| 1 | Day to day preventive & corrective maintenance of the entire Fire Detection and Alarm system installed at the Vidyasagar S.G. Hospital by engaging 1 no. skilled person in each shift as given in Annexure-I having adequate knowledge in fire detection system as per terms & condition. |
| 2 | Skilled Labour - Total 03 Shifts Per Day (01 No Per Shift) |
| 3 | Replacement cost for following supply & installation of spare parts (Consumable spares & Emergency spares) as and when required for annual preventive and corrective maintenance of Fire Detection System. (As per attached Annexure II) |
| 4 | Supply, Installation, Testing & Commissioning analog Addressable Intelligent multi sensor detector (VDS/UL/FM/ULC aproved) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable photo thermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard (Make: Siemens/Edwards) |
| 5 | Supply, Installation, Testing & Commissioning Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Make: Siemens/Edwards) |
| 6 | Supply, Installation, Testing & Commissioning Addressable Loop Powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Make: Siemens/Edwards) |
| 7 | Supply, Installation, Testing & CommissioningAddressable Manual Call Point (VDS / UL / FM / ULC approved) soft addressable type within built fault isolator as per NFPA style 7 wiring complete as required. (Make: Siemens/Edwards) |
| 8 | Supplying, installation, testing and commissioning of LED type Response Indicator (VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Make: Siemens) |
| 9 | S&F of MCP Glass in place of damaged one |
| 10 | S&F of 12 Volt, 12 AH SMF UPS Battery (FR Type) (Make: Exide/Amara Raja) |
| 11 | The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. |
| 12 | Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. |
| 13 | Rate Should be quoted inclusive of LWC and all other related taxes & duties. |
| 14 | Agency must visit the site for gathering information about the nature of work. |
| 15 | Defect Liabibility Period 1 (One) year |
| 16 | Make & model of each and every material to be approved by EIC Please Enable Macros to View BoQ information |