| 1 | Supply , Carriage upto site,installation ,testing & commissioning of 11/0.433kV, 63 KVA , 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Efficient Level-2, Al. wound , and with LV Cable Box having detachable Al. Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable. |
| 2 | Supply , Carriage upto site , Erection , Testing and Commissioning of Steel Tubular Poles 9 Mtr Long (410-SP-33) with Planting depth of 1/6 th of the height of Poles as per REC standard. |
| 3 | Supply , Carriage upto site , Erection , Testing and Commissioning of Steel Tubular Poles 8 Mtr Long (410-SP-15) with Planting depth of 1/6 th of the height of Poles as per REC standard. |
| 4 | Supply & fixing of GI nuts and bolts of sizes |
| 5 | Supply , Carriage upto site , Laying , stringing, tensioning and binding of 50 mm2 ACSR Conductor (Rabbit) , including joints by PG clamps wherever required as per REC standard. |
| 6 | Cement bottoming of S T Ploes 8Mtrs long in 1:2:4 mix , 0.40 cum/pole, muffing 20 cm above ground, including plaster and curing of concrete as per REC standard. |
| 7 | Cement bottoming of S T Ploes 9Mtrs long in 1:2:4 mix, 0.48 cum/pole, muffing 20 cm above ground, including plaster and curing of concrete as per REC standard. |
| 8 | Supply and Painting of poles with one coat of redoxide and two coats of Aluminium paint of standard quality including Marking of Poles |
| 9 | Supply , installation ,testing & commissioning of pole Earthing Complete by GI Pipe 40 mm 3mtr long through GI Strip 25x3 mm as per REC standard. |
| 10 | Supply , installation ,testing & commissioning of GI “V’ cross-arm (75x40x40x6)mm with Pole Top Bracket including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket as per REC standard. |
| 11 | Supply , installation ,testing & commissioning of Iron GI Channel/Angle/Flat of sizes including clamps for Transformer Pad/G.I Channel Bedding ,L.A Set/G.O Set/Horn Gapas per specification enclosed in Drawing.( Refer Drawing) |
| 12 | Supply , installation ,testing & commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type as per REC standard |
| 13 | Supply , installation ,testing & commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A confirming to ISI specification |
| 14 | Supply , installation ,testing & commissioning of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 15 | Supply , installation ,testing & commissioning of Sundry items like Aluminium lugs, Jumpers, binding Tape, |
| 16 | Supply , installation ,testing & commissioning of --Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover as per REC standard. |
| 17 | Supply & fixing ,testing, commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm as per REC specification. |
| 18 | Supply , installation ,testing , commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mmas per REC specifications. |
| 19 | Supply & laying, testing ,commissioning of 120 mm² single core Cable,1.1kV Grade, XLPE Insulated Stranded Conductor FRLS type |
| 20 | Supply and Fixing of LT Structure Single shackle set (Mukhi Type) as per REC standard. |
| 21 | Supply & fixing, testing ,commissioning of LT shackle Insulators 16KN as per REC specification. |
| 22 | Supplying and Fixing of Danger Plates with clamps with writing in English and Regional Language |
| 23 | Providing, Installation, Fabrication of Sign Board of dimensions 3ft' x 2ft', 2mm MS Painted Sheet indicating Name of the work, Name of Loaction/Block, Name of Scheme, Est. Cost, Year & Executing Agency: Please Enable Macros to View BoQ information |