| 1 | FIRE HYDRANT SYSTEM - Supply, Installation, Testing and Commissioning of electric motor driven Terrace pump capable to deliver 450 LPM at 36 mtr head ,7.5 HP, 3 phase.(Kirloskar/Texmo/Lubi/WILO/KSB) |
| 2 | Supply & fixing of Terrace tank (5000 ltr) Fiber Water tank triple layer unbrakable extra thick and flexible material for long life new UV threaded lid to keep dust particles out with all needed accessories. (Plasto/Sintex) |
| 3 | Supply, Installation of structural steel like ( Beam , Channel, Angle, Plate & Sheet) for 2 nos terrace tank base & barricade . |
| 4 | Supplying, installation testing and commissioning of the following. ‘C' class MS pipe as per IS 1239 with welded / flanged / with heavy clamps, hangers, brackets or pipe supports as required including MS pipe of shorter lengths, tapering connecting pieces, short or long bends, forged specials like sockets, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners to the satisfaction of the Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes. (Sail/Jindal/Tata/Vizag Steel) - 100mm NB |
| 5 | 80 mm NB |
| 6 | 25 mm NB |
| 7 | Supply, installation, testing and commissioning of CI Butterfly valve of PN 1.6 rating with metal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required: . (Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) - 100 NB |
| 8 | Supply , installation ,testing and commissioning of Isolation Sluice valves tested to ISI marked ,PN 1.6 with CI body, bonnet & brass trim parts, & having necessary companion flanges, bolts, nuts, gasket including indicator for open and shut position to be installed. (Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) - 100mm NB |
| 9 | NRV conforming to IS 5312 (swing type) PN 1.6 having necessary companion flanges, CS hardwares. Gaskets, arrow indicating direction of flow, etc. complete. It shall be Marked and approved make (Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) - 100mm NB |
| 10 | Supply, Installation,Testing and Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with all accessories as per direction of Engineer-in-charge.(H guru/G-Guru) |
| 11 | Supply, Installation,Testing and Commissioning of Pressure Switch with with all accessories as per direction of Engineer-in-charge.(Danfoss) |
| 12 | Supply, Installation,Testing and Commissioning of 1\\" Air Release Valve with all accessories as per direction of Engineer-in-charge.(Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) |
| 13 | Supply, Installation,Testing and Commissioning of 2 - way fire brigade connection with all accessories as per direction of Engineer-in-charge..(Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) |
| 14 | Providing and fixing Single headed hydrant having outlet of 63 mm dia (2.1/2”) N.B. hydrant (IS:5290) landing valve in Stainless Steel Morris Pattern instanteous coupling type TAC / LFA approved & ISI certified heavy type hydraulically tested to 1.5 times working pressure with necessary nuts, bolts etc. (Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) |
| 15 | Providing and fixing Stainless Steel standard branch pipe dia 63 mm inlet with nozzle 20 mm dia outlet conforming to IS : 903, suitable for instantaneous connections to hose coupling etc. as required:(Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) |
| 16 | Providing & fixing 63mm dia 15 meter long RRL hose pipe as per IS 636 TYPE A TAC/ LFA approved of standard length of approved pattern and size including ss male and female Coupling duly bound with copper wire etc. complete. (CRC) |
| 17 | Supplying and fixing MS hose box of suitable size made of 1.6 mm thick MS sheet with double door arrangement , front door fixed with full glass and locking arrangement to accomodate two nos. 63 mm dia RRL hose reel , one no. branch pipe with powder coated and postal red finishing along with all accessories etc as required.The hose box size is 750 mm x 600 mm x 300 mm |
| 18 | Supply and installation, testing and commissioning of NRV conforming to API 594/598 (dual plate check type) with CI body & trim part, PN 1.6 having necessary companion flanges, CS hardwares. Gaskets, arrow indicating direction of flow, etc. complete. It shall be ISI Marked and approved. - 100mm NB |
| 19 | Supplying & fixing first aid fire hose reel of thermoplast braided suitably reinforced 20 mm size & 30 m standard length with Shut off nozzle, Hose to be swinging type wall mounted drum & recessing into hose cabinet to suit location including fixing with lead anchor fasteners & bolts (Including drum and swivel arrangement) etc complete.Hose reel having 30 mtr. Length with drum etc. complete. |
| 20 | Supply & fixing Ball Valve With all accessories as per direction of Engineer - in - charge.(Make-Ceasefire/Kartar/Zolota/NewAge/Leader/Audco) - 25 mm |
| 21 | 15 mm |
| 22 | Supply, installation, testing and commissioning of upvc pipes for filling line from existing tank to fire water tank on terrace floor on with all accessories.(Make-Plasto/Oriplast/Finolex)) |
| 23 | Supply , Installation,Testing and Commissioning of MCC cum Starter control panel (7.5 HP)for Terrace pump sets with incomer and selector switch for standby and working and auto/manual operation and necessary annunciation asper direction of Engineer-in-charge (Kirloskar/Texmo/Lubi/WILO/KSB) |
| 24 | Supply , Installation,Testing and Commissioning of Power cable (4 C X 10 SQMM) as required for motor run from Panel of the pump system as per direction of Engineer-in-charge. (Make-Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI) |
| 25 | Supply , Installation,Testing and Commissioning of Control cable (3C X 1.5 SQMM) as required for establishing automation Panel of the pump system as per direction of Engineer-in-charge.(Make-Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI) |
| 26 | Supply, Installation of Pump protection shed on terrace made by structural steel & sheet (Make-Sail/Jindal/Tata/Essar) |
| 27 | Supplying, installing, testing and commissioning approved make PVC FRLS conduits on ceiling / wall / floor etc. complete with accessories like, Junction boxes, Collars, Bends etc. 20mm dia.(Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal) |
| 28 | FIRE EXTINGUISHERS - FIRST AID - ISI Marked portable Fire extinguisher, 4.5 kg alluminium CO2 type fire extinguishers complete in all respect including initial fill and wall suspension brackets & shall conform to latest IS 15683 (Make-Ceasefire/Andx/Secure Zone) Meter Guage Mandotory. 1. The current and valid BIS certification IS: 15683 needs to be submitted along with offer.2. The vessel should be PESO Approved.3. The Product should be EN PED Approved and CE marked.4. The bidder must have valid PESO license to refill and store compressed gas cylinders as per Gas Cylinder rules 20045. The carbon dioxide gas shall conform to IS 15222 with latest amendment.6. Discharge valve shall be conform to all the requirement given in IS 3224:2002 or latest version thereof.7. The Co2 Cylinder shall be conforms to all the requirement given in IS 15660:2006.8. Minimum Fire rating as per IS: 15683 Class B: 55B needs to be provided for the extinguisher.9. The firm should submit the product performance test report from NABL accredited Lab as per IS 15683. |
| 29 | 6 Kg ABC (Powder Type) Fire Extinguisher In HP Mild Steel Cylinders ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683 (Make-Ceasefire/ Andx/Secure Zone) Meter Guage Mandotory. 1. The current and valid BIS certification IS 15683:2018 needs to be submitted along with the offer.2. The Product should be certified by any EN notified body as per EN 3-7, EN 3-8, EN 3-9.3. The firm shall submit the product certificate from an EN notified body.4. Dry Chemical powder used as extinguishing agent should be Mono Ammonium Phosphate (MAP) 90% concentration.5. The Product should be EN PED Approved and CE marked. 6. The extinguisher should be pressurized using high grade Dry Nitrogen as per IS 1747 standard. OEM declaration should be submitted.7. The firm should submit the product performance test report from NABL accredited Lab as per IS 15683. |
| 30 | Supply, Installation of Fire bucket 3 nos with stand (Red Colour) |
| 31 | AUTOMATIC FIRE DETECTION SYSTEM - Supplying, installation, testing and commissioning of Addressable Multi Detector(Smoke cum Heat) complete with base and isolator as per direction of Engineer-in-charge.(Make-Ceasefire/Kanex/Safepro) |
| 32 | Supply and installation of visual type response indicators with LED indicating lamp, housed in suitable MS enclosure with acrylic cover fixed in flush with wall to operate in conjunction with smoke/Heat detectors operating on 24 VDC installed above the false ceiling or below the false floor, complete with all accessories and fixing materials as required and as directed by Engineer-in-charge.(Make-Ceasefire) |
| 33 | CONTROL PANEL - Providing S.I.T.C of Microprocessor based Addressable Fire Alarm Control Panel (2 Loop) suitable for serving the followingg detectors & Devices in maximum with LCD display, complete with) 2 Nos 12 Volt 40 Ah SMF battery, Battery backup and also provision for 2 Nos potential free Normally open contact per loop to be used for interlocking of AHUs in the event of fire as per direction of Engineer-incharge. |
| 34 | MCP - Supplying, installing ,testing and commissioning of break glass type Manual call point . The Manual call point with monitor module shall be single stage type with all accessories and suitable sinages complete., the Manual call point shall be as per technical specification. and shall be of EN and LPCP listed. |
| 35 | Electronic Hooters - Supplying, installing ,testing and commissioning of Hooter Cum Strobe at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication. With Control Module. The Hooter cum Strobe with Control Module shall be flush or surface mountable type with all accessories etc., complete and as per technical specification. The devices shall be of EN and LPCP listed (Make: Bosch) |
| 36 | SIGNAGE Floor identification signage ( i.e., GROUND FLOOR …etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 7.5 cm with contrasting color from back ground. Size shall be 15cm x 60cm. |
| 37 | Way to exit signage at each stair on every floor, indicating the direction of fire exit, lettering size shall be 7.5 cm with contrasting color from back ground. Size shall be 15cm x 60cm. |
| 38 | Supplying and installing of in position the signages \\" FIRE ORDER\\" it should contain the following matter on 3mm thick \\"Opaque\\" PVC foam board of computerized cut, PVC Non-reflective self adhesive vinyle painted foam board of 3' x 4'. as per BIS Specification.a. A) evacuate the occupants by obeying fire exits / way to exit and emergency exits only and assemble at various assembly points. (B) if possible try to extinguish the fire by using nearest / suitable portable extinguisher or water from nearest wet riser. C) be calm and do not give any room from panic, walk, do not run. (D) if you encounter serious difficulty in evacuation, flat and try to attractattention of rescue team. |
| 39 | Fire hose reel (Size:6\\" X 4\\") |
| 40 | Fire extinguishers (Size:6\\" X 4\\") |
| 41 | Manual Call Point (Size:6\\" X 4\\") |
| 42 | Wiring - Supplying and drawing of 2X1.5 sq.mm PVC insulated PVC Sheathed FRLS cable in the existing surface/ recessed conduit with all accessories as per direction of Engineer-in-charge. Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI |
| 43 | Refilling of ABC 6 kg type fire extinguisher . |
| 44 | Refilling of Co2 4.5 kg type fire extinguisher . |
| 45 | Annual Comprehensive Maintenance Contract ( CMC) for fire fighting system of the building( @10%/Year) Please Enable Macros to View BoQ information |