| 1 | Supply and Fix in replacement of XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 95 sq mm 3.5 core, laid in trenches/ducts /encased in GI pipe /fixed to pole complete all as specified and directed by Engineer-in-Charge. |
| 2 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 3 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 4 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 5 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 6 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 500 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 7 | Material and Labour for GI tubing medium grade in repairs incl. accessories for protection of cables on poles / under road crossingof sizes 80 mm dia. complete all as specified and directed by Engineer-in-Charge. |
| 8 | Excavation in trenches of n.exc 1.5m wide and n.exc 1.5 m in depth for laying of cables, erection of poles, struts/stays etc andany type of soil, complete all as specified and directed by Engineer-in-Charge. |
| 9 | Earth work in excavation of soft disintegrated/ordinary rocks by mechanical means (Hydraulic excavator)/ in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. complete all as specified and directed by Engineer-in-Charge. |
| 10 | M&L for Tibba sand for cushioning to underground cable for 8cm below the cable and 15cm above cable complete all as specified and directed by Engineer-in-Charge. Note :- Only punned thickness will be measured for payment purpose. |
| 11 | Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mmand abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables for protection. complete all as specified and directed by Engineer-in-Charge. |
| 12 | Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cm in soil. complete all as specified and directed by Engineer-in-Charge. |
| 13 | Removing of excavated soilnot exc. 50 M and deposting where directed at a level n.exc. 1.5m above the startingpoints complete all as specified and directed by Engineer-in-Charge. |
| 14 | M&L for Auguring/ Driling /Boring of holes under road, pavement, hard standing by trenchless technology by mannual /machine, suitable for laying of HDPE/GI pipe of 80/100 mmbore dia complete all as specified and directed by Engineer-in-Charge. |
| 15 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size 95 to 185 sqmm complete all as specified and directed by Engineer-in-Charge. |
| 16 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Al conductor cable of size 240 to 500 sqmm complete all as specified and directed by Engineer-in-Charge. |
| 17 | Supply, fixing and replacement of MCCB 400 Amps 4 pole 36 KAmicroprocessor adjustable release type (Icu=Ics=100%) including accessories like spreaders, nut bolt etc suitablesetting complete all as specified and directed by Engineer-in-Charge. |
| 18 | Supply, fixing and replacement of MCCB 250 Amps 4 pole 36 KAthermal adjustable release type (Icu=Ics=100%) including accessories like spreaders, nut bolt etc suitablesetting complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply, fixing and replacement of MCCB 160 Amps 4 pole 36 KA thermal adjustable release type (Icu=Ics=100%) including accessories like spreaders, nut bolt etc suitablesetting complete all as specified and directed by Engineer-in-Charge. |
| 20 | M&L for disconnectingloading, unloading andtransportation for shiftingof transformer of any capacity and type from one location to another within the army area by wheeled crane incl. connecting complete necessary electrical connection, installation, testing and commissioning of repaired/serviced transformer complete all as specified and directed by Engineer-in-Charge. |
| 21 | Supply, fixing, testing and commissioning as in replacement of feeder piller box, outdoor type, floor mounted, factory made CPRI approved suitable for 415 volt, 4 pole, 50 Hz, AC supply system having aluminium bus bar duly insulated by insulation of RYB and nutral colour coding 400 Amps rating mounted on porcelain insulators including RYB LED indication lamp panel mounting type (Set of three) - 01 No. The size of the panel should not be less than 600 x 500x 350 mm and panel shall be powder coated, factory made double door made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frameof size 50 mm x 50 mm x 5mm and ground clearance 600 mm minimum duly embedded in PCC (1:3:6) type C-1 platform and including wiring of multistranded copper cable of suitable size including lugs and cable gland to incoming and outgoing cables complete all as specified and directed by Engineer-in-Charge. |
| 22 | M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick,buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised using galvanised iron strip 32×6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of MES SSR part-I 2010 connected to earthing test point as specified and testing on completion including provision of 40mm dia light grade pipe upto 7.5m length as protection and watering pipe shall be 20mm bore medium grade including all excavation and earth work in any type of strata incl PCC pit (1:3:6) type C-1 with RCC cover including charcoal,salt,funnel, complete all as specified and directed by Engineer-in-Charge. |
| 23 | M&L for Earthing complete with copper earth plate elctrodes 60cm×60cm × 3.15 mm thick and 20×3 mm copper strip as earthing lead buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 3 meter (BGL) connected to Copper strip of size 20x3 mm earth leadby means of bolts, nuts, check nut and washer of copper including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 25 mm bore “light grade” galvanized iron protection pipe for earth lead copper strip upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete all as specified and directed by Engineer-in-Charge. |