| 1 | Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS / International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only 2.0 TR with 5 Star BEE Rating |
| 2 | Same as above but for 1.5 TR with 5 Star BEE Rating |
| 3 | S/F of Extra main lead wire 2.5 sq mm 3 core round copper cable for providing the power supply from the indoor unit to the outdoor unit for split AC.(without GST) |
| 4 | S/F Automatic Voltage stabilizer 5 KVA voltage range130V to 300V for upto 2.0 Ton AC copper winding.(without GST) |
| 5 | S/F Automatic Voltage stabilizer 4 KVA voltage range130V to 300V for upto 1.5 Ton AC copper winding.(without GST) |
| 6 | SITC of Suction/Discharge copper pipe line in split AC unit 1.5 Ton capacity including brazing,nitrile, rubber insulation 6 mm thick class\"O\" etc. complete 1/4\" (6.40mm) and 1/2\"(12.70 mm).(without GST) |
| 7 | SITC of Suction/Discharge copper pipe line in split AC unit 1.8/2.0 Ton capacity including brazing,nitrile, rubber insulation 9 mm thick class\"O\" etc. complete 3/8\" (9.50 mm) and 5/8\"(15.90 mm).(without GST) |
| 8 | S/f of Extra Drain Pipe heavy duty PVC plastic braided 20 mm OD flexible pipe for condensed water drain with clipping accessories.complete(without GST) |
| 9 | S/f of M.S angle iron mtg.bracket for outdoor unit with antirust paint.(without GST) |
| 10 | Supplying & fixing suitable size Gl box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required. |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 12 | Same as above but 3 pin 5/6 A socket outlet |
| 13 | Same as above but 15/16 A switch |
| 14 | Same as above but 6 pin 15/16 A socket outlet |
| 15 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 16 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 3 Module |
| 17 | Same as above but 4 Module |
| 18 | Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching)<3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt )12 -15 watt |
| 19 | S/F Single LED Light wall bracket 3 to 6 watt on matching M.D.F.E.G. board base etc. complete in all respect. but excluding GST . 330-660 system lumens, 110lm/w, PF>0.95. Make Philips /Havells or equivalent |
| 20 | Supply & Installation of Water Geyser 25 Liter complete in all respect including supply of all material, labour and T & P etc. required for proper completion of the work as directed by Engineer in charge.(Havells/Bajaj or equivalent ) Excluding GST |
| 21 | Supply of Oil Room Heater 2400 Watt complete in all respect including supply of all material, labour and T & P etc. required for proper completion of the work as directed by Engineer in charge. (Havells/Bajaj or equivalent ) Excluding GST |
| 22 | LED Batten light (System lumen efficacy ≥105 Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency85%, Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)18-22 Watt |
| 23 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 24 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.185 Sq mm 3-1/2 core |
| 25 | S/L of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade on wall surface.95 Sq mm 3-1/2 core |
| 26 | Same as above but for 35 Sq mm 3-1/2 core |
| 27 | Same as above but for 16 Sq mm 4 core |
| 28 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.200 mm dia (OD-200 mm & ID-175 mm nominal) |
| 29 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 30 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 31 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 32 | Supplying and laying 25 mm X 5 mm G.l. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.l. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.l. nut bolt & spring washer spaced at 50mm) |
| 33 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator)6 way (4 + 18), Double door |
| 34 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCCBs and incomer) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door |
| 35 | S&F of 63 Amp. 4 pole MCB(10 KA) C Curve Cat A |
| 36 | S&F of 80 to 100 Amp 4 pole MCCB (16 KA) Thermal Magnetic release Cat A |
| 37 | S&F of 160 Amp 4 pole MCCB (16 KA) Thermal Magnetic release |
| 38 | S/F of Rubber matting 1800x900x12 mm tested and chequred |
| 39 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 40 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 31/2 X 185 sq. mm (57mm) |
| 41 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 31/2 X 95 sq. mm (45mm) |
| 42 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 31/2 X 35 sq. mm (32mm) |
| 43 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm) |
| 44 | S/F of 250 mm sweep fresh air fan Model Ventilus 10\" Make:- Crompton Greaves |
| 45 | Supply, Installation, Testing and Commissioning of LT Panel vermin proof floor mounting , M.S. channel base with bottom and Fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Bus Bar of panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating.The main bus bar shall run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure the bear the jerks of short Circuit of 50kA for panels having ACB as Incomer & 36kA for panels having MCCB Incomers. Panel shall be constructed in fully Segregated Compartment Design for Each Feeder as per 3b construction Format. The Panel shall be completed in all respect as per IS: 8623 Part-2&3. There shall be Separate Metering Compartment for incomer metering and outgoing metering. All Incomer Feeders shall be provided with Multifunction Metering along with Phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. and all Outgoing Feeders 100A & above shall be provided with 3 phase Ammeter along with phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. The Feeders above shall be provided a accommodated all Measuring Instruments shall be Digital type & all Indicating Lights shall be LED type. Wiring shall be done from 1100V Grade PVC Insulated copper flexible wire. All ACB shall be Electrically operated Draw-out type with Microprocessor Based O/L, S/C & E/F Release of Breaking/ Withstand Capacity (ICU/ICs/Icw) 50kA or more All MCCB shall be Thermal Magneetic/Microprocessor with O/L & S/C Protection along with Required Spreaders & Extended Rotary Handle with pad Locking facility of Breaking capacity (ICU/ICS) 36kA or more All MCB shall be Thermal 10kA \"C\" Curve. Cubicle type switch board shall be Cat-A and B only. Incoming 400 Amp MCCB -1 No & outgoing 200 A MCCB-1 no., 100 A MCCB-2 nos. & 63 A MCCB-1 no. |
| 46 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 47 | S/O LED Lamp 12Watt |
| 48 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 49 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 50 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130 mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T&P complete in all respect. |
| 51 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130 mm and base plate 12mm thik) having 3mm thikness with double arm bracket (1 Mtr length) in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T&P complete in all respect. |
| 52 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) 90 watt |
| 53 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.10 Sq mm 4 core |
| 54 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 55 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 56 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 57 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 nos. 2.5 sqmm |
| 58 | Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with Base Plate made of powder coated die cast aluminium and extruded Al. housing with UV Stablized PC diffuser, SMD LEDS, Electronic driver set, confirming to IP 65/66 and IK 07 and above prolection, 600- 800mm height, complete in all respect. 960-1920 sy stem lumens, >120 Lm/W, PF>0.95, THD <10% at fulll load, >300V Over Voltage protection, 4 KV internal Surge Protection, with 5 years warránlee. CAT-AAA |
| 59 | Supply and fixing of decorative 40 to 45 Watt LED Post top indirect light luminaire having Pressure die cast aluminium body and Clear glass with driver set confirming to IP 65 and above protection complete in all respect. CAT-AA |
| 60 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. 25 A TPN |
| 61 | Providing, laying and fixing 100 mm dia G.l. pipe (medium class) in ground complete with G.l. fittings including trenching (75 cm deep)and re-filling etc as required. |
| 62 | S/F of 40 Amp 4 way heavy duty cadmium plated copper conector with end plate complete in all respects. Please Enable Macros to View BoQ information |