Tender For Repair, Restoration, And Upgradation Of Fire Detection System At Central Combined Lab, Tangra, Kolkata - Due To Damage Of Loop Cable During Ongoing Construction Works., Kolkata-West Bengal
TDR : 54473349
Tender Notice
BOQ
6 Days Left
Kolkata
West Bengal
Tender For Repair, Restoration, And Upgradation Of Fire Detection System At Central Combined Lab, Tangra, Kolkata - Due To Damage Of Loop Cable During Ongoing Construction Works.
Name of Work:- Repair, Restoration, and Upgradation of Fire Detection System at Central Combined Lab, Tangra, Kolkata – due to damage of loop cable during ongoing construction works.
Sl. No.
Item Description
1
System Checking & InspectionComprehensive verification of the installed detection system. Includes functional testing of all devices, panels, and cabling to ensure proper operation.Identification of faults, irregularities, or performance issues for corrective action.(295 no Devices)
2
Erection & Refixing of Cable and DevicesProper erection and alignment of system cables and connected devices.Refixing of loose, faulty, or misaligned cables to restore system integrity.Ensuring compliance with safety standards and site requirements.Replacement and adjustment of devices where necessary to achieve optimal performance.(g+3 building)
3
Panel Reprogramming ChargesReprogramming of the control panel to integrate corrected devices and cabling.Updating system configuration to match site-specific requirements. Testing and validation of reprogrammed settings to confirm smooth operation.
4
Supply and laying of 2 core 1.5 sq. mm FRLS copper cable (for loop), approved make Finolex/KEI, with 20 mm NB medium-grade PVC rigid conduit pipe, approved make Precision, installed on the surface of the wall, including proper clamping, alignment, and fixing to ensure durability,safety, and neatness; complete with all labor, tools, and consumables required, executed in compliance with standard electrical practices
5
Supply, Installation, Testing, and Commissioning (SITC) of Addressable Multi-Criteria Detector, Make: Eaton (Cooper), odel: CAPT340, fully compatible with Eaton (Cooper) Fire Alarm Control Panel CF1200. (VDS/UL/FM/ULC approved with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost).
6
SITC of LED type Response Indicator having 2 Nos. red coloured LED lamps including connection set, etc. (Approved Make: Esser/ Cerberus Pro/Secutron/ Notifier/Edward/Bosch/Apollo/ Morley/ SystemSensor/ Johnson Controls/RAVEL)
7
Rate should be quoted incl. of all taxes and cess.
8
Defect Liability period : 1 year Please Enable Macros to View BoQ information