| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2X 1.5 sq.mm FRLS PVC insulated copper conductor ( Havell/Polycab/ Anchor/equivalent as directed by engineer incharge.) single core cable in surface / recessed medium class PVC conduit ( including cost of conduit), with modular switch ( ABB /Legrand /SSK/schneider/Eq.make.), modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Sample to be approved by EIC |
| 2 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required,ISO/IEC Certified of Havells/ Legrand/ Panasonic/ Anchor/ Schneider/ eq. Make & shall be approved before execution of work. |
| 3 | Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/ Polycab/ Anchor / eq. make to be approved by EIC including Cost of Conduit 25mm) |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified r ( ABB /Legrand /SSK/schneider/Eq.make.) & shall be approved before execution of work. |
| 5 | Wiring for 6Amp Plug(Computer Point) with (P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Polycab/Anchor/ eq. Make to be approved by EIC) (including Cost of Conduit 25mm) |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings), ISO/IEC Certified ( ABB /Legrand /SSK/schneider/Eq.make.) & shall be approved before execution of work. |
| 7 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required of Schneider /Havells/ Legrand/Anchor roma plus/ eq. Make to be approved by EIC |
| 8 | Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLS PVC insulated copper conductor, single core Cable (Havells/Polycab/Anchor / eq. make to be approved by EIC) in surface/Recessed medium class PVC conduit (Incl. cost of conduit) & shall be approved before execution of work. |
| 9 | 2x10 sq.mm+ 1x10 sq.mm (P+N+E) for Power point Sub main in One run from Main Panel to Distribution Boards |
| 10 | 2x6 sq.mm+ 1x6 sq.mm (P+N+E) for Lighting Sub main in One run from Main Panel to Distribution Boards. |
| 11 | Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/Schneider / eq. make to be approved by EIC) |
| 12 | Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/Schneider / eq. make to be approved by EIC) |
| 13 | 40 Amp. |
| 14 | 63 Amp. |
| 15 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) |
| 16 | 8(4+24) way, Double door |
| 17 | Supply/Installation/Testing and Commissioning of 18W + LED Surface Mounted Panel (Commerical Type) light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Philips/Havell's/Wipro/ eq. make to be approved by EIC |
| 18 | Providing & Fixing of IK08 IP-66 protected high power LED 50 Watt flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 Im/wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR:-High Power LED Flood Light Minimum lumen output 6200 Im of Havells/Crompton/Philips/ eq. Make as approved and to be installed on outside block including S/F of suitable size of Gyser bolt.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of two years reckoned from date of successful commissioning /handing over of site to intending department. |
| 19 | Supply,Installation,Testing and Commissioning 450 Cu.m/Hr. AC 220-240 Volts, 50 Hz industrial type Exhaust fan Material with inbuilt thermo cut-off Protection and Noise Level not exceeding 37 dB of Following Sizes including connection etc.Usha 450mm Shutter Typed ( heavy duty) |
| 20 | Supply/Installation/Testing and Commissioning of 1200 mm sweep, ceiling fan with 03 No. blades, 30 cm long down rod, 02 No. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havells/Polycab/Orient / eq. make to be approved by EIC.(Minium 3-Star) |
| 21 | Supply/Laying/Connecting and Commissioning of 70 sq.mm 3.5-Core XLPE/PVC insulated and steel armored 1.1 KV grade Aluminum Cable of Havells/Polycab/Anchor / eq. make to be approved by EIC with required size of thimbles dully crimped with hydraulic crimping tool including Providing/Fixing of saddles/clips with making of connection and partially to be laid underground through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench .(Material to be approved before execution) |
| 22 | Supply/Installation/Testing and Commissioning of CPRI Approved (IS/IEC:61439) Main Controlling Panel,fabricated out of heavy gauge sheet steel ,dully Painted with powder coated paint ,dust protected ,earth terminal fitted on epoxy cleats, volt meter & Ammeters with selector switch & CT Coil of required ratio with all necessary connections & inner wiring of panel on both heating and lighting circuits. The switches are connected with bus bars inside panel & manufacturer CPRI Certified.The switch are adjustable type made of Havells/ L&T/ABB/Legrand/Siemens / eq. make to be approved by EIC and change over switch should be of Havells/ L&T/Legrand/ Schneider / eq. make to be approved by EIC.(1) Normal Incomer:a) 160 Amp-4-Pole ,65kA C-CURVE MCCB with extended terminals Havells/L&T/Legrand/Schneider / eq. make to be approved by EIC as approved=01 No. b) 250 Amps TPN Al. Bus Bar Set = 01 Set,Digital Voltmeter ,Ammeter ,C.T Coils with Selector Switch & Phase indicator Set.(2) Outgoing:(1) Normal outgoing for Heating/Lighting etc load(a) 40-Amp DP MCB = 02 No. for lighting load(b) 63-Amp DP MCB = 02 No. for heating load |
| 23 | ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER ROD EARTHING SYSTEMNecessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value.Supply,Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 20mm Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through suitable DWC High Density Poly ethylene Pipe having Corrugation complete job. |
| 24 | Supply/Laying of 25/32/38mm Dia and 2mm thick PVC Conduit/Lockable Channel of Anchor/Ravindra Blue/Finolex / eq. make to be approved by EIC with other accessories like bends,etc complete to be laid in wall for downs and finishing the surface to its original shape by cement mortar plastering/Wall Putty/Paint etc. Please Enable Macros to View BoQ information |