| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 7 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 8 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 9 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 10 | 3 x 1.5 sq. mm |
| 11 | 3 x 2.5 sq. mm |
| 12 | 3 x 4 sq. mm |
| 13 | 3 x 6 sq. mm |
| 14 | supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed/ PVC conduit as required. |
| 15 | 2 Pair |
| 16 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 17 | 20 mm |
| 18 | 25 mm |
| 19 | Supplying and fixing metal box of following size (nominal size) on surface or in recessed with suitable size of phenolic laminated sheet cover in front including painting etc as required. |
| 20 | 100 mmx 100 mmx 60 mm deep |
| 21 | 180 mmx 100 mmx 60 mm deep |
| 22 | 200 mmx 125 mmx 60 mm deep |
| 23 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc as required. |
| 24 | 5/6 amps switch |
| 25 | 15/ 16 amps switch |
| 26 | 3 pin 5/6 amps socket oulet |
| 27 | 6 pin 15/ 16 amps socket oulet |
| 28 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 29 | 5/6 amps switch |
| 30 | 15/ 16 amps switch |
| 31 | 3 pin 5/6 amps socket oulet |
| 32 | 6 pin 15/ 16 amps socket oulet |
| 33 | Telephone socket outlet |
| 34 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required |
| 35 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 36 | 1 or 2 module (75 mm x 75 mm) |
| 37 | 3 module (100 mm x 75 mm) |
| 38 | 6 module (200 mm x 75 mm) |
| 39 | 8 module (125 mm x 125 mm) |
| 40 | 12 module (200 mm x 150 mm) |
| 41 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 6 pin 5/6 and 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. As required |
| 42 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 43 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 44 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 45 | Installation, testing and commissioning of ceiling fan, including wiring the down rod of standrand lenght ( up to 30cm) with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable etc. As required |
| 46 | Providing and fixing following rating and breaking capacity MCCB in existing cubical panel board including drilling holes in cubical panel, making connections etc as required |
| 47 | 200 Amp, 25 KA, TP MCCB |
| 48 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 49 | 12 way (4 + 36), Double door |
| 50 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 51 | Single pole |
| 52 | Double pole |
| 53 | Triple pole and neutral |
| 54 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 55 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 56 | Supplying and fixing DP sheet steel enclosure on surface/Recess alongwith 25/32 Amp. 240 volt \\" c' curve DP MCB complete with connection, testing, commissioning et. As required. |
| 57 | Supplying and fixing TP sheet steel enclosure on surface/Recess alongwith 16/25/32 Amp. 240 volt \\" c' curve TP MCB complete with connection, testing, commissioning et. As required. |
| 58 | Supplying nd Fixing 20 A, 240V SPN Industrial type socket outlet, with 2 pole and Earth metal enclosed plug top along with 20 A, \\" C\\" curve SP MCB in sheet steel enclosure, on surface or in recess. With chain metal cover for the socket outlet and complete with connections, testing, commissionimng etc. as required. |
| 59 | Supplying nd Fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and Earth metal enclosed plug top along with 30 A, \\" C\\" curve TP MCB in sheet steel enclosure, on surface or in recess. With chain metal cover for the socket outlet and complete with connections, testing, commissionimng etc. as required. |
| 60 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 61 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 62 | LED Panel light 2x2 ft. (System lumen efficacy ≥105<120 lm/Watt) |
| 63 | 36 watt (Refer tender document Annexure: III for detailed specification) |
| 64 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) |
| 65 | 30 watt (Refer tender document Annexure: III for detailed specification) |
| 66 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 67 | Upto 35 sq. mm |
| 68 | Above 35 sq. mm and upto 95 sq. mm |
| 69 | Above 95 sq. mm and upto 185 sq. mm |
| 70 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in existing RCC / HUME / METAL pipe etc. As required. |
| 71 | Upto 35 sq. mm |
| 72 | Above 35 sq. mm and upto 95 sq. mm |
| 73 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct asrequired. |
| 74 | Upto 35 sq. mm |
| 75 | Above 35 sq. mm and upto 95 sq. mm |
| 76 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 77 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 78 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 79 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 80 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 81 | Above 4.5 Meter and upto 6.5 Meter |
| 82 | Providing and laying cement concrete for pedestal of electric pole including shuttering along with demolishing of exisiting cement concrete base with complete as per directions of Engineer-in-Charge [Each Pedestal size: 0.3 X 0.3 X 0.45 mtr) |
| 83 | Demolishing cement concrete manually/ by mechnical means including disposal of material withing 50 Meter lead as per direction of engineer-in-charge. Nominal concrete 1:3:6 or richer mix (including equivalent design mix)[50 Pedestals of 0.04 Cum each] |
| 84 | Providing and laying in position cement concrete of specifed grade excluding the cost of centering and shuttering- all work upto plinth level: 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) [50 Pedestals of 0.04 Cum each] |
| 85 | Centering and shuttering including strutting, propping etc. and removal of form for foundations, footings, bases of columns, etc. for mass concrete [50 Pedestals of 0.54 sqm each] |
| 86 | Supplying and embedding following dia G.I Pipe (medium class) in pole collar/ foundation during casting for cable entry including bending the pipe to the rquired shape complete as required. |
| 87 | 32 mm dia |
| 88 | Supplying and fixing 32/40 mm dia x 2.00 meters long G.I pipe (meidum class) bracket for mounting of fiuorscent/ HPMV/ HPSV street light fitting on pole including bending shape, 2 nos. 40 mmx 3mm flat iron clamps with nuts, bolts andthe pipe to the require washer, painting the flat iron primer and finish piant etc as required. |
| 89 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. |
| 90 | Excavation for cable trenches in soft soil depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soi, refilling with sand or good soil after laying of cable/pipe etc. in layers of 20 cm, ramming watreing and disposal of surplus excavated soil as directed, witinh a lead of 50 meters. |
| 91 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 92 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 93 | Supplying, Installation, Testing and commissioning of CAT6 Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 94 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required. |
| 95 | 1 Run of cable |
| 96 | Painting steel work with Deluxe Multipaint to give even shade . Two or more coat applied @0.90 litre /10Sqm over an undercoat of primer applied @0.80 ltr/ 10 Sqm of approved brand and manufacture |
| 97 | Supplying of labour for miscellaneous work for dismantling of boards, wiring etc |
| 98 | Skilled labour in Electrical trade |
| 99 | Unskilled labour in Electrical trade |
| 100 | Attending day to day complaints of no light/ non working points / providing temporary connections in IIP lab buildings, hostel & guest house etc as required. |
| 101 | Supplying and installation of Industrial Heavy duty exhaust fan of 380 mm sweep 1400 rpm suitable for 230v 50hz ac supply complete with blade, regular, frame and moving system etc as required .The same will be inspected and aproved by Engineer-in-charge before its dispatch from factory to site. |
| 102 | Supplying and installation of exhaust fan of 300 mm sweep metal frame suitable for 230v 50hz ac supply complete with blade, regular, frame and moving system etc as required .The same will be inspected and aproved by Engineer-in-charge before its dispatch from factory to site. |
| 103 | Supplying and installation of exhaust fan of 230 mm sweep metal frame suitable for 230v 50hz ac supply complete with blade, regular, frame and moving system etc as required .The same will be inspected and aproved by Engineer-in-charge before its dispatch from factory to site. |
| 104 | Supplying and installation of exhaust fan of 250 mm sweep PVC frame suitable for 230v 50hz ac supply complete with blade, regular, frame and moving system etc as required .The same will be inspected and aproved by Engineer-in-charge before its dispatch from factory to site. |
| 105 | Supplying and fixing 40A to 63A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 106 | Double pole |
| 107 | Triple pole |
| 108 | Four pole |
| 109 | Supply and fabrication of sheet steel MCB enclosure fitted with din rail for MCB of following rating complete with connections including drilling holes etc as required. |
| 110 | Double pole enclosure |
| 111 | Four pole enclosure |
| 112 | Supply and replacement of capacitor of ceiling fans/ exhaust fan/ wall fan/ padestal fan of size of 2.5 to 4 mfd etc as required |
| 113 | Supply & replacement of 16 Amp. Plug top, 3 pin with indigator etc. as required |
| 114 | Supply & replacement of 6 Amp. Plug top, 3 pin with indigator etc. as required. |
| 115 | Supplying of following General purpose industrial compact batten suitable for single or twin LED Tube light with integral LED driver, available in single / double side connection options with all as required. Fixture size: (LxWxH) in (1233x36x46) mm (for 1x22 W), (1233x71x46) mm (for 2x22 W) |
| 116 | 1 X 4' X 22W LED batten |
| 117 | 2 X 4' X 22W LED batten |
| 118 | Supplying of following high efficiency LED tube rod lamps LED luminaire in existing fitting fixture with connection etc. as required. |
| 119 | 4' X 20W LED luminaries tube rod |
| 120 | Providing 9 watt retrofit LED bulbs for guest house etc…as required. |
| 121 | Supply of GI electrical pole straight pole of overall length upto 6 meter having two steps and dimensions of 80 mm x 60 mm and pole thickness is 3.65 mm x 3.25 mm for fixing street light complete with M.S base plate having 6.00 mm thickness and with one meter welded tubalar bracket for mounting light fixture all etc. as required. (Detailed pole structure will be as per drawing and aproved by Engineer-in-charge before its dispatch from factory to site). |
| 122 | Supplying, Installation, Testing and Commissioning of 145-500 VAC, Digital Voltage Monitoring Relay (1C/O + 1C/O) associated with 32A 4 Pole power contactor with 2NO+2NC auxiliary contacts and 240V AC coil voltage installed in 200 X 200 X 150 mm Metal Enclosure fabricated out of high quality CRCA sheet, suitable for indoor installation with door lock arrangement with ON and Fault indication lamps (240V AC) complete with 3 phase 4 wire wiring with 6mm2 FLRS Cu wire for input and output, 1.5mm2 FRLS Cu wire for Control circuit, 0.5mm2 FRLS Cu wire for indication circuit etc. as per direction of Engineer In Charge.Cable gland holes shall be provided in top and bottom of the Metal enclosure. |
| 123 | Repairing of exisiting ceiling fan motor complete with bearing replacement, dismantling, rewinding and assembling including with all necessary accessories etc. as required. |
| 124 | Supply & Installation of Pole mounted SMC/PVC/FRP junction box for street lighting for 1 phase/3 phase high wattage HPSV/HPMV/MH based lighting system including terminal blocks suitable for 16Sqmm Size , 2 Amps MCB SP , Cable entry from bottom ,Weatherproof and shall be suitable for Pole mounting arrangement etc. as required.minimum size 200 X 140 X 95 |
| 125 | Supply & Installation of Electrical Panel/DB Door lock with all necessary accessories etc. as required. Please Enable Macros to View BoQ information |