| 1 | Supply, Installation, Testing & Commisioning of Microprocessor based Intelligent, soft addressable,(VDS/UL/FM/UL approved), ethernet ready fire alarm control panel, with each loop capable of taking minimum 120 devices. The panel shall be able to give pin point location of all fire/ fault conditions. The Panel should be able to store minimum 1000 log events in its Memory as per recommended standards. |
| 2 | The panel shall have in-built rectifier, Loop cards, interface card for connecting external serial printer, 4 line,40 charecter/line alphanumeric LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working or capable of operating the system for 2 hours during alarm condition, with integral battery charger complete as required. The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards. The FACP shall be capable of being networked with other similar FACP located at different part of the premises through ethernet (LAN). The panel should have necessary Ethernet card installed in it for bidirectional communication with 3rd party BMS/Scada and 3rd party public address system. All necessary memory map (incl. device address) should be provided. Minimum 4 potential free spare contacts should be provided with the panel. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer/Edward/ Bosch/Apollo/Morley / System Sensor/Johnson Controls/Securiton). |
| 3 | 2 Loops panel with one additional loop, expandable upto 4 Loops. |
| 4 | Supply, Installation, Testing & Commissioning of Analog Addressable Intelligent OPC complied multisensor detector (VDS/UL/FM/ULC approved) with inbuilt optical smoke sensors & heat detectors sensor with decentralize intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost). (Approved Make: Cerberus Pro/Secutron/ Edward/Bosch/ Apollo/Morley/System Sensor/Jahnson Controls/ Secunton/ Honey Well/ Notofire) OPC complied |
| 5 | Supplying, installation, testing and commissioning of soft Addressable Heat Detector (Fixed temperature cum rate of rise) with twist lockable removal base, built in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard [Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for each addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost]. (Approved Make: Cerberus Pro/Secutron/ Edward / Bosch / Apollo / Morley / System Sensor/Johnson Contros / Securiton/Honey Well/ Notofire) |
| 6 | Supplying, installation, testing and commissioning of LED typ Response Indicator (VDS/UL/FM/ULC approved) having red coloured LED lamps including connection etc(Approved Make: Cerberus Pro/Secutron/ Edward/Bosch/Apollo/ Morley/ System Sensor/Johnson Controls/Secunton/Honey Well/ Notofire).OPC complied |
| 7 | Supply, Installation, Testing & Commisioning of OPC complied Addressable Manual Call Point (VDS/UL/FM/ULC approved soft addressable type with in built fault isolator as par NFPA style 7 wiring complete as required. (Approved Make: Cerberus Pro/Secutron/ Edward/Bosch/Apollo/ Morley/ System Sensor/Johnson Controls/Secunton/Honey Well/ Notofire). |
| 8 | Supply, installation, Testing & Commissioning of Addressable Loop Powered Hooter (sound output of minimum 90 db) cum strobe (strength of light 10 cd) complete with inbuilt isolator & IP65 base and (VDS/UL/FM/ULC approved) (Approved Make: Cerberus Pro/Secutron/ Edward /Bosch/Apollo/Morley / System Sensor/Johnson Controls/ Secunton/Honey Well/ Notofire) OPC complied |
| 9 | Supply, Installation, Testing & Commissioning of OPC complied Addressable Relay Modules (VDS/UL & FM approved) for switching integration of Lift/AHU etc complete as required. (Approved Make: Cerberus Pro/Secutron/ Edward /Bosch/Apollo/Morley / System Sensor/Johnson Controls/ Secunton/Honey Well/ Notofire) |
| 10 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make Finolex/Polycab/RR Kable) with 20 mm NIB PVC rigid conduit pipe (Make-Precission Medium) on the surface of the wall. |
| 11 | Terms & Conditions |
| 12 | 1. The Agency must procure the materials from the manufacturer / OEM or from their authorized. sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.2. Documents that authenticates such procurement form the manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the manufacturer /OEM / authorized sales channel to the e-mail of Engineer-in-charge and hard copy of it to be submitted during execution of work/submission of bill.3. If any refurbished material is supplied and installed, penal action will be taken as per existing rules. |
| 13 | Rate is inclusive all taxes and cess |
| 14 | Defect Libility Period 1 year Please Enable Macros to View BoQ information |