security logs, account lockout, syslog, videoencryption, IP/MAC filtering, HTTPS, trusted upgrade,trusted boot.9) Onboard Storage: Camera should support built-inMicro SD/SDHC/SDXC Card slot upto 512 GB. Itshould be supplied with minimum 128GB memoryCard.280 10) Recording Management: Format SD, overwrite, storage management, video to NAS device 11) Alarm Trigger : Motion/tampering detection; audio detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,unicast13) System Capability: ONVIF, Camera shall supportopen source VMS14) Ethernet: 1 RJ 45 10/100 Ethernet port15) Audio : It should support 1 x Built-In Mic and 1/1Alarm In/ Out for External Mic. and Speakers as persite requirement.16) Power Input: The camera should supportsimultaneous dual power input—12 VDC (via poweradapter) and PoE (802.3af)—to ensure continuousoperation in the event of a failure in one power source.17) Power Requirement: 12VDC/24 VAC/PoE(802.3af)/ePoE18) Housing/ Enclosure:- IP67 weather proof, IK10, Metallic body 19) Operating Condition:- Ambient Temperature:- (- )05°C to 50°C, humidity 95% (max) (non-condensing) 20) IR life: 40000 hours or higher 21) Video Bit rate: 32 KBPS - 8 MBPS or better22) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS 2MP (@ 25/30fps@1080P (1920×1080)) IP IR Dome Camera with 2.8/ 3.6mm fixed lens |
| 524 | Supplying Installation Testing and Commissioning of 2MP Fixed Lens IP IR Outdoor Bullet Camera havingfollowing specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: >50 dB,Camera should display Camera title, Date &Time in live & recorded video 2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS to get color image even at nightcondition(Minimum Illumination: 0.006 Lux@ F1.4,AGC ON, 0 lux with IR or better) True Day & NightHigh Performance Mechanical IR cut filter with autoswitch, Integrated IR Source (Auto, Manual)- InbuiltSmart IR LED's with effective distance upto 50 meteror better and 30 meter for colour view in night,Imaging: 1/3s to 1/30000s electronic shutter support,Auto Gain Control , White Balance- Auto, Back LightCompensation, Multi zone Privacy Masking, HLC,Digital Watermarking.3) Compression (Minimum):-Video:- H.265 or better,H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726,AAC, G.7234) Wide Dynamic Range:- WDR (120db or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming, configurable(Main stream: 2MP (1920 ×1080)@25/30 fps Sub streams minimum:720P@25/30 fps).7) Image Setting: Rotate Mode, saturation, brightness,contrast, sharpness adjustable through client softwareor web browser, Edge Analytics: Tripwire, Intrusion,Motion Detection8) Cyber Security: AES 256-bit Encryption,Configuration encryption, trusted execution, Digest,security logs, account lockout, syslog, videoencryption, IP/MAC filtering, HTTPS, trusted upgrade,trusted boot.9) Onboard Storage: Camera should support built-inMicro SD/SDHC/SDXC Card slot upto 512 GB. Itshould be supplied with minimum 128GB memoryCard.10) Recording Management: Format SD, overwrite,storage management, video to NAS device,11) Alarm Trigger : Motion/tampering detection; audiodetection; network disconnection detection; IP conflictdetection; memory card state detection; memoryspace detection12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP,NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,unicast,13) System Capability: ONVIF, Camera shall supportopen source VMS 2MP @ 25/30fps@1080P (1920×1080) Outdoor Bullet Camera with 2.8/ 3.6mm fixed lens |
| 525 | 16 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16, 2nd screen: 1/4/8/9/16 |
| 526 | Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. |
| 527 | TELEPHONE |
| 528 | Supply of User Phone- Analog phone |
| 529 | Supplying and drawing following pair 0.5 mm dia FRLS/HFFR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair |
| 530 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet |
| 531 | Supply, Installation, Testing and Commissioning of air-cooled VRV (Variable Refrigerant Volume) / VRF (Variable Refrigerant Flow) outdoor units (ODUs) equipped with highly efficient, full DC inverter-driven scroll compressors only, air-cooled heat exchangers having internally grooved copper tubes, and low-noise condenser fans. The units shall have auto-addressing, an auto-check function for connection errors, and operate with R-410A or equivalent refrigerant gas. Each unit shall be fitted with a noise filter, high-pressure switch, fan motor overload protector, over-current relay, inverter overload protector, and other necessary protective devices. A power failure of one or more IDUs shall not affect operation of other units/circuits. The units shall deliver the rated capacity in accordance with IS 18728:2024 and CPWD specifications. The efficiency of the ODUs shall meet the latest ASHRAE / ECSBC 2024 standards. Suitable vibration isolators shall be provided with the ODUs. The system shall operate at outdoor conditions up to a maximum ambient dry-bulb temperature of 50°C. Each unit shall be equipped with an oil recovery system to ensure stable operation with long refrigeration piping lengths and an oil-balancing circuit to prevent inadequate lubrication. Compatibility with centralized control systems such as BACnet, LonWorks, and Modbus is required. The ODUs shall be suitable for a 3-phase, 415 V, 50 Hz power supply, with suitable interconnecting control cabling between IDUs, ODUs, and the central controller. All necessary power cabling up to the ODU electrical panel, pressure testing, additional refrigerant charging for commissioning, and all associated accessories required for commissioning shall be included in the scope of work. The VRF outdoor unit circuit schedule shall be as per the tender drawings/specifications.. |
| 532 | Supply, Installation, Testing, and Commissioning of VRV/VRF 1.0TR high-wall type indoor unit complete with a corded/cordless remote (subject to consultant's approval). The machine shall be suitable for operation on 230 V, 50 Hz, single-phase AC supply, including all power cabling to the nearest power socket. The unit shall include a washable synthetic media pre-filter, DC fan section with a low-noise fan/dynamically balanced blower, multi-speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pan, and necessary accessories, etc.. |
| 533 | Supply, Installation, Testing, and Commissioning of VRV/VRF 1.3TR high-wall type indoor unit complete with a corded/cordless remote (subject to consultant's approval). The machine shall be suitable for operation on 230 V, 50 Hz, single-phase AC supply, including all power cabling to the nearest power socket. The unit shall include a washable synthetic media pre-filter, DC fan section with a low-noise fan/dynamically balanced blower, multi-speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pan, and necessary accessories, etc.. |
| 534 | Supply, Installation, Testing, and Commissioning of VRF/VRV 1.6TR ceiling-mounted low-static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low-noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, a corded remote control, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz.. |
| 535 | Supply, Installation, Testing, and Commissioning of VRF/VRV 2.0TR ceiling-mounted low-static ductable type indoor unit along with a corded remote. The unit shall be equipped with a washable synthetic media pre-filter, a fan section with a low-noise, dynamically balanced fan, a multi-speed motor, a coil section with a Dx copper coil, an electronic expansion valve, a corded remote control, an outer cabinet, vibration isolators, a drain pan, and other necessary supports, suitable for operation on a single-phase AC supply of 230 V ± 10%, 50 Hz.. |
| 536 | Supply, Installation, Testing, and Commissioning of VRV/VRF 2.0TR Cassette Type Indoor Ceiling Mounted Units along with a Cordless Remote. The machine should be equipped with a synthetic washable media pre-filter, a multi-speed motor, a DX copper coil, an electronic expansion valve, and an insulated drain pan as required.The unit is to be enclosed in a powder-coated cabinet. The blower shall be dynamically balanced and designed for silent operation. The address of the indoor unit shall be set automatically in case of individual and group control. The units should be suitable for operation on a single-phase, 230V, 50Hz supply. The machine should include a high-lift drain pump as necessary, a drain connection with a U-trap, and all necessary fittings, elbows, electrical cabling from the power plug, and structural supports, etc |
| 537 | Supply, Installation, Testing, and Commissioning of VRV/VRF3.2TR Cassette Type Indoor Ceiling Mounted Units along with a Cordless Remote. The machine should be equipped with a synthetic washable media pre-filter, a multi-speed motor, a DX copper coil, an electronic expansion valve, and an insulated drain pan as required.The unit is to be enclosed in a powder-coated cabinet. The blower shall be dynamically balanced and designed for silent operation. The address of the indoor unit shall be set automatically in case of individual and group control. The units should be suitable for operation on a single-phase, 230V, 50Hz supply. The machine should include a high-lift drain pump as necessary, a drain connection with a U-trap, and all necessary fittings, elbows, electrical cabling from the power plug, and structural supports, etc |
| 538 | Supply and installation of indoor Refnet / Y-joint separation tubes for refrigeration pipe joints and headers, in appropriate orientation to enable proper distribution of refrigerant. The distribution joints shall be factory insulated with pre-formed sections of expanded polystyrene or equivalent.. |
| 539 | Supply and installation of outdoor Refnet / Y-joint separation tubes for refrigeration pipe joints and headers, in appropriate orientation to enable proper distribution of refrigerant. The distribution joints shall be factory insulated with pre-formed sections of expanded polystyrene or equivalent.. |
| 540 | Supply, Installation, Testing, and Commissioning of centralized type remote controller, color touchscreen type with UPS battery backup, all-inclusive of necessary installation supports and wiring. The controller shall function as an advanced air conditioning management system, providing complete control of VRV/VRF air conditioning equipment (including connected air handling units (AHUs)). It shall offer user-friendly operation through its touchscreen, icon display, and color LCD display. The controller shall be compatible with BACnet, LonWorks, or Modbus interface. The controller shall control up to 64 groups of indoor units with the following functions: 1. Start/stop of air conditioners as a zone, group, or individual unit 2. Temperature setting for each indoor unit or zone 3. Switching between temperature control modes, fan speed adjustment, and airflow direction control, including enable/disable of individual remote controller operation 4. Monitoring of operation status, including operation mode, temperature settings of individual indoor units, maintenance information, and troubleshooting details 5. Scheduling indoor unit operating time 6. Displaying air conditioner operation history.. |
| 541 | Supply, Installation, Testing, and Commissioning of the Soft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:1/4 inch (6.35 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 542 | Supply, Installation, Testing, and Commissioning of theSoft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:3/8 inch (9.52 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 543 | Supply, Installation, Testing, and Commissioning of the Soft drawn Copper Pipe 19/20 Gauge with 19mm thick Insulation:1/2 inch (12.7 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 544 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:5/8 inch (15.88 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 545 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:3/4 inch (19.05 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 546 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:7/8 inch (22.2 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 547 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1.0 inch (25.4 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 548 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/8 inch (28.6 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 549 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/4 inch (31.8 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 550 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-3/8 inch (34.9 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 551 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 18/19 Gauge with 19mm thick Insulation:1-1/2 inch (38.1 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 552 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 17/18 Gauge with 25mm thick Insulation:1-5/8 inch (41.3 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 553 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 16/17 Guage with 25mm thick Insulation:1-3/4 inch (44.45 mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 554 | Supply, Installation, Testing, and Commissioning of the Hard drawn Copper Pipe 16/17 Guage with 25mm thick Insulation:1-7/8 inch (47.62mm) gas/liquid insulated copper piping. The insulation for copper piping shall be round, closed-cell, antimicrobial nitrile rubber sleeve insulation. The minimum R-values for pipes shall be 0.4 for pipe sizes less than 40 mm and 0.7 for pipe sizes 40 mm and above. Insulation shall be finished with 7 mils of factory-laminated fiberglass cloth. The thermal conductivity of the insulation material shall not exceed 0.035 W/(m·K) at a mean temperature of 0°C as per EN ISO 8497. The installation includes suction filters for the gas line, a filter drier, and a sight glass for the liquid line per the system design between each indoor and outdoor unit. The scope of work shall include chasing, drilling, core cutting, and concealing in walls, as per site conditions, along with the required pipe fittings and accessories such as bends, tees, reducers, Y-joints, supports, refnets, and wall clamps, for the proper commissioning of the VRF/VRV circuit. The thickness of the fittings shall match the pipe thickness. PVC sleeves shall be securely fixed over the copper pipes to provide a protective barrier at all wall openings and along support channels. The work shall be completed as per the consultants approval. The contractor shall ensure that the pipe size and thickness of all refrigerant pipes installed are in accordance with the Original Equipment Manufacturer (OEM) recommended technical specifications.. |
| 555 | Supply, installation, and testing of shielded copper flexible communication cabling between VRF indoor and outdoor units. The communication cable shall be routed through PVC conduits. The cable size shall be 2-core x 1.5 SQMM (or) as per VRF OEMs technical specifications.. |
| 556 | Supply, installation, testing, and commissioning of 25mm dia rigid UPVC condensate drain piping duly insulated with 9 mm thick closed-cell nitrile finished with 7 mils factory-laminated glass cloth, along with necessary U-trap, clamps, fittings such as bends, tees, and other necessary fittings, adequately supported as per site requirements, conforming to tender specifications.. |
| 557 | Supply, installation, testing, and commissioning of 32mm dia rigid UPVC condensate drain piping duly insulated with 9 mm thick closed-cell nitrile finished with 7 mils factory-laminated glass cloth, along with necessary U-trap, clamps, fittings such as bends, tees, and other necessary fittings, adequately supported as per site requirements, conforming to tender specifications.. |
| 558 | Supply, installation, testing, and commissioning of 40mm dia rigid UPVC condensate drain piping duly insulated with 9 mm thick closed-cell nitrile finished with 7 mils factory-laminated glass cloth, along with necessary U-trap, clamps, fittings such as bends, tees, and other necessary fittings, adequately supported as per site requirements, conforming to tender specifications.. |
| 559 | PIPES AND ACCESSORIES |
| 560 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :25 mm dia |
| 561 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :32 mm dia |
| 562 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :40 mm dia |
| 563 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :50 mm dia |
| 564 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :65 mm dia |
| 565 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia |
| 566 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :100 mm dia |
| 567 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :150 mm dia |
| 568 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required : 80mm dia |
| 569 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required : 100mm dia |
| 570 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.150 mm. Dia |
| 571 | VALVES |
| 572 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required80 mm dia |
| 573 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required100 mm dia |
| 574 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required150 mm dia |
| 575 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :80mm dia |
| 576 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :100mm dia |
| 577 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :150mm dia |
| 578 | Supply, installation, testing and commissioning of lever operated 25mm dia Gate/ball valve conforming to IS 9890:1981 with forged body, brass/stainless steel ball and shall be internally threaded to receive pipe connections25mm dia |
| 579 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conformingto IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required:Single headed Stainless steel |
| 580 | AIR RELEASE VALVE;Supply, installation, testing and commissioning of gunmetal air release valve 25 mm with necessary fittings etc. complete. |
| 581 | SWITCHES |
| 582 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required |
| 583 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 584 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc asrequired.100mm dia |
| 585 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304) |
| 586 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.a.20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585b.20 mm nominal internal dia gun metal globe valve & nozzle. c.Drum and brackets for fixing the equipmets on wall.d.Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30 m |
| 587 | Supply, installation, testing and commissioning of hose boxes wall/pedestal type of size 600 x 250 x 400 mm made out of 18 gauge MS sheet steel with front side glass, locking arrangement and painted with approved colour completed as required and as per specifications. |
| 588 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Stainless Steel (Grade 304) |
| 589 | Providing, fixing, testing and commissioning of Ball Valve, PN-25 Forged Brass & Nickel / Chrome Plated, conforming to IS: 9890 with Screwed Female Ends to BS:21, and with non-corrosive handle / lev er, all as per Technical specification. including necessary accessories and connections. Dia - 20mm. |
| 590 | SPRINKLERS |
| 591 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Pendent Sprinkler |
| 592 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, centre bracket, stock bar of following sizes complete as required.1000mm |
| 593 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 594 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Horizontal side wall sprinkler |
| 595 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Upright Sprinkler |
| 596 | FIRE BRIGADE |
| 597 | FIRE BRIGADE INLET : Supply, installation, testing and commissioning of 3 way tank filling Inlet connection of 63 mm dia. valves instantaneous coupling type arrangement to be connected to wet riser main. |
| 598 | FIRE EXTINGUSHERS |
| 599 | SITC OF ISI marked (IS:2878) fire extinguisher CO2 type capacity 4.5kg. Flat base including valve, discharge hose of not less than 10mm dia , 1 meter long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1996 filled to filling rate of not more than 0.667 and wall bracket (fixed with anchor Fastner) or floor mounted |
| 600 | Supply and fixing of 4 Kg ABC Dry Powder (Stored Pressure) Type Fire Extinguisher. pressurized with dry nitrogen gas at 15 bar. Design, construction and testing as per IS 2171-1999 external epoxy powder coating with PO Red Shade No. 538 of IS 5, Supplied with standard accessories. |
| 601 | SIGNAGES |
| 602 | Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters FIRE in black and gold. Cost shall be inclusive of providing MS stand for 2 nos of fire buckets, duly painted over a coat of primer. |
| 603 | Providing and fixing standard fireman's axe with heavy rubber handle. |
| 604 | Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMPROOM, FIRE CONTROL ROOM, ELECTRICALROOM, FIRE LIFT, PASSENGER LIFT Etc.) standard size(500x225 mm as per conventional design / colour code on 3 mm thick aluminium composite panel, conforming to IS 9457. The signage will be either fixed on the wall with the help of chain and screws etc. complete as required as per the technical specification." |
| 605 | SIGNAGE : Supply installation of necessary Signages as per standard including " FIRE DUCT,FIRE EXIT,EXIT,NO SMOKING etc." |
| 606 | SIGNAGE : Supply installation of Signage "ASSEMBLY POINT" |
| 607 | SIGNAGE : Supply installation and testing of emergency exit system with battery backup |
| 608 | FIRE ALARM SYSTEM |
| 609 | Supplying, installation, testing & commissioning of smokedetector with builtin LED and mounting base complete withall connections etc. as required. |
| 610 | Supplying, installation, testing & commissioning of manualcall boxes of MS construction in surface/recess with stainlesssteel chain & hammer assembly complete with glass andpush button etc. as required. |
| 611 | Supplying, installation, testing & commissioning fire alarmsounder with facility to make announcement, mounted inM.S. box (16 SWG) with hinged cover plate & suitable foroperation with amplifier i/c line matching transformer etc.complete as required. |
| 612 | Supplying, installation, testing & commissioning sector panelsuitable for following zones, complete with visual indicationsfor short circuit fault, open circuit fault, fire condition and allother standard facilities as per IS:2189 with mimic diagramfor all area/zone covered, complete with all connections,interconnections as required. 4 Zone |
| 613 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable,600/1000V rated with annealed copper conductor havingXLPE insulation, steel wire armouring & FRLS/HFFR outersheath complete as required. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail