Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | SITC OF VCB PANEL, TRANSFORMER & LT PANEL |
| 2 | SITC of Indoor-type, floor mounted,metal clad,single tier, totally enclosed and fully interlocked, fully compartmentalized, free standing, 6 kV VCB Panel with 3 Nos 800 A VCBs (1 Incomer + 2 Outgoing) as per IS 13188, as ammended upto date and as per detail specification and approved make attached ( uploaded in the specification section) , suitable for use on 6 KV, 3 Phase,50 Hz AC supply to energise 2 nos 630 KVA Mineral Oil Type Transformers . |
| 3 | SITC 630 KVA, 3 Phase , Mineral Oil Type Transfirmer suitable for operation in 6KV/0.433 KV, 415V, 50Hz power supply, having cable end box in the HV side & provision for bus truncking at LV side and all accessories and conforming to IS 11171-1985 & IS - 2026 with latest modification (if any) & CBIP Specification and as per detail specification and approved make attached ( uploaded in the specification section) |
| 4 | MAIN LT PANEL |
| 5 | SITC of floor mounted indoor type expandable cubical MV Switchboard with ACB/MCCBs in suitable enclosure having Short Circuit withstand capacity of 31 MVA for one second, fabricated by CPRI Approved panel builder as per detail specification and approved make attached ( uploaded in the specification section) [I/C 1000A 4P ACB - 2 Nos & Buscoupler 1000A 4P ACB - 1 No with electrical-mechanical Interlock, BBC 1600A 4 Bars- 2 Set, O/G : 800A 4P ACB-3 NOS+ 400A 4P MCCB- 3 NOS + 250A 4P MCCB - 2 NO + 125A 4P MCCB - 1 NO] |
| 6 | LT SOURCE INSIDE LAUNDRY |
| 7 | SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section)[I/C 800A 4P ACB -1 Nos, BBC 1200A 4 Bars- 1 Set ] |
| 8 | PUMPROOM PANEL |
| 9 | SITC of floor mounted Indoor type extensible cubical type LT Panel,fabricated by CPRI approved panel maker as per size, design & drawing to be approved by EIC and conforming to relevant IS with latest modification and as per detail specification and approve make attached ( uploaded in the specification section)[I/C 250A 4P MCCB -1 No , BBC 415A 4 Bars- 1 Set, O/G : 63A TPN SFU - 6 NOS] |
| 10 | Making testing arrangement and submitting all the test reports for high voltage testing of specified voltage incl. checking & testing of all HT & LT equipments incl. earth resistance test and any other tests as desired as per notification no. 826/PO/O/C-IV/IE-06/12 Dated 28/05/2025, Department of Power , Special Secretary to Govt of WB, and Schedule II of FORM-III Central Electricity Authority ( measures relating to safety and electric supply) regulations, 2023. |
| 11 | SITC OF BUS TRUNKING ARRANGEMENT |
| 12 | Supplying, installing by suspension on ceiling , testing andcommissioning of following capacity Sandwich Type Rising Mains foruse on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal cladenclosure having IP-54 rating after fixing the tap off boxes and allaccessories, made of 1.6mm thick steel sheet duly powder coated inconvenient sections complete with 4 Nos aluminium bus bars havingcurrent density of 130 A/ sq cm at nominal current rating, necessaryjoints, elbow joints & expansion joints and bends, fire barrier at eachfloor, provision of tapping at every metre, adopter box and copperflexible for joints, continuous earthing with 2 Nos aluminium strip ofsuitable size (one on each side) including, G.I. clamping brackets,suspenders, angle iron bracket, steel fasteners, connecting to earthingsystem etc. as required. [From secondary (LT) terminal of 2 nos 630 KVA Oil type transformer to 2 nos 1000A incomer ACB of LT panel board ] |
| 13 | (SUB-STATION &Sub-Panel EARTHING) |
| 14 | Excavation of soil for installation of Earth Electrode and filling & ramming as to GS. For soft soil. |
| 15 | Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts.long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts.[For 2nos Transformers Neutral - 4nos, 2 nos transformer Body-4 nos, Consumer HT panels (3 panel breaker)-2nos, Utility gear- 02 nos, Main LT panel-2nos.] |
| 16 | Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts[Sub Panel-1 & 2 = 4nos, Pump Panel=2nos, LC= 6nos] |
| 17 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) MS hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe as to GS. |
| 18 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 19 | Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc. |
| 20 | S&D 150 sq. mm. single core multistrand PVC insulated flexible Cu wire in suitable size of PVC flexible pipe (reinforced) from nutral earth busbar to transformer point as required (for Transformer neutral earthing) |
| 21 | Construction of Masonry Trench of size 800mmx600mm with both side wall & base made up of breaks, including groove for holding of MS checker plate. The whole Masonry Trench should be finished with net cement. |
| 22 | Supplying & fixing 40mm dia medium gauge GI Pipe ( ISI-Medium)Protection with necessary fittings and jointing metarials asrequired. |
| 23 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish.a) Above 95 sqmm at an average depth of 100 mm infloor/pavement/wall etc. |
| 24 | Finishing of the 150 Sqmm PVC insulated wire ends by socketting withring type copper sockets and insulated tapes etc., includingsupplying sockets, tapes. |
| 25 | Insulating the 65 x 8 mm M.S. flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar). |
| 26 | Note: All bolts/washers/nuts etc must be are of Stainless steel type and washers must be spring type. |
| 27 | ( SAFETY EQUIPMENT ) |
| 28 | Providing & fixing danger plates made of mild steel at least 2mm thick & vitreous enameled white on both sides & with inscription in signal red colour on front side as required. |
| 29 | High Voltage - size 250mm x 200mm |
| 30 | Medium Voltage - size 200mm x 150mm |
| 31 | Providing and fixing carbon dioxide (CO2) type fire extinguishers conforming to IS 15222-2002 and cylinders fully charged of following capacity(4.5 Kg ) [Make - Fire Shield/ Ceasefire] |
| 32 | Supply and fixing of foam fire extinguishers conforming to IS 4989-2006, Portable type 9 lit capacity hanged on wall with bracket complete as required. [Make - Fire Shield/ Ceasefire] |
| 33 | Supply and fixing safety instruction chart in word duly framed with 5mm thick glass as required (approx. Front area 1.20 sq.mt.) |
| 34 | Providing of set of 4 nos. 9.5 litre capacity GI bucket painted in post office red colour with prior coat of red-oxide paint and written with white paint 'FIRE' and mounted on MS angle iron frame with bracket and suitable base of appropriate size & capacity I/c filling sand etc. |
| 35 | Providing First Aid Box as approved by St. John Ambulance Brigade / Indian Red Cross conforming to IS 13115-1991. |
| 36 | Supply and fixing shock treatment chart duly mounted on a wooden frame with 5mm thick glass as reqd. (approximate front area 1.20 sq.metre). |
| 37 | Providing of rubber mat 2 mtrs Length x 1 m. wide and 12mm thick to withstand 15 KV dielectric strength as per IS 15652-2006. |
| 38 | Providing of rubber mat 2 mtrs Length x 1 m. wide and 6mm thick to with stand 3.3 KV dielectric strength as per IS 15652-2006. |
| 39 | S/D of 11kV grade rubber/equivalent gloves (ISI marked). |
| 40 | Supply & Delivery of Safety Helmet ISI Certified Safety Helmet, Easy fit Ratchet with Adjustable Chin Strap, Lightweight Comfortable Hard Hat, Stylish Executive Style, Construction & Outdoor Activity (White) |
| 41 | Supply and delivery Clamp Meter, True RMS AC Current: 1000A,DC Current: 1200A,AC Voltage: 750V,DC Voltage: 1000V,Resistance: 400- 40M,Capacitance: 4nF, 40nF, 400nF, 4uF, 40uF,Freqeuncy: 9.999 to 999.9Hz, 9.9999Mhz,Duty Cycle: 10-90%,Temperature: 20-750 Degree,Data Hold APO, Duty Cycle, Frequency 4200 Counts.(Make:-MECO 3600+/ MECO-3600) for 2 Year warenty with maintenance. |
| 42 | Submission of a complete drawing of power distribution from Sub Station up to SPNDB( Computer AUTOCAD generated & printed in A1 sheet in Triplicate) showing HT & LT cable ducts single line power diagram EI Layout Earthing system ( Equipment neutral earthing) etc entire plan as per direction & satisfaction of EIC and as per reqirement of DOE). |
| 43 | (HT CABLE) |
| 44 | Supplying of 6.6 KV (UE) Grade XLPE Aluminium conductor, PVC sheathed, armoured cable conforming to IS 7098, of earthed system of following size.[ From Supplier HT Gear to Consumer HT Gear and to Transformer]. |
| 45 | 3 Core x 300 Sq.mm |
| 46 | (LT CABLE) |
| 47 | Supply of XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes Note : Cables may be run single run/double run etc.and conforming to IS: 7098(Part-I):1988/1554(Part-I):1988/ 5831:1984/ 3961(Part-I):1967/ 3975:1970/ 10810:1984 / 3975:1970 /8130:1984/ 3961:1967/ 10418:1982 / 10810:1984 as amended upto date, in respect of component materials and tests.Material Test certificate of all size of cable to be submitted to dpt. |
| 48 | 4 Core 240 Sq. mm [ (1 X 3 runs X100 Mtr) ] (Considering one connections for each source to be installed inside the Laundry shed from Sub station LT Panel) |
| 49 | 4 Core 120 Sq. mm |
| 50 | 4 Core 70 Sq. mm |
| 51 | 4 core 35 Sqmm |
| 52 | HT-Cable Jointing |
| 53 | Making heatshrinkable joints indoor type to the ends of the following XLPE HT cable at the transformer end as well as at the VCB ends supplying with necy. jointing kits (Raycham), sockets, sleeves, anti-corrossive paste, wires, solders, jointing compounds, rubber sheets etc. incl. supplying of necy. tools & tackeles for crimping the end sockets, soldering irons & making of glands at the both end of the cable as per directions of EIC |
| 54 | 3 Core x 300 Sq.mm |
| 55 | Laying of 1 No. 6.6KV (UE) Grade XLPE Aluminium conductor, PVC sheathed, armoured cable confirming to IS 7098, of earthed system of following size in the Masonary Open Duct as required. |
| 56 | 3 Core x 300 Sq.mm |
| 57 | Supply and delivery of Single core sheathed PVC Insulated, stranded Copper Cable for Voltage Grade Up To 1100 Volts for Changover to loopbox interconnection as below size.(Make: Gloster/ RR Kabel/Polycab/Havells) |
| 58 | 70 Sqmm |
| 59 | SITC of PVC loop Box having with 2mm thickness with front side opening door and locking arrangement. Junction box having suitable size power terminal bar for interconnection between different size cable like- 120 Sqmm cable to changeover with power terminal included.(Make: Syntex/ AKG/ Supreme) |
| 60 | LAYING OF CABLES |
| 61 | Laying of one cable 240 sqmm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand. |
| 62 | Laying of one cable upto 150 sqmm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand. |
| 63 | Laying of three cables 4 core x 240 sqmm in an underground trench in single tier formation (horizontal) the trench size : 915 mm x 760 mm average depth with brick protection on the top of each cable with 8 nos. bricks per Mtr. and 4 nos. bricks per mtr. as separator between every two cables including filling the space between the bricks and cables and also the trench with shifted soil, levelling up and restoring surface duly rammed . |
| 64 | Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed.. |
| 65 | Laying of cable on wall/surface with shaddles/clamps:- |
| 66 | Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting. |
| 67 | Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making. |
| 68 | Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting. |
| 69 | S& laying 150 mm (6\\") NB (ISI Heavy) HDPE pipe for Cable protection with necy. fittings & jointing materials as required. ( makelist attached) |
| 70 | S& laying 100 mm (4\\") NB (ISI Heavy) HDPE pipe for Cable protection with necy. fittings & jointing materials as required. ( makelist attached) |
| 71 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. 40mm |
| 72 | Cable Gland,socket |
| 73 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE armoured cables as below. |
| 74 | 4 Core 240 Sq. mm |
| 75 | 4 Core 120 Sq. mm |
| 76 | 4 Core 70 Sq. mm |
| 77 | 4 core 35 Sqmm |
| 78 | Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. |
| 79 | Single Core 70 Sq. mm |
| 80 | Finishing |
| 81 | Finishing the end of following XLPE armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. |
| 82 | 4 Core 240 Sq. mm |
| 83 | 4 Core 120 Sq. mm |
| 84 | 4 Core 70 Sq. mm |
| 85 | 4 core 35 Sqmm |
| 86 | S & drawing 1.1KV grade 7 core 2.5 sqmm. PVC/Ar. copper cable from transformer's WTI relay to VCB WT relay Relay for power & control supply. |
| 87 | S & F of termination and finishing end of the 7 core 2.5 sq.mm cooper cable as per direction of EIC. |
| 88 | S & F suitable angle/flat iron bracket for holding the HT/LT cables in proper place with all necy. materials as required and rigidly fixed as per direction of the EIC. |
| 89 | SUPPLY OF LIGHT FITTINGS |
| 90 | Supply & Delivery of 240V, 18/ 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 91 | Supply and Delivery of 4 feet Industrial box type double LED tube batten/ mounting rail (rust free) suitable for single TLED lamp. [Make- Philips/ Wipro/Lighting Technology/manufacturer with own NABL accredited lab with valid test certificate] |
| 92 | Supply and Delivery of 4 feet Industrial box type single LED tube batten/ mounting rail (rust free) suitable for single TLED lamp. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] |
| 93 | SUPPLY OF FAN FITTINGS |
| 94 | Supply & Delivery of 230V, 1-Ph, AC ceiling fan of follwing size incl. all accessories. (Make- Crompton / Usha / Orient) [BEE star rated]Sweep Size- 1200 mm (48\\"), Wattage ≤ 55 Watt, R.PM ≤ 380, Air Delivery ≥ 210 C.M.M |
| 95 | Supply & Delivery of following 230V, 1-Ph, Wall Mounting/ Pedestal Air Circulators with all accessories. (Make- Crompton / Usha / Orient/EPC) [BEE star rated]450 mm Sweep, 1-Ph, 3 Blade, RPM ≤ 1440 , Wattage ≤ 100 Watt, Air Displacement (In CMH) ≥ 5000 Wall Mounting |
| 96 | FIXING OF LIGHT FITTINGS |
| 97 | Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. |
| 98 | Extra for suspension exceeding 25 cm with S&F additional 2 no.20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. |
| 99 | FIXING OF FAN FITTINGS |
| 100 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush, etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire as per G.S. |
| 101 | Fixing only 18\\" (450 mm) dia air circulator fan on wall incl. S & F necy. MS fastner, nuts & bolts,wooden block etc. as reqd. |
| 102 | EXECUTION OF MISCLLENEOUS WORKS |
| 103 | Making masonary cable trench after cutting all sorts of soil. The inside mearsurment of trench 900 mm clear width x 900 mm clear depth by providing 250 mm thick brick work with 1st class brick cement mortorr (1:4) on both sides and bottom of the trench consisting with 100 mm thick cement concrete (1:3:6) with stone chips over a layer of jhama brick flat soling 15mm thick (1:4) cement plaster to inside wall & 3mm thick neat cement finish. |
| 104 | Cutting floor/ brick wall by suitable tools for passing electrical cables/ cable tray/ protection pipes/ earthing strip etc including mending the damages as per direction of the EIC. |
| 105 | Supply, fabrication and placing/fixing MS checkered plate made of 6mm thick incl 30mm x 30mm x 6mm MS angle iron structure welded by fixing for insert plates at 4 sides in cable trench top with 2 nos 3/8\\" TMT handle rod incl gas cutting, grinding & drilling with one coat of red laid primer and one coats of synthetic enamel paint as per direction of EIC. |
| 106 | S&F of MS Channel of following sizes with nut, bolt, washer etc to provide overhead supporting arrangement above different LT panels, cable support at HV side of transformer incl painting as to GS for following : |
| 107 | 150mmX 75mm X 10mm |
| 108 | 100mmX50mmX8mm |
| 109 | 75mmX40mmX6mm |
| 110 | Supply and grouting wire-mesh type heavy duty cable trays ( 300 MM CABLE TRAY) made of 8 SWG anodized steel wires both for cross-members and longitudinal members (4 nos.) to form a tray having 12” width for cradling portion 3” crowning at both end. |
| 111 | Horizontal run |
| 112 | ladder type for vertical run |
| 113 | Tightning, cleaning and painting of the existing (2x500 KVA) oil type/Dry type Sub-station incl. transformer & and Main Panel, DG Panel & 10 nos Sub Panel. Following works are included in this item:All this work must be done as per direction of EIC with prior approval of the requirments as per site conditions. |
| 114 | COMPOUND LIGHT |
| 115 | Supply & Delivery of 240V, 120W LED street lights with optic lens and polycarbonate diffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 116 | Supply & Delivery of 9 Mtr. HDG Octagonal Poles in 3mm shaft thickness in MS Condition before Galvanization with Top A/F 70 mm, Bottom A/F 155 mm, Base Plate 260x260x16 mm suitable for wind speed 180 Km/hr. as per IS:875 and 4 Nos. M24x750 “J” Type Foundation Bolts as per EN-8 (Min UTS-600) & Anti-theft locking door arrangement for safety with suitable MCBs, Terminal etc. Manufacturer with own house NABL accredited lab with valid test certificate as per IS & BIS. |
| 117 | S&F 50 mm. dia 1.5 mtr. long detachable type G.I. Single arm bracket, suitable for pole head. The arm bracket shall be properly welded with 15 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts, nuts and washer as per direction of EIC. |
| 118 | Fixing outdoor type LED light fitting on pole including S&F 40 mm dia x 1.68 mts. long GI Pipe (ISI-Medium) bracket with 40 mmx10 mm thick, MS clamp etc. and providing wiring with 2x1/1.40 PVC insulated & sheathed wire (single core) partly in GI conduit & partly through above bracket from OH line to the fitting, without control switch, incl. making connections and painting. |
| 119 | Fixing of the above LED light fitting on the arms of 9 m high HDG Octagonal poles/ wall with good fastening arrangement using sufficient nos. of nuts and bolts etc with one's own tools and tackles as required including scafolding arrangement as directed by EIC. |
| 120 | Erection of upto 9 Mtr octagonal GI (Hot Dip Galvanised in single dip) pole 1.6 Km from the store to work-site with foundation of M20 grade concrete for 9.0 Mtr GI Octagonal Pole with all the materials like sand, cement, stone chips, reinforcement steel, binding wire etc as relavent IS Code. soil bearing capacity at site as 10 T/sqmtr., by PCC Base foundation having (L-1000mm x W-1000mm x H-100mm) & RCC foundation having dimention (L- 500mm x W-500mm x H-1400mm) including neatly cemented finish (3mm thick) partly below and above ground level. There should be multiple alkathene pipes upto 1.2 mtrs of 50 mm dia of adequate length for distribution of incoming & outgoing cables for street light wiring as directed by EIC in the CC foundation of octagonal poles. |
| 121 | SITC of Junction Box having SS material with 2 mm thickness with front side opening door and locking arrangement, with SS clamp and canopy type. Junction box having 140x140x100mm dimension with canopy.Each have consist of the following materials i) EARTH Stud, ii) 32A, 2 WAY Stud Type Power Terminal , iii) 6A SPMCB - 1nos, iv) SS LOCK, v) 30x3 GASKET. The Junction Box is to be powder coated painted after required. surface treatment by 7 tank process / sand blushing with 2 coats of finish paint over dried or powder coating. |
| 122 | Distribution wiring in 1.1 KV, 2 x 2.5 sqmm + 1 x 1.5 sqmm ECC single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. |
| 123 | Supply of XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes 3core 10 sqmm |
| 124 | Laying of one No. cable 3 Core 10 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. |
| 125 | Laying of cable upto 3 core 25 sqmm on wall/surface incl. S&F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire making holes etc. as necy. Mending good damages and painting. |
| 126 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 40mm Dia. |
| 127 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables for 3 core 10 sqmm. |
| 128 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials for 3 core 10sqmm. |
| 129 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. As following sizes.A)2.5 Sqmm |
| 130 | S & F Timer Control Unit for Street Light time control assembled with following accessories: - i) 16-way SPNDB Box-1 no. ii) 25A DP MCB -1 no.iii)Digital 24 hour time switch -1no. iv)25A 2-pole contactor -1no. v)Melamine terminal block-2 nos. vi)LED indicating lamp -1 no. vii)2X4sq.mm+2.5sq.mm copper wire -2 mtr. viii)1.5sqmm copper wire-3 mtrs. ix) 3 way ON-OFF-ON toggle switch -- 1 no. x) cu socket of 4/2.5/1.5 sq mm -- L.S(Make-L & K/ABB/Legrand) with complete interconnection as required as per direction of EIC. |
| 131 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the groundlevel as: By TATA-Medium GI pipe |
| 132 | Excavation of soil for installation of Earth Electrode and filling & ramming for soft soil. |
| 133 | Lightning Conductor |
| 134 | S & F Lightning Conductor Air Terminal made of 20 mm dia 1000 mm long GI pipe (ISI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered/ welded with 7/16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapet etc. in CC mortar ( 4:2:1), including thimble joints of 7/16 SWG wire and (25 x 6) mm GI strip with SS nuts, bolts & washers. |
| 135 | Supply & fixing of 25 mm x 6 mm thick GI (Hot Dip) flat / strips for Horizontal & Vertical run on wall / floor with GI shaddles as required including drilling holes, bolts, nuts, washers, etc./ and mending good the damages to building works . |
| 136 | Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works:i) Length upto 0.5 Mtr |
| 137 | Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run. |
| 138 | Supply & Fixing of Testing Joints by 25 mm x 6 mm thick GI (Hot Dip) strip 125 mm long on wall after making suitable arrangement to establish a clearance of 50mm from wall for making junction connection with vertical conductor and conductor from earth electrode complete with S & F GI bolts, nuts, check-nuts, spring washers etc. as required. |
| 139 | Excavation of soil for installation of Earth Electrode and filling & ramming as to GS. (For morum soil) |
| 140 | Supply, Laying & Fixing of 50mm x 6mm galvanized (Hot Dip) steel strip in underground trench for interconnection between the Earth Points by joining (As per item no 11). |
| 141 | Jointing for Horijontal & vertical run of GI strip through welded joint of (25 x 6) mm or (50 x 6) mm GI Strip to Lap joints/ 'T' joints, etc. and painting the joints with 2 (two) coats of bituminous paint. |
| 142 | Glowsign Board |
| 143 | Supply and Fixing of sign board acrylic signages i) Supply and fixing of angle iron frame fabricated from 40 mm x 40 mm square four nos hollow bar with cross and radial support including one no 40x40 mm angle iron support in the middle for the Sign board of following size with suitable three nos. crosss angle support welded with 4 nos angle hook in equal space for fixing on the structure with all necessary welding and fabrication. The structure shall rest in both sides with proper welding as per instruction of EIC. ii) S&F LED Sign Board made 3 mm thick ACP Sheet (Alstrong/ Aludecor) finished with approved metallic colour as back ground (blue) after router cutting. The riser structure also shall be covered with ACP Sheet.& appx 6-7 inch depth (Both side ACP sheet) iii) S&F Special type of imported acrylic English letter appx 50 mm thickness flushed on the ACP board made on imported acrylic cast sheet. The mater appvd by EIC letter font shall be in horizontal line as mentioned. Matter taken from Authority 11/0.415 KV SUBSTATIONMECHANIZED LAUNDRYK.S. ROY T.B. HOSPITAL |
| 144 | iv) S&F SMD LED inside the board and to run for each letter including wiring , soldering etc and fixing the SMPS properly with the specification of the SMD 1.LED colour : White/ Red/ Blue (make-samsung) 2.Stright : 2 or 3 nos LED per module 3. Luminous Flux : 140 LUMEN 4. Life : 70000 burning hours 5. Visibility: 100 meter atleast normal eye 6. Power Supply: 1.2 watt to1.6 watt per module 7.Input : 230A.C , Output : 12V DC 8.Shape of LED : recrangle or square 9. Grade : IP - 65 |
| 145 | v) S & F LED Power supply 300/ 400W IP65 50/60Hz frequency, 108 to 305 VAC driver power supply other electrical accessories the panel prepared along with its necessary arrangement ( make Hisine/Migion/Cehosa/PWD appvd ) vi) Cost of painting of MS structure with 2 coats of RO primer and one coat of synthetic enamel paint after scrapping with emery paper properly make ICI/Asian paints vii) Cost of erection of scaffolding for fixing the Signage viii) Testing and commissioning of the LED board as per following nomenclature ix) Cost of carrying the LED sign board from work shop to site |
| 146 | Supply of XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes 3 core 6 sqmm (from PDB to Glowsign board loop box ) |
| 147 | Laying of cable upto 3 core 25 sqmm on wall/surface incl. S&F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire making holes etc. as necy. Mending good damages and painting. |
| 148 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : 3 core 6 sq mm |
| 149 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. 3 core 6sq mm |
| 150 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. Fittings as reruired. 2x36/0.3(2.5 sqmm) + 1x22/0.3(1.5 sqmm)ECC |
| 151 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint.(Make: Syntex) |
| 152 | Terms & Conditions |
| 153 | 1. The Agency must procure the materials from the manufacturer / OEM or from their authorized. sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.2. Documents that authenticates such procurement form the manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the manufacturer /OEM / authorized sales channel to the e-mail of Engineer-in-charge and hard copy of it to be submitted during execution of work/submission of bill.3. If any refurbished material is supplied and installed, penal action will be taken as per existing rules. |
| 154 | Defect Liability period 1 (One) Year |
| 155 | Rates are Inclusive GST @ 18% & LWC @ 1% Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail