| 1 | electrical |
| 2 | 1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm |
| 3 | 90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 4 | 90.12.7.12:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 4 sq mm with factory made clamp |
| 5 | 90.6.4.54:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 4 Run |
| 6 | 90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size |
| 7 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 8 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 9 | 1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 10 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 11 | 90.6.10.1:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm |
| 12 | 90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm |
| 13 | OD386891/2025-2026:Supply and providing 230V, 40 W, integrated, energy saving, long life, corrosion resistant, die-cast, LED well glass Luminaire fitting, aesthetically designed with symmetrical light distribution, fixing / hanging from ceiling / stress work with fixing bracket and nut bolt, giving connections etc as required. (Luker Faro LW040 / Havels / Crompton or equivalent make) |
| 14 | 90.10.1.8:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )10 module moulded plastic box on surface |
| 15 | 1.28.6:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.12 Module |
| 16 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 17 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 18 | 1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 19 | 90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm |
| 20 | OD386894/2025-2026:Supply and providing 25 mm Corrugated PVC flexible conduit as required. |
| 21 | 90.6.10.3:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required32 mm |
| 22 | 90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 23 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 24 | 90.14.24.3:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.3 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Capacitor, Cylinderical Type suitable for direct connection to motors. |
| 25 | OD384212/2025-2026:Supply and Providing 4 pole enclosure for independent mounting of MCB/RCCB/Isolator etc.as required |
| 26 | 2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 27 | 2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.63 amps |
| 28 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 29 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 30 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 31 | OD384208/2025-2026:Supply and fixing 63A backelite HRC Fuse unit with HRC fuse link in the existing meter board and giving connections as required. |
| 32 | OD384205/2025-2026:Supply and fixing 63A ,415V ,2 way neutral link mounted on DMC/SMC base in the existing meter board and giving connections as required |
| 33 | OD384236/2025-2026:Earthing with G.I. earth pipe 2.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 34 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 35 | 5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 36 | OD384207/2025-2026:Supply and providing Test joint for earthing made up of 2 nos, 25x5 mm GI strip, 25 cm long placed on either sides of earth leads and watering pipe, bending, drilling and tightening with 4 sets of brass/SS nut, bolt, washer etc as required. |
| 37 | 90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 38 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 39 | 90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG) |
| 40 | OD384213/2025-2026:Providing Earthing system with B class G.I. earth pipe 1.7 meter long, 40 mm dia including accessories, earth excavation and providing masonry enclosure (300x300x300 mm inside), with CI/RCC cover plate having locking arrangement, 65x6 mm SS nut bolt with SS washers andwith charcoal/ coke etc as required |
| 41 | 90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class) |
| 42 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 43 | OD384209/2025-2026:Supply and providing the following size of bolt & nut with washers on the existing MS boxes/ earth bus etc as required including drilling necessary holes as required. 12x3mm brass nut & bolt. |
| 44 | OD384206/2025-2026:Supply and providing the following size of bolt & nut with washers on the existing MS boxes/ earth bus etc as required including drilling necessary holes as required. 25x6 mm brass nut & bolt. |
| 45 | OD384204/2025-2026:Supply and providing M8 eye bolt hook in wall / parapet for binding support for KSEB service main. |
| 46 | OD384210/2025-2026:Preparing completion and test certificates for KSEB connection Please Enable Macros to View BoQ information |