| 1 | Supply and fixing sheet moulding compound junction box shock and rust proof, termite resistant, tamper proof , front openable type for single phase, two wire rating of size 250x200x105mm complete with one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete. Make - Sintex or equivalent in Hensel/ABB / Power System & Controls. |
| 2 | Supply and fix single phase of 5KW of automatic street light switch using Infrared Sensor based NATURAL SWITCH for automatic switching of street lights. nature switch operation should be based on Natural Light Lux level, required illumiance level for switching ON is ≤ 30 Lux and for switching off ≥ 10 Lux. The sensor should have part night operation facility of min 4 hrs to max 12 hrs. The sensor along with suitable power contractor of 20 to 25 Amps current rating. incomming MCB and outgoing MCBs of 20-25 Amps and auto- manual (sensor By pass), size of circuit should be multistranded FRLS min size of 10 Sqmm, selection operation should be enclosed in a pole/wall mounted enclosure made of rust proof, electric shock proof termite proof and FR grade special mounting compound (Sintex made SMC junction box) conforming to IP 54. complete all as specified |
| 3 | Supply & fixing multifunctional digital timer switch with inbuilt function for switching on / off street lights according to the rising / setting of the sun with combination function according to astronomical time and / or fixed preset times complete with all connection to existing panel as per directed & complete testing . Make :- Legrand as per Cat Part No 4126 54 or equivalent L&T / C&S / Havells |
| 4 | Supply & fixing Automatic Security light control panel having sheet steel enclosure power coated CRCA sheet suitable for three phase,6 KW rating, outdoor installation,floor mounted, IP 54 protected including making all connections and grouted in PCC of type B-1 (1:2:4) with foundation should be 100mm above ground level complete with comprising of the following switch gears:-(i) MCB TPN 40Amp rating -01No (ii) Multifunctional Digital Timer Switch - 01 Nos(ii) Contactor with nominal current rating 32Amp TP (iii) Outgoing MCB SP with Suitable rating - 03 Nos (iv) Auto/manual switch(v) Incoming and outgoing terminal suitable for three phase supply. vi) Voltmeter , Ammeter and indicator lights |
| 5 | M&L for scraping, scretching, cleaning the old paint, preparation of the surface for repainting. Painting LT 9 Mtr long PCC pole in Black & White strip 30 Cm a part alternaterly up to 1.5Mtr height from ground level with synthetic enmel paint, writing pole Nos. & applying one coat of snowcem on PCC muff & remaining portion of the pole all as directed by Engr-In-Charge. |
| 6 | M&L for street light bracket made out of 40mm dia medium grade GI pipe of 1.2m length bent to required shape suitable for fixing street light / security light fitting on Steel tubular pole / RCC pole / including two Nos of clamps, nuts & bolts etc and two coats of aluminium paint over a coating of red oxide primer and Taking down of existing unserviceable rusted street light brackets with clamps, nuts and bolts etc, complete all as directed. |
| 7 | M&L for Building security light bracket made out of 32mm dia medium grade GI pipe of 45 cm length bent to required shape suitable for fixing building security light fitting on wall including two Nos of clamps, nuts & bolts etc and two coats of aluminium paint over a coating of red oxide primer and Taking down of existing unserviceable rusted brackets with clamps, nuts and bolts etc, complete all as directed. |
| 8 | Supply and fixing steel tubular swaged poles with cast iron base plate, finial taper plug, bolts, nuts & washers made out of mild steel tubing, type 410 SP -31 (9 Mtr long) including marking pole No on pole including painting of poles with one coat of red oxide primer and two coat of aluminum paint (one coat before fixing and one coat of aluminum paint after fixing) over exposed surface and two coats of bituminous paint over embedded portion & the portion above coping shall be painted in alternative bands of black and yellow colour starting with white colour (each band of 30cm wide) by two coats of super enameled paint upto 1.5m height complete all as specified and directed by Engr in Charge. Note : Earth work and PCC in foundation shall be measured separately. |
| 9 | M & L for plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundation of PCC poles/struts as specified including necessary form work. |
| 10 | M & L for plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundation of stay assembly etc including necessary form work , all as specified and directed. |
| 11 | M & L for plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate for copping around poles, including necessary form work finishing even and smooth without using extra cement, all as specified and directed. |
| 12 | Supplying, laying or fixing or passing through pipe, testing and commissioning XLPE insulated, steel tape / wire armoured heavy duty electric underground cable, 1100 volts grade with stranded aluminium conductor of following nominal cross sectional area :- |
| 13 | 10 sqmm 4 core. |
| 14 | 16 sqmm 4 core |
| 15 | 25 sqmm 4 core |
| 16 | 35 sqmm 3.5 core |
| 17 | 50 sqmm 3.5 core |
| 18 | 70 sqmm 3.5 core |
| 19 | Excavation in trenches for laying under ground cable, any type of soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep and getting out complete all as specified and directed by Engr–in–charge. |
| 20 | supply , spread river sand of approval in cable trenches providing for cable cushoning as directed , NOTE : punned thickness of sand only will be measured and paid |
| 21 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed by Engr in charge. |
| 22 | Removing surplus excavated material to a distance not exceeding 50meter above the starting point complete all as specified and directed by Engr in charge. |
| 23 | Supply & fixing Weather proof flat twin core copper conductor cable of size 1.5 Sqmm, 1100 volts grade including dismantling existing unserviceable cable any description and complete all as specified and directed. Make : Havells/Plaza/Finolex/Polycab |
| 24 | Supply and fixing LED Building security light fitting 60 watt 230v AC Outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP65/66 protection complete all as specified and directed. Make : Havells/ Syska/ PHILIPS/ Bajaj/ Crompton. |
| 25 | Supply and fixing LED street light fitting 70 watt 230v AC Outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP65/66 protection complete all as specified and directed. |
| 26 | Supply and fixing LED street light fitting 90 watt 230v AC Outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP65/66 protection complete all as specified and directed. |
| 27 | Supply and fixing LED street light fitting 120 watt 230v AC Outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP65/66 protection complete all as specified and directed. |
| 28 | Supply and fixing LED flood light 100 watt 230v AC Outdoor type with thermal management in multiple optics and equipped with IP-66 protection with impact and corrosion resistant complete with driver and lamp complete all as directed at site. |
| 29 | Supply and fixing LED flood light 200 watt 230v AC Outdoor type with thermal management in multiple optics and equipped with IP-66 protection with impact and corrosion resistant complete with driver and lamp complete all as directed at site. |
| 30 | Supply and fix electric water heater, storage type steel body with copper inner tank and heating element of 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc including grouting of studs in wall in cement mortar 1:3, clamps, nuts, bolts and 02 Nos flexible PVC connection pipe heavy duty 450mm long with brass nuts complete all as specified and directed. |
| 31 | S&F Ceiling Fan having sweep 1200 mm, 3-blades of aerodynamic ABS material (dust & mark resistant), energy-efficient BLDC motor single phase with inverter technology consuming not more than 28 W at rated speed of approx. 280 RPM and air delivery not less than 245 m³/min. The fan shall be supplied without LED under light and in Pearl White colour finish only. The fan shall include RF remote control with timer (up to 8 hours), sleep/breeze modes, and memory function. Noise level shall be whisper-quiet. The fan shall have 5-Star energy rating,Service value not less than 7.40, 2 years manufacturer’s warranty, and be BIS/ISI marked wherever applicable. Installation shall be carried out by authorized service personnel with all accessories complete as per manufacturer’s standard. |
| 32 | S&F Ceiling Fan having sweep 1400 mm, 3-blades of aerodynamic ABS material (dust & mark resistant), energy-efficient BLDC motor single phase with inverter technology consuming not more than 28 W at rated speed of approx. 280 RPM and air delivery not less than 245 m³/min. The fan shall be supplied without LED under light and in Pearl White colour finish only. The fan shall include RF remote control with timer (up to 8 hours), sleep/breeze modes, and memory function. Noise level shall be whisper-quiet. The fan shall have 5-Star energy rating,Service value not less than 7.40, 2 years manufacturer’s warranty, and be BIS/ISI marked wherever applicable. Installation shall be carried out by authorized service personnel with all accessories complete as per manufacturer’s standard. |
| 33 | Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250 mm Note: Old fan should be deposited in MES store. |
| 34 | Supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet outer body and 2mm thick CRCA MS sheet inner body duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6MM duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication.The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right. The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- INCOMING - MCCB 400 Amps, 415 volts, 4 Pole, 36KA, 50 Hz, (Incoming) with Ics=100% Icu and microprocessor release type all as per L&T Make, Cat No. CM921510000x1 - 01 No. and including spreader terminals - set of 08, direct rotary handle - 01 No. or equivalent in Legrand/Schenider/ABB/Seimens OUTGOING - MCCB 200 Amps, 415 volts, 4 Pole,35 KA, 50 Hz, (Incoming) with Ics=100% Icu and microprocessor release type all as per L&T Make,Cat No CM21520000x1 - 01 Nos. and including spreader terminals - set of 06, direct rotary handle - 01 No. or equivalent in Legrand/Schenider/ABB/Seimens MCCB 100 Amps, 415 volts, 4 Pole,35 KA, 50 Hz, (Incoming) with Ics=100% Icu and microprocessor release type all as per L&T Make,Cat No CM21520000x1 - 02 Nos. and including spreader terminals - set of 06, direct rotary handle - 02 No. or equivalent in Legrand/Schenider/ABB/Seimens MCCB 63 Amps, 415 volts, 4 Pole,35 KA, 50 Hz, (Incoming) with Ics=100% Icu and microprocessor release type all as per L&T Make,Cat No CM21520000x1 - 02 Nos. and including spreader terminals - set of 06, direct rotary handle - 02 No. or equivalent in Legrand/Schenider/ABB/Seimens 3 phase Digital Type Ammeter with Inbuilt Selector - 04 Nos. 3 phase Digital Type Voltmeter with Inbuilt Selector - 04 No. LED Type Indicating Lamps R,Y,B - 12 Nos.6 Amps MCB SP, 10 kA, C curve type for back supply for measuring meters and LED indicator lamps - 06 Nos. Ring Type CT 2500/5/1A, 10 VA, CL1 Tape Wounded - 03 Nos. Aluminium Main bus bar of size 100x10MM for R-Y-B phases and 25x12MM |
| 35 | Material & labour for earthing with Copper plate electrode 60cm x 60cm x 3.15 mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Copper strip of Size 20 X 3 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 5 of SSR 1991(Part-I) complete all as directed. |
| 36 | Point wiring complete with 1.5 sqmm single core PVC insulted FRLS cable 1100 volts grade with multistranded copper conductor drawn through and including 20mm dia PVC rigid non metallic PVC conduit with all accessories such as internal bend end caps etc complete fixed on walls/ceiling/roof/etc by means of suitable GI saddles/Spacers and including provision of 1.5 Sqmm single core PVC insulated FRLS cable 1100 volts grade with multistranded copper conductor cable as earth continuity conductor, fabricated steel terminal box made out of 1.60mm thick MS sheet concealed in walls with 3mm thick bakelite top cover sheet, ISI maked with chrominium plated screws and cup washers for housing the switches , socket outlets, fan regulators etc, all as specified and as directed for the following :- |
| 37 | a) One light/ fan/ exhaust fan point controlled by one way switch 5 amp complete. |
| 38 | b) One 3 pin 5 Amps socket point controlled by one way switch on same board. |
| 39 | c) One 3 pin 5 Amps socket point controlled by one way switch on independent board. |
| 40 | M & L for Point wiring with 4 Sqmm (nominal area) single core PVC insulated unsheathed FRLS cable, multi-stranded, copper conductor, in universal colour code with & including suitable size of rigid non-metallic PVC conduit (not less then 20mm dia med grade) and its all accessories complete concealed in wall / roof incl cutting & chases( making good all to the disturbed surfaces as per existing) and including with modular flush metal boxes with modular cover plates & frame for mounting modular switches, sockets, regulators etc and including earth wire of PVC insulated FRLS copper conductor multistranded of 4 Sqmm size in green colour complete all as specified in current SSR Part-I & II & directed by the Engineer-in-Charge, as described below:- |
| 41 | Supply and Fixing Modular switch 6 Amps single pole one-way, 1 Module complete all as specified. |
| 42 | Supply and Fixing Modular switch 16 Amp single pole one way,1 Module all as specified. |
| 43 | Supply & Fixing Modular fan Regulator electronic step type 2M complete all as specified. |
| 44 | Supply and Fixing Modular socket 2-in-1, 5 pins 6 Amps , combined 2 Module complete all as specified. |
| 45 | Supply and Fixing Modular socket 2-in-1,3 and 5 pins 6 /16 Amps, combined 2 Module complete all as specified. |
| 46 | Supply and Fixing ceiling rose surface bakelite 65mm x 50mm three terminals complete all as specified. |
| 47 | Supply and fixing lamp holder (Angle), PVC / polycarbonate type with back plate suitable for batten fittings complete all as specified. |
| 48 | S/F Modular White cover plate with frame,1 module |
| 49 | S/F Modular White cover plate with frame,2 module |
| 50 | S/F Modular White cover plate with frame,3 module |
| 51 | S/F Modular White cover plate with frame,6 module |
| 52 | S/F Modular Metal flush box 1/2 module |
| 53 | S/F Modular Metal flush box 3 module |
| 54 | S/F Modular Metal flush box 6 module |
| 55 | Supply & fixing indoor decorative ultra slim surface /Wall mounted LED batten tube light complete fitting 1x 20 watt LED Tube fitting with polycarbonate channel housing & integrated electronic driver,energy efficient, 140V-270 volts,co- related colour temperature (CCT) of 6500K, >100 Lm/Watt complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed by Enginee-in-Charge. |
| 56 | Supply and fix LED T-5 Intergrated Batten PC housing extruded 2' light fittings 9W complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed by Enginee-in-Charge. |
| 57 | S&F Recess mounting LED light fitting 2X2, Square shape 24W, 230V, complete with all accessories internally prewired and including connected up with twin core twisted flexible copper conductor cable with suitable sizes all as specified and directed. Make Surya /cromptom/bajaj |
| 58 | Supply and fix LED retrofit lamp 9 Watt. |
| 59 | Supply & fix of MCB DP 40 -63 Amps,' C' series , bracking cap 10KA, 240V complete all as specified and directed. |
| 60 | Supply & fixing in replacement of MCB SP 6 - 32 Amps, ' B' series ,bracking cap 10KA, 240V complete all as specified and directed. |
| 61 | Supply and fix SP enclosure modular type, with a two pin and earth plug and socket complete with Single Pole MCB of rating 20-32 Amps, 240 Volts complete with all conction as directed. |
| 62 | S&F steel tubes light grade galvanised with all fittings such as clamps, nuts and bolts, washers etc fixed to walls/ floors/ poles/ road crossing etc of following sizes 40mm dia bore complete all as directed:- |
| 63 | Earthing complete all shown as electrical plate No -03 of MES Sch part -I as specified and as directed including the following:- (i) GI earth plate of size 60x 60cm x6.0mm thick burried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.50 metres below ground level. (ii) Earth plate surrounded by and packed with charcoal and common salt in alternative layers. ( n.exc 15 cms each layer) (iii) 4 mm GI wire from earth plate to MCB DB/machinery incl necessary GI bolts, nuts check , washers, thimbles etc. (iv) 20 mm bore, light grade, Gi pipe for watering including GI funnel and wire mesh. Pipe shall be provided vertically upto top level of earth pit and then taken horizontaly to the earth pit. (v) 15 mm dia bore G. I. medium grade pipe for protection of earth wire.(vi) Cement concrete chamber of PCC (1:3:6) type C-2 using 40mm graded stone aggregate. The chamber shall be constructed one metre away from edge of earth pit. (vii) 50 mm thick precast cover of reinforced cement concrete(1:2:4) type B-1 using 20mm graded stone aggregate with steel rainforcement 8 mm dia mild steel TMT bar @ 10 Cm c/c both ways and MS angle iron 50x50x6mm frame including two coats of painting over a coat of red oxide to exposed steel surfaces with suitable handle to lift the cover.(viii) Excavation in soft/loose soil, returning filling & removal of surplus soil to a distance of 50 m as directed. |
| 64 | Supply and fix sheet metal enclosure with distrubution board 08 way TPN double door type with 200 Amps rated bus bar |
| 65 | Supply and fix sheet metal enclosure with distrubution board 04 way TPN double door type with 200 Amps rated bus bar |
| 66 | S&F MCB distribution board, SPN 8 way, double door, sheet steel, phosphatised, powder painted with bus-bar 200Amp, neutral link, earth bar and din rail, cable ties for cable management, 240 V, complete all as specified. |
| 67 | S&F MCB distribution board, SPN 4 way, double door, sheet steel, phosphatised, powder painted with bus-bar 200Amp, neutral link, earth bar and din rail, cable ties for cable management, 240 V, complete all as specified. |
| 68 | S&F MCB distribution board, SPN 12 way, double door, sheet steel, phosphatised, powder painted with bus-bar 200Amp, neutral link, earth bar and din rail, cable ties for cable management, 240 V, complete all as specified. |
| 69 | S&F TP&N Vertical Loadline distribution board, 4 Way, Double door, sheet steel, phosphatised, powder painted with bus-bar 200Amp, neutral link, earth bar and din rail ,blanking Plates, cable ties for cable management, 440 V, 4 way complete all as specified including fitting suitable for MCBs with connections complete all as specified and directed.Note : -MCB & MCB /MCCB DBs shall be of same make and measured and paid seperately under respective items of Sch A. DB shall be fixed in flush pattern by cutting the wall and making good disturbed surface as pe directed & rate shall be included in the items. Please Enable Macros to View BoQ information |