| 1 | Lumpsum price worked out by the contractor for “BUILDINGS AND STRUCTURES” as listed in Sch 'A' part I above/below the lumpsum price of Rs.7,10,45,000.00 as inserted by MES for Sch ‘A’ part I on srl page No. 31(R) |
| 2 | Lumpsum price worked out by the contractor for “SITE CLEARANCE/ EARTHWORK” as listed in Sch '‘A” part II above/below the lumpsum price of Rs.9,34,685.88 as inserted by MES for Sch ‘A’ part II on srl page No.32(R) |
| 3 | Lumpsum price worked out by the contractor for “DEMOLITION OF B/R PORTION” as listed in Sch '‘A” part IIIA above/below the lumpsum price of Rs. 17,85,268.79 as inserted by MES for Sch ‘A’ part IIIA on srl page No.34 |
| 4 | Lumpsum price worked out by the contractor for “DEMOLITION OF E/M PORTION” as listed in Sch '‘A” part-IIIB above/below the lumpsum price of Rs. 97,855.60 as inserted by MES for Sch ‘A’ part IIIB on srl page No.35 |
| 5 | Lumpsum price worked out by the contractor for “INTERNAL WATER SUPPLY\\" as listed in Sch ‘A” part IV representing above/below the lumpsum price of Rs. 5,09,602.80 inserted by MES for Sch ‘A’ Part IV on srl page No.36(R) |
| 6 | Lumpsum price worked out by the contractor for “INTERNAL ELECTRIFICATION\\" as listed in Sch ‘A” part V representing above/below the lumpsum price of Rs. 16,66,153.15 inserted by MES for Sch ‘A’ Part V on srl page No.38 |
| 7 | Lumpsum price worked out by the contractor for “ROAD/ PATH/ CULVERT/ HARDSTANDING” as listed in Sch ‘A” part VI representing above / below the lumpsum price of Rs. 26,34,985.34 as inserted by MES for Sch ‘A’ Part VI on srl page No.40(R) |
| 8 | Lumpsum price worked out by the contractor for “SEWAGE DISPOSAL” as listed in Sch ‘A” part VII representing above / below the lumpsum price of Rs. 3,57,700.96 as inserted by MES for Sch ‘A’ Part VII on srl page No.42 |
| 9 | Lumpsum price worked out by the contractor for “AREA DRAINAGE” as listed in Sch ‘A” part VIII representing above / below the lumpsum price of Rs.6,40,489.18 as inserted by MES for Sch ‘A’ Part VIII on srl page No.43 |
| 10 | Lumpsum price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Sch ‘A” part IX representing above / below the lumpsum price of Rs.3,19,716.82 as inserted by MES for Sch ‘A’ Part VIII on srl page No.44 |
| 11 | Lumpsum price worked out by the contractor for “EXTERNAL ELECTRIFICATION” as listed in Sch ‘A” part X representing above / below the lumpsum price of Rs.3,77,657.00 as inserted by MES for Sch ‘A’ Part X on srl page No.45 |
| 12 | Lumpsum price worked out by the contractor for “FIRE FIGHTING” as listed in Sch ‘A” part XI representing above / below the lumpsum price of Rs.66,059.00 as inserted by MES for Sch ‘A’ Part XI on srl page No.47(R) |
| 13 | Lumpsum price worked out by the contractor for “LIGHTENING PROTECTION” as listed in Sch ‘A” part XII representing above / below the lumpsum price of Rs.1,09,034.10 as inserted by MES for Sch ‘A’ Part XII on srl page No.48(R) |
| 14 | SCH 'A' PART XIII (MISC B/R & E/M ITEMS) Note:- Excavation and earthwork to the extent required for execution of relevant item under this schedule unless otherwise specified shall be measured and paid under relevant items of Sch 'A' Part-II. |
| 15 | (A) DEMOLITION (E/M) |
| 16 | Taking down DB/main switch of any size and making good disturbed surface of wall floor complete all as specified and directed. |
| 17 | Taking down carefully sub-main wiring of any description and making good to their disturbed surfaces to match the existing all as specified and as directed |
| 18 | Taking down Geyser of any size, capacity and any make, including hot and cold flexi pipe from the GI pipe at dismantling and removing the same and deposit to store all as specified and as directed. |
| 19 | Taking down MCCB/MCB of any type any capacity and any make from DB complete all as specified and directed. |
| 20 | Taking down energy meter single phase from blogs of any type and any make and deposit the same at MES store for reuse complete all as specified and directed. |
| 21 | Taking down old unsw GI wire earthing from the blogs complete all as specified and directed. |
| 22 | Taking down old unsw GI tubing 50mm bore from blogs including earth work complete all as specified and directed. |
| 23 | Taking down old unsw GI tubing 25mm bore from blogs including earth work complete all as specified and directed. |
| 24 | Taking down old unsw GI tubing 20mm bore from blogs including earth work complete all as specified and directed. |
| 25 | Taking down old unsw GI tubing 15mm bore from blogs including earth work complete all as specified and directed. |
| 26 | Taking down old unsw LT XLPE cable 35 sqmm 3.5 core from the trench and remove the both ends from the panel and TPN DB of bldgs including earth work complete all as specified and directed |
| 27 | (B) INTERNAL WATER SUPPLY |
| 28 | Supply & Fix 15 mm bore (concealed) angle valve of cast copper alloy chromium plated fancy type screwed down high pressure with crutch or butterfly handle screwed both ends for CPVC pipe or for unions and fixed complete all as specified & directed. |
| 29 | Supply & Fix two way bib taps, 15 mm size fancy type cast copper alloy chromium plated with crutch or butterfly handle, screwed down, for CPVC pipe or for brass ferrule and fixed complete all as specified & directed. |
| 30 | Supply and fix stop/ angle valve 15mm bore cast copper alloy, chromium plated, screwed down, high pressure with crutch or butterfly handle, screwed both ends for CPVC pipes or for unions & fixed complete all as specified and directed. |
| 31 | (C) INTERNAL ELECTRIFICATION |
| 32 | Materials & Labour for point wiring complete with two runs of 1.5 sqmm PVC insulated Point underlined multistranded copper conductor FRLSH cable 1100 volts grade, single core, drawn through and including concealed PVC conduit (medium Grade) of adequate size (not less than 20mm dia) with all fittings and accessories. Including one run of 1.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH Cable (green colour), single core as earth continuity conductor connected to common earth dolly for light.fan and call bell point controlled by one switch and Cutting chases for conduits and sinkings for boxes and making good to walls, floors etc.making good disturbed surfaces complete all as specified and as directed. |
| 33 | Materials & Labour for point wiring complete with two runs of 1.5 sqmm PVC insulated Point underlined multistranded copper conductor FRLSH cable 1100 volts grade, single core, drawn through and including concealed PVC conduit (medium Grade) of adequate size (not less than 20mm dia) with all fittings and accessories. Including one run of 1.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH Cable (green colour), single core as earth continuity conductor connected to common earth dolly for one light point controlled by Two way switch and Cutting chases for conduits and sinkings for boxes and making good to walls, floors etc.making good disturbed surfaces complete all as specified and as directed. |
| 34 | Materials & Labour for point wiring complete with two runs of 1.5 sqmm PVC insulated Point underlined multistranded copper conductor FRLSH cable 1100 volts grade, single core, drawn through and including concealed PVC conduit (medium Grade) of adequate size (not less than 20mm dia) with all fittings and accessories. Including one run of 1.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH Cable (green colour), single core as earth continuity conductor connected to common earth dolly for one 5Amp Switch Socket Combination on Independent board and Cutting chases for conduits and sinking's for boxes and making good to walls, floors etc.making good disturbed surfaces complete all as specified and as directed. |
| 35 | Materials & Labour for point wiring complete with two runs of 2.5 sqmm PVC insulated Point unsheathed multistranded copper conductor FRLSH cable 1100 volts grade, single core, drawn through and including concealed PVC conduit (medium Grade) of adequate size (not less than 20mm dia) with all fittings and accessories. Including one run of 2.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH Cable (green colour), single core as earth continuity conductor connected to common earth dolly for one Power point (15 Amps Switch socket Combination) on independent board, and Cutting chases for conduits and sinking’s for boxes and making good to walls, floors etc.making good disturbed surfaces complete all as specified and as directed. |
| 36 | Materials & Labour for point wiring complete with two runs of 2.5 sqmm PVC insulated Point unsheathed multistranded copper conductor FRLSH cable 1100 volts grade, single core, drawn through and including concealed PVC conduit (medium Grade) of adequate size (not less than 20mm dia) with all fittings and accessories. Including one run of 2.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH Cable (green colour), single core as earth continuity conductor connected to common earth dolly for Geyser Point and Cutting chases for conduits and sinking’s for boxes and making good to walls, floors etc.making good disturbed surfaces complete all as specified and as directed. |
| 37 | Materials & Labour for point wiring complete with two runs of 4.0 sqmm PVC insulated Point unsheathed multistranded copper conductor FRLSH cable 1100 volts grade, single core, drawn through and including concealed PVC conduit (medium Grade) of adequate size (not less than 20mm dia) with all fittings and accessories. Including one run of 4.0 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH Cable (green colour), single core as earth continuity conductor connected to common earth dolly for AC point Cutting chases for conduits and sinking’s for boxes and making good to walls, floors etc.making good disturbed surfaces complete all as specified and as directed. |
| 38 | Supply and fixing LED Lamp 9 watt 220 volts AC of suitable size complete all as specified and as directed. |
| 39 | Supply & Fix in repair LED building security light fitting 25 watt complete all as specified and directed. |
| 40 | Supply & Fix GI light grade pipe 1.5 m long bend to 45 degree and of diameter 25 mm suitable to building security light power cord pipe diameter with necessary clamps for fixing building security light all as specified and directed including making hole to wall if necessary (For Bldg Security Light) complete all as specified and directed. |
| 41 | Material and labour for sub main wiring with two single core PVC insulated unsheathed cable 6.00 Sqmm (Nominal area) with multistranded FRLSH copper conductor cable, 1100 volts grade drawn through concealed PVC Conduit with all fittings and accessories and earth continuity conductor of single core PVC insulated, unsheathed cable 6.00 Sqmm (Nominal area) with multistranded FRLSH copper conductor, 1100 volts grade and making good disturbed surfaces complete all as specified and as directed. (From 4 way TPN DB to 12 Way SPN DB) Note: (i) Two run of wiring cable, one run of earth wire and one run of PVC Conduit shall be measured as one unit. |
| 42 | Supply and fixing MCCB 63 Amps 4P 25 KA 415 Volt Make Indoasian Car No 830020 including MCCB Enclosure for 63 Amp MCCB Make Indoasian Car No 811985 fixed on wooden board of appropriate size for mounting of enclosure complete all as specified and as directed. Rate inclusive of Fixing of cable including lugging complete all as specified and as directed. |
| 43 | Suppl and fix Smart RF/Cellular Single Phase AC Meter Tamper Proof, Static Meter of Class 1.0, 315 V, 50 Hz, 10 A-60 A conforming to IS-1644-and relevant IEC standards with intuiti Radio Frequency communication facility with self healing mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuit including Polycarbonate Meter Box of minimum suitable size for 1 Phase meter with viewing glass, concealed hinge and earth bolt plugged complete all as specified and directed. Meter Should support sending the following data : 15/30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, monthly billing survey for Cumulative Energy and Max Demand to software. Meter should have connect / disconnect functionality operable from main/billing software and prepaid features would be MDM / Billing end as per prevalent IS including taking down of existing meter and deposit to MES store yard for safe custody all as specified and as directed. Note:- Contractor has to ensure integration and maintainance of the above 06 nos of meters with the existing Advance Metering Infrastructure (AMI) of smart meters |
| 44 | Material and labour for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion complete all as specified and directed. |
| 45 | (D) EXTERNAL WATER SUPPLY |
| 46 | Supply and lay 100 mm dia ductile Iron pipe, S/S including specials, Class “K-7” complete all as specified and directed. |
| 47 | Supply and fix 80mm dia Strainer Y type conforming to IS, complete all as specified and directed. |
| 48 | Supply and fix 80mm dia Foot Valve conforming to IS 4038, complete all as specified and directed. |
| 49 | Material & Labour for cutting existing 150 mm steel tubing for alterations or additions necessarily done in position without taking down and inserting Tee of 150 x 150 x 100 mm for tapping all as specified and directed.(Tapping point shown and as directed) |
| 50 | Supply, install, connecting, testing and commissioning centrifugal monobloc pump set, with suitable suction / delivery head of head 36 mtr and discharge 417 LPM, CI impeller coupled with three phase induction motor 415 Volt, 2800 RPM with capacity 3.5 HP, including base frame for pump with foundation and connected with inlet as well as delivery pipe with standard arrangement as per manufacturer specification motor, pump, base complete including including accessories complete all as specified and directed. |
| 51 | Material & Labour for valve chamber of internal size 750x750x750mm comprising of 50mm thick PCC 1:5:10 type E2 foundation, 200mm thick brick wall in CM 1:6, 15mm thick plastering in CM 1:4 internally and externally up to 50mm be;ow GL,100mm thick PCC 1:3:6 type B1 as in copings,3mm thick MS sheet cover with suitable hinges and locking arrangement, painting steel surfaces with two coats of synthetic enamel paint over a coat of primer including necessary earth work and excavation in any type of soil complete all as specified and as directed. |
| 52 | Material & Labour for earthing complete with galvanized earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized iron strip of 32x 6 mm (up to 7.5m in length from earth plate) by means of brass bolts and nuts checknuts and washers of brass all as specified and shown in electrical plate no 3 of SSR part 1 including Charcoal and rock salt with necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with CI Cover 10mm thick Hinged to CI frame with MS bar 6mm dia 150mm c/c reinforcement, watering funnel, 40 mm dia light grade pipe for protection of earth electrode and 20mm dia pipe medium grade for watering all as specified and directed and tested on completion complete all as specified and as directed. |
| 53 | (E) EXTERNAL ELECTRIFICATION |
| 54 | Material & Labour for cement concrete in foundation, filling and mass concrete type B2 1:2:4 (40mm graded aggregate), not exceeding 15 CM in depth for plinth protection for path including dismantling of old surface complete all as specified and directed. |
| 55 | Material & Labour for DWC pipe of 63 mm dia for cable protection complete all as specified and as directed |
| 56 | Supply and fixing LT Panel made out of CRCA sheet 3.15mm thick outdoor Pedestal type CPRI approved, totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switch gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material including as per IS-8623 tinned aluminum bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 250 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following: (Main Panel) |
| 57 | Incoming:(a) MCCB 4 Pole, 415 V,36 KA (ICS=ICU=ICW for 1 Sec), with magnetic release of capacity 160 Amps, with adjustable type overload protection, short circuit protection - 01 NoOutgoing:(b) MCCB 4 Pole, 415 V,16 KA (ICS=ICU=ICW for 1 Sec), with thermal release of capacity 63 Amps, with fixed type overload protection, short circuit protection - 01 No for DG Panel(c) MCCB 4 Pole, 415 V,16 KA (ICS=ICU=ICW for 1 Sec), with thermal release of capacity 100 Amps, with fixed type overload protection, short circuit protection - 02 No for Building(d) Intelligent Panel meter to measure voltage, current, frequency, power factor etc with all connected CTs of each breakers(e) LED indicating Lamps for each phase with colour code Red Yellow Blue for R, Y and B Phases for each breakers |
| 58 | Supply and fixing LT Panel made out of CRCA sheet 3.15mm thick outdoor Pedestal type CPRI approved, totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size, weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switch gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material including as per IS-8623 tinned aluminum bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 150 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following: (DG Panel) |
| 59 | Incoming:a) MCCB 4 Pole, 415 V, 25KA (ICS=ICU=ICW for 1 Sec), with thermal release of capacity 63 Amps, with adjustable type overload protection, short circuit protection - 01 No for DG PanelOutgoing:b) MCCB 3 Pole, 415 V, 25 KA (ICS=ICU=ICW for 1 Sec), with thermal release of capacity 32 Amps, with fixed type overload protection, short circuit protection - 02 No for Lift panelc) MCB 3 Pole, TP, 415 V,16 KA C curve, 32Amps - 01 No for Fire pumpd) MCB SP, 230 V,10 KA C curve, 10Amps - 01 No for street lighte) Astro Timer switch -01 no for Street lights(f) Intelligent Panel meter to measure voltage, current, frequency, power factor, etc with all connected CTs of each breakers(g) LED Indicating Lamps for each phase with colour code Red Yellow Blue for R, Y and B Phases for each breakers. |
| 60 | Supply and installation LT Electric control Panel cubical type for out door use floor mounted made out of CRCA outer sheet 3 mm thick and inner sheet of 2mm thick and angle iron legs of size 50 mm x 50 mm x 5mm having front and rear open hinged doors with front openable shutters for each MCCB with spreader with fully enclosed bus bar chamber having insulated bus bar made out of aluminium strips of rating 400 amps for 3 phase/415 volts. 50 C/S 4 wire system with cable entry provision with suitable lugs gland voltmeter, ammeter, CTs and phase indicator complete duly painted with projected an raised platform of suitable size weather and waterproof with necessary locwo costs of stove enameled powder coated paint over a coat of red oxide primer complete and nuts bolt washers for connection of cable, including necessary PCC work of height 45 cm from ground level and white washing to the platform all as specified and equipped with the following items: (LT Panel at Pump House of Airmen area) |
| 61 | Incoming:i) MCCB 4 Pole, 415 V, 25kA, with thermal release of capacity 125 Amps-01 Nos ii) Digital Ammeter 0-300 Amps CT Operated with selector switch-01 No (L&T) iii) Digital Voltmeter 0-500 Volts with selector switch-01 No (L&T) iv) LED Indicator lamp in three colour RYB - 03 Nos(L&T) v) LED Index Outgoing:(i). MCB 32 Amp TP, 415 Volts - 01 Nos(ii) MCB 25 Amps TP, 415 Volts-01 Nos (iii) MCB 32 Amps TP-415 Volts (Spare) - 01 Nos II Supply and fix DOL starter for 7.5 HP - 02 Nos |
| 62 | Supply and fix Loop in loop out box (minimum size - 210mm x 155 mm x 92 mm) of FRP made with IP 65 protection of thermoplastic circuit breaker boxes with metric knockouts for cable entry and exit, Combi climate Cable Glands of IP 66/ IP 67 for cable entry with MCB 1 Amps, 10 kA, C Curve terminals as bus terminals for cable with necessary fixing arrangements and with cable glands, complete all as specified and directed. |
| 63 | Material & Labour for PVC insulated copper conductor of size 1.5 sqmm 3 core for each steel light complete all as specified and directed. Please Enable Macros to View BoQ information |
| 64 | Material & Labour for PVC insulated copper conductor of size 1.5 sqmm 3 core for each steel light complete all as specified and directed. Please Enable Macros to View BoQ information |