Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | ( HVAC Work) |
| 2 | Sectional type air handling unit |
| 3 | Supply installation, testing and commissioning of double skin floor mounted AHU with backward curved fan ,cooling coils dx type , 4(W)+4(S) RD , 50 mm external static complete with filter section with 50 mm thick washable synthetic pre filters having efficiency 90% down to 10 micron with drive package with TEFC drive motor suitable for 415 +-5% volt, 50 hz 3 phase ac supply, to be connected with outdoor condensing units. |
| 4 | 8000 CFM (50 mmwg st. press.) |
| 5 | 11 TR outdoor units for DX coil AHU. |
| 6 | Supply, Installation, Testing & comissioning of aircooled ductable airconditioning unit with Scroll compressors, statically dynamically balanced centrifugal blower having nominal air flow 2200 CFM driven by belt wilth multi speed motors, multi rows colling coil internally grooved copper tube with Aluminium fins, Inbuilt safety devices for compressor protection like thermal protector, Internal pressure, cutout enclosure shall be equiped with synthetic filter with following capacity. |
| 7 | 5.5 TR ductable package unit. |
| 8 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for HVAC system, complete with fittings ,with suitable adjustable ring type hanger supports, jointing / brazing including accessories, insulated with XPLE Class-O tubular insulation with Class-O closed cell elastometric nitrile rubber tubular sleeves section so specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 9 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm or as per OEM standard with 19 mm thick insulation |
| 10 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm or as per OEM standard with 19 mm thick insulation |
| 11 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm or as per OEM standard with 19 mm thick insulation |
| 12 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
| 13 | 22 GUAGE (0.80 mm) |
| 14 | 24 GUAGE (0.63 mm) |
| 15 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. |
| 16 | 19 mm |
| 17 | P/F Flexible double canvas connection water proof between indoor units and supply air duct. |
| 18 | SITC of duly painted MS stand. |
| 19 | Supply installation testing and commisioning of GI volume control damper complete with neoprene rubber gaskets,nuts,bolts,screw linkages,flanges etc as per specifactions. |
| 20 | Supplying & Fixing of powder coated extruded aluminium Suplly Air grills with aluminium volume control damper as per specifications. |
| 21 | Supply fixing of powder coated extruded aluminium return Air grills with louvers but without volume control Damper complete as required. |
| 22 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control Dampers with anti smudge ring & removable core. |
| 23 | Supply, fixing testing commissioning of return air diffusers of powder coated aluminium without volume control Dampers anti smudge ring & removable core. |
| 24 | P/F Heater Bank for winter heating comprising of 15 kw capacity having arrangement for on/off in stages with thermostat, geyserstat contactor, interconnected wirting control panel etc. |
| 25 | P/F Heater Bank for winter heating comprising of 4.5 kw capacity having arrangement for on/off in stages with thermostat, geyserstat contactor, interconnected wirting control panel etc. |
| 26 | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. |
| 27 | Fire damper |
| 28 | Actuator |
| 29 | Supply, Installation, Testing and Commissioning of Electrical Panel Cubical Type, dust and vermin proof ingress protection, IP-42 Floor Mounted Switchboard with Hinged Lockable Doors fabricated out of 14/16 SWG CRCA Sheet with Powder Coating through 7 tank process with all accessories live parts shrouded and busbars insulated with heat shrinkable sleeves including solid / flexible connections, earthing etc., having 3mm thickness Gland Plate. LT Panel should have withstand fault levet of equal to 50 KA for 1 second. Fittted with gaskets, Panel comprising of the following:- |
| 30 | PANEL No.-1 & 2 (8000CFM AHU) |
| 31 | INCOMER |
| 32 | 200A FP MCCB 25KA TMD BASED WITH O/L & S/C PROTECTION (1) |
| 33 | EXTENDED ROTARY HANDLE (1) |
| 34 | SPREADER SET (1) |
| 35 | RED INDICATION LAMP RED LED TYPE, 240V AC (1) |
| 36 | YELLOW INDICATION LAMP YELLOW LED TYPE, 240V AC (1) |
| 37 | BLUE INDICATION LAMP BLUE LED TYPE, 240V AC (1) |
| 38 | AMMETER & VOLTMETER (1) |
| 39 | CT`s 60/5A CL-1 15VA RESIN CAST/NYLON CASING FOR METERING (3) |
| 40 | CT SHORTING LINK (3) |
| 41 | END PLATE FOR CT SHORTING LINK (1) |
| 42 | NEUTRAL LINK (1) |
| 43 | MCB SP 6A,10 KA C-CURVE (3) |
| 44 | 5HP DOL STARTER (FOR AHU MOTOR) |
| 45 | 40A TP MCB 10KA (1) |
| 46 | 12A POWER CONTACTOR TP (1) |
| 47 | OLR(1) |
| 48 | GREEN PUSH BUTTON (1) |
| 49 | RED PUSH BUTTON (1) |
| 50 | ON INDICATION LAMP RED (1) |
| 51 | OFF INDICATION LAMP GREEN (1) |
| 52 | TRIP INDICATION LAMP AMBER (1) |
| 53 | AUTO/MANUAL SELECTOR SWITCH6A, 2P 2W WITH OFF (1) |
| 54 | NEUTRAL LINK (1) |
| 55 | MCB SP 6A,10 KA C-CURVE (1) |
| 56 | SPP (1) |
| 57 | FOR 15KW HEATER BANK |
| 58 | 63A FP MCB 10KA (1) |
| 59 | 60A TP CONTACTOR (1) |
| 60 | ON INDICATION LAMP RED (1) |
| 61 | 6A SP MCB 10KA (1) |
| 62 | 18.5KW S/D STARTER (OUTDOOR COMPRESSOR UNIT 11TR) |
| 63 | 80A TP MCCB 25KA TMD BASED WITH O/L & S/C PROTECTION (4) |
| 64 | SPREADER SET (4) |
| 65 | 70A CONTACTOR (8) |
| 66 | 50A CONTACTOR (4) |
| 67 | ADD ON BLOCK (8) |
| 68 | 6A SP MCB 10KA (4) |
| 69 | ON INDICATION LAMP RED (4) |
| 70 | OFF INDICATION LAMP AMBER (4) |
| 71 | GREEN PUSH BUTTON (4) |
| 72 | RED PUSH BUTTON (4) |
| 73 | NEUTRAL LINK (4) |
| 74 | STAR DELTA TIMER (4) |
| 75 | SPP (4) |
| 76 | AUTO MANUAL SEL SWITCH (4) |
| 77 | CURRENT TRANSFORMER 60/5A (12) |
| 78 | CT SHORTING LINK WTH END PLATE (12) |
| 79 | AMMETER WITH ASS (4) |
| 80 | VOLTMETER WITH VSS (4) |
| 81 | ENCLOSURE & ACCESSORIES(L=950,H=1925,D=350) |
| 82 | Fabrication in 1.6/2.0mm.CRCA Sheet Powder Coating in Siemens Gray Shade, Wall mounted,Cable Entry will be Top & Bottom Suitable for Cable ,Lock, Rubber Gasket, hardware etc. (1) |
| 83 | BUS BAR & HARDWARE |
| 84 | 100A. Aluminium Main Bus Bar,Load wise Sub Feeder Bus Bar Colour Coated Heat Shrink Bus Bar sleave Nut-Bolt,Washer |
| 85 | ,Hardware etc. (1) |
| 86 | WIRING & ACCESSORIES |
| 87 | Power & Control Wiring will be (ISI 1100V) flamc smoke FRLS PVC Single Core Copper Wire,Copper Lugs, PVC Sleeve, Ferruels Numbers, Hardware & Labour etc. (1) |
| 88 | PANEL No.-3(WALL MOUNTED) |
| 89 | 63A FP MCCB 25KA TMD BASED WITH O/L & S/C PROTECTION (1) |
| 90 | EXTENDED ROTARY HANDLE (1) |
| 91 | SPREADER SET (1) |
| 92 | RED INDICATION LAMP RED LED TYPE, 240V AC (1) |
| 93 | YELLOW INDICATION LAMP YELLOW LED TYPE, 240V AC (1) |
| 94 | BLUE INDICATION LAMP BLUE LED TYPE, 240V AC (1) |
| 95 | AMMETER & VOLTMETER (1) |
| 96 | CT`s 60/5A CL-1 15VA RESIN CAST/NYLON CASING FOR METERING (3) |
| 97 | CT SHORTING LINK (3) |
| 98 | END PLATE FOR CT SHORTING LINK (1) |
| 99 | NEUTRAL LINK (1) |
| 100 | MCB SP 6A,10 KA C-CURVE (3) |
| 101 | 5.5TR PACKAGE UNIT |
| 102 | 25A FP MCB 10KA (2) |
| 103 | HEATER BANK-A, 4.5KW |
| 104 | 25A FP MCB 10KA (1) |
| 105 | 25A TP CONTACTOR (1) |
| 106 | ON INDICATION LAMP RED (1) |
| 107 | 6A SP MCB 10KA (1) |
| 108 | HEATER BANK-B, 4.5KW |
| 109 | 25A FP MCB 10KA (1) |
| 110 | 25A TP CONTACTOR (1) |
| 111 | ON INDICATION LAMP RED (1) |
| 112 | 6A SP MCB 10KA (1) |
| 113 | ENCLOSURE & ACCESSORIES(L=900,H=1000,D=250) |
| 114 | Fabrication in 1.6/2.0mm.CRCA Sheet Powder Coating in Siemens Gray Shade, Wall mounted,Cable Entry will be Top & Bottom Suitable for Cable ,Lock, Rubber Gasket, hardware etc. (1) |
| 115 | BUS BAR & HARDWARE |
| 116 | 100A. Aluminium Main Bus Bar,Load wise Sub Feeder Bus Bar Colour Coated Heat Shrink Bus Bar sleave Nut-Bolt,Washer,Hardware etc. (1) |
| 117 | WIRING & ACCESSORIES |
| 118 | Power & Control Wiring will be (ISI 1100V) flamc smoke FRLS PVC Single Core Copper Wire,Copper Lugs, PVC Sleeve, Ferruels Numbers, Hardware & Labour etc. (1) |
| 119 | Supply, laying, testing and commisioning of XLPE insulated armoured copper cabling 4 core 6 sq mm complete in all respect as per speification and direction of engineer incharge. |
| 120 | Supply, laying, testing and commisioning of PVC insulated armoured copper cabling 4 core 10 sq mm . complete in all respect as per speification and direction of engineer incharge. |
| 121 | Supply, laying, testing and commisioning of XLPEinsulated copper cabling 3 core 2.5 sq mm . complete in all respect as per speification and direction of engineer incharge. |
| 122 | Supplying and laying 25 mm x 5 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm.) |
| 123 | Supplying and laying 6 SWG wire at 0.50 metre below ground level for conductor earth electrode, including connection / termination with G.I. thimble etc. as required. |
| 124 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 125 | 300 mm width x 50mm depth x 1.6 mm thickness. |
| 126 | 150 mm width x 50mm depth x 1.6 mm thickness. |
| 127 | P/F rigid CPVC/UPVC drain piping (40 mm dia) complete with fittings, supports as per specifications and duly insulated with 9 mm thick closed cell nitrile rubber insulation. |
| 128 | Minor civil work including opening of walls, cutting, chieseling etc. complete in all respect. |
| 129 | Additional GST @ 6.33% |
| 130 | Civil component |
| 131 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed. |
| 132 | All kinds of soil |
| 133 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth: consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m |
| 134 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 135 | 1:5:10 (1 cement : 5 coarse sand (zone-III) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 136 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : |
| 137 | 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size). |
| 138 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 139 | Foundations, footings, bases of columns, etc. for mass concrete |
| 140 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete in foundation & superstructure. |
| 141 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 142 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : |
| 143 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 144 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. |
| 145 | Cement mortar 1:4 (1 cement :4 coarse sand) |
| 146 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. |
| 147 | Granite of stone slab colour Black, cherry/ Rubby Red |
| 148 | Area of slab over 0.50 sqm |
| 149 | Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete. |
| 150 | Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete. |
| 151 | Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : |
| 152 | 300x16 mm |
| 153 | 250x16 mm |
| 154 | Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : |
| 155 | 250x10 mm |
| 156 | Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete : |
| 157 | 125 mm |
| 158 | Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868)transparent or dyed to required colour and shade with necessary screws etc. complete. |
| 159 | Twin rubber stopper |
| 160 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work , including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 161 | Steel work in built up tubular (round, square or rectangular hollow tubesetc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding andbolted with special shaped washers etc. complete. |
| 162 | Hot finished welded type tubes |
| 163 | Providing and laying double charged Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. |
| 164 | Size of Tile 600x600 mm |
| 165 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : |
| 166 | 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) :2011 (Board with BIS certification marks) |
| 167 | 12 mm cement plaster of mix : |
| 168 | 1:4 (1 cement: 4 fine sand) |
| 169 | 15 mm cement plaster on the rough side of single or half brick wall of mix : |
| 170 | 1:6 (1 cement: 6 fine sand) |
| 171 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : |
| 172 | Two or more coats on new work |
| 173 | Providing and applying white cement based putty of average thickness 1 mm @ 6kg /10 Sqm of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 174 | Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. |
| 175 | two coats |
| 176 | Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete |
| 177 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge. |
| 178 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
| 179 | In cement mortar |
| 180 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : |
| 181 | Of area beyond 3 sq. metres |
| 182 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. |
| 183 | Providing and fixing soil, waste and vent pipes : |
| 184 | 75 mm dia |
| 185 | Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS: 3989 |
| 186 | Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including cost of cutting holes and making good the walls etc. : |
| 187 | For 75 mm dia pipe |
| 188 | Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. |
| 189 | 75 mm dia |
| 190 | Sand cast iron S&S as per IS- 3989 |
| 191 | Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. |
| 192 | 75x75x75 mm |
| 193 | Sand cast iron S&S as per IS - 3989 |
| 194 | Providing and fixing collar : |
| 195 | 75 mm dia |
| 196 | Sand cast iron S&S as per IS- 3989 |
| 197 | Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fittings of diameter: |
| 198 | 75 mm |
| 199 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 200 | 100 mm inlet and 75 mm outlet |
| 201 | Sand cast iron S&S as per IS - 3989 |
| 202 | Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall : |
| 203 | 15 mm dia nominal bore |
| 204 | 20mmdia nominal bore |
| 205 | Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : |
| 206 | 25 to 40 mm nominal bore |
| 207 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : |
| 208 | 20 mm nominal bore |
| 209 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) : |
| 210 | 15 mm nominal bore |
| 211 | 20 mm nominal bore |
| 212 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 213 | 15 mm nominal bore |
| 214 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame o f 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: |
| 215 | 150 x 100 mm size P type |
| 216 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 217 | Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. complete : |
| 218 | For pipes 100 to 250 mm diameter |
| 219 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : |
| 220 | For fixed portion |
| 221 | Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 222 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately). |
| 223 | Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 224 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. |
| 225 | Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side |
| 226 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item) |
| 227 | With Tinted/ float glass panes of 5.50 mm thickness |
| 228 | Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete. |
| 229 | Upto 5mm depth and 5 mm width |
| 230 | Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete. |
| 231 | Providing and fixing 30 mm thick factory made prelammated internal PVC flush door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 20 mm x 40 mm for styles as well as top, bottom & lock rail. M.S. frame shall have a coat of steel primers of approved make and manufacture. The inside panel shall consist of 20 mm thick multi chamber hollow PVC section of 1 mm wall thickness bonded using solvent cement / Cynoacrylate adhesive with 5 mm thick (±0.5 mm ) plain PVC sheet of density 600 kg / cum manufactured by an ISO 9000 certified company, on both side of inside panel. All the four edge of the panel to be sealed with lipping of 10mm thick & 20 mm wide PVC sheet batten (made by sticking 2 nos. rigid foam PVC sheet of 5 mm (±0.5 mm ) thickness using PVC solvent cement adhesive. Door edge lipping to be painted with PVC ink of matching colour of plain moulded PVC sheet of door 20 mm thick (5mm x 4 nos.) PVC sheet to be given for lock provision at lock height. Door to be fixed with frame with 3 nos. S.S. butt hinges of size 100 x 25 x 2 mm & 50 mm long steel screws drilled suitable to pass through both the walls of the M.S. tube. Other hardwares should be fixed by 25 x 8 mm size steel screws etc. complete in all respect as per direction of Engineer Incharge. |
| 232 | Providing and fixing of 100 mm wide horizontal Zebra blinds with accessories and powder coated channels, louvers, bottom weight etc of approved make including removal of existing blinds complete in all respects. |
| 233 | P/F C.P. grating 100 nominal dia |
| 234 | Less rebate for dismantled material |
| 235 | Pressed steel door frame |
| 236 | Wooden flush door shutters of assorted sizes including fittings |
| 237 | Add 0.5% Water Charges |
| 238 | Add GST IMPACT @ 6.33% |
| 239 | Electrical component |
| 240 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 241 | Group C |
| 242 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 243 | Group C |
| 244 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 245 | 25 mm |
| 246 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 247 | 3 x 1.5 Sq. mm |
| 248 | 3 x 4 Sq. mm |
| 249 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 250 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 251 | Supplying and fixing of High efficacy max 20w min 130 lm polycarbonate batten having sleek design and efficient aluminum heat sink, complete in all respect upto the entire satisfaction of EIC. |
| 252 | Supplying and fixing of Suspended Linear 8 Feet Fixture in 40 W+/- 1W Suspended mounted having Extruded Aluminium housing with HET diffuser with minimum system lumen efficacy of 115 lm/W with system lumen 4600 lm and width<55mm, P.F.>0.95 with THD<10% ,CCT 5700 K, CRI 80.The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 140V to 300V. Fixture have Surge Protection 3kV , complete in all respect upto the entire satisfaction of EIC. |
| 253 | Supplying and fixing of 35 W +/- 1W suspended Hexagonal shaped Hollow ring type fixture having Housing made up of extruded Aluminum powder coated White/Black Housing with 100lm/W ,THD<10%,PF>=0.95 CRI 80 and CCT of 4000K with High efficiency, non-yellowing PMMA diffuser having dia of 600 mm with Surge protection 2.5 KV, complete in all respect. |
| 254 | Supplying and fixing suspended Linear 2 Feet Fixture suitable for creating Hexagonal pattern by continous connection in 10 W+/- 1W Suspended mounted having Extruded Aluminium housing with HET diffuser with minimum system lumen efficacy of 115 lm/W with system lumen 1150 lm and width<55mm, P.F.>0.95 with THD<10% ,CCT 4000K, CRI 80.The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 140V to 300V .Fixture have Surge Protection 3kV, complete in all respect upto the entire satisfaction of EIC. |
| 255 | Supplying and fixing suspended Linear10W 300mm V Connector Suitable for connecting linear fixture for creating Hexagonal Pattern, complete in all respect upto the entire satisfaction of EIC. |
| 256 | Supplying and fixing of Suspended Linear 4 Feet Fixture in 20 W+/- 1W Suspended mounted having Extruded Aluminium housing with HET diffuser with minimum system lumen efficacy of 115 lm/W with system lumen2300 lm and width<55mm, P.F.>0.95 with THD<10% ,CCT4000 K, CRI 80.The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 140V to 300V. Fixture have Surge Protection 3kV , complete in all respect upto the entire satisfaction of EIC. |
| 257 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 258 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 259 | 4 Module (125mmX75mm) |
| 260 | 8 Module (125mmX125mm) |
| 261 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 262 | 5/6 A switch |
| 263 | Telephone socket outlet |
| 264 | I/O Socket 2 Module |
| 265 | Supply, Installation, Testing and Commissioning of 1400 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, long down rod( as required at site), 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 250 CMM, 280 RPM (tolerance as per IS : 374-2019), THD less than 10%, all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 266 | Supply and installation of MS fan hook made from 12mm round iron rod, job includes making proper arrangement in the ceiling to install the hook with the existing structure so as to give it strength and re dress the same as required at site, completed in all respect. |
| 267 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 268 | 4 way (4 + 12), Double door |
| 269 | Supplying and fixing following way, horizontal type three poleand neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 270 | 6 way (4 + 18), Double door |
| 271 | Supplying and fixing 5amps. To 32 amp. Rating, 240/415 volts, ''C'curve, MCB suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 272 | Single pole |
| 273 | Triple pole |
| 274 | Triple pole and neutral |
| 275 | Supply of 4 core XLPE insulated and PVC sheathed armoured power cable of 1.1 kV grade, copper conductor armoured cable of following size. (i) 10 sqmm. |
| 276 | Supply of 3.5 core XLPE insulated and PVC sheathed armoured power cable of 1.1 kV grade, Aluminum conductor armoured cable of following size. (i) 120 sqmm. |
| 277 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 278 | upto 35 sq. mm (clamped with 1mm thick saddle) |
| 279 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 280 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required. |
| 281 | 4 X 10 sq. mm (25mm) |
| 282 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required. |
| 283 | 3½ X 120 sq. mm |
| 284 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 285 | 1 run of cable |
| 286 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 287 | 2 Pair |
| 288 | Supplying,installation,testing and commissioning of Passive Infrared(PIR) technology based occupancy sensor for corridor having high preformance, non regulating programmable type, suitable for connected load upto 10Amp , for mounting height up to 2.8 mtr and for 12 m coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required. |
| 289 | Rebate on old dismantled material Fixture-50Nos, Choke-30Nos, old switch/cockets and bakelite sheets,etc |
| 290 | Add GST @6.33% on DSR items (i.e481699/-) Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail