| 1 | Supply, installation,testing and commissioning of factory made 11 KV Compact Sub Station as per IS-14786 (2000) with non extensible consisting of 1 Nos manually operated 11 KV/400 Amps VCB in SF6 insulated stainless enclosure, HT Cable/Bus bar 630A,1 No, Transformer 315 KVA, 11/0.433 KV CRT Oil cooled and LT switchgear complete in accordance with IEC: 62271-202 of& associated LT devices, Fault making capacity 52.5 KA/ Sec,Power frequency 1 min : 28 kV, Input range +5% to -5%, HV Current 16.83 Amps and LV Current 420 Amps, Star / Delta connection, 3 phase, and off load tap changeover, Losses as per IS-1180 (part-1) 2014 EEL-3 with amendment no. 4 Total Losses @50% load -890W, Total Losses @100% Load -2440W , 5 steps, Average AmbTemp 50 degree C, HV & LV Winding -Copper Wound,Winding temp - 95 deg C above ambient(ACB/MCCB/bus bar/Cable) comprising of and including the following: - |
| 2 | Enclosure(i) Outdoor type 2 mm thick galvanised iron (GI) enclosure with 4 mm thick GI base, powder coated. Roof shall be designed to support load upto 250kg/ sqm with suitable slanting (approx 10 degree) to prevent accumulation of water. Partition between compartments with 2 mm thick GI sheet(ii) Door with locking arrangement at suitable positions for easy operation and maintenance of all the components(iii) Suitable provision for HT and LT cable entry and S&F at site double compression cable glands for each cable entry (iv) Suitable LED illumination lamp with door operated switch for each compartmentIntegral lifting arrangement. Appropriate Danger notice plates at all sides and on each compartment(v) Protection grade IP 54 for HT & LT switchgear compartment and IP 34 for transformer compartment(vi) Type tested against Internal Arc at 21kA for 01 second duration(vii) Suitable louvers designed for natural ventilation and thermal class K10 |
| 3 | HT Section(i) 01 No VCB SF6 insulatedconsisting of 11 KV 630 Amps 50 Hz Vacuum Circuit BreakerHorizontal Draw Out VCB with Manual/230V AC Motor Operated Spring Charging Mechanism with 24V DC Closing /Opening Shunt trip coils, Aux. Switch, Mechanical On/Off Push Button, mechanical Operating Counter with metering 1 No CT, PT, IDMT, Cubical Auxiliary Relay, 8 Window Annunciator Model No. SI-801, Battery Power Pack with 7AH Battery & in built charger for 24V Circuit 01 VCBand cable box with direct Raiseras per IEC 62271 and other relevant IS/ IEC standards.(ii) Copper Busbar of suitable size-01 set(iii) Vacuum Circuit Breaker shall be suitably rated to withstand max 28 KV (RMS) at rated power frequency and lightning impulse withstand voltage 75 KV peak. It should have short circuit withstand capacity 21 KA for 3 seconds and internal arc withstand capacity 21 kA for 0.1 second.(iii) Self powered microprocessor electronic based numerical relay (with LCD display.and manual reset type) for protection against over current, earth fault, short circuit and transformer winding temperature increase. (iv) Current Transformers for 03 phases (03 Nos) with ratio : 200/5A,Class1.0/10P10, Burden 15-15 VA. (v) Three position (Open, Close & Earth) independent operation Disconnector Switch(vi) Fault passage indicator(vii) Mechanical operation interlock(viii) Operation counter |
| 4 | (ix) Emergency Push button(x) Shunt Trip Coil suitably rated(xi) Manual Operating Handle (xii) Automatic motorised Spring Charging mechanism alongwith facility for manual spring charging handle / motor(xiii) Thermostatically controlled space heater of suitable rating connected through MCB and mounted by suitable spacers so that heater does not come in contact with panel wall or panel accessories.(xiv) Cable Boots suitable for 3C x95 Sqmm forincoming and 3 x 1C x 95 sqmm for outgoing |
| 5 | (xiv) HT Metering Module comprising of (A) Potential Transformers for 03 phases with ratio: 11 KV/√3/110V/√3/110V/√3, class 0.5-3, Burden 50-50 VA earthed (B) Three phase LED multi-function meter for indication of Current, Voltage, Frequency, Power Factor, KW, KVA, KVAR, KWH, KVAH, KVARH, MD, fault data memory etc(C) Suitable Battery with battery charging unit alongwith suitable circuit for standby connection/ operation of control/ protection circuits(D) Suitable size and numbers of MCBs, Limit Switches and control wiring as per OEM(E) Suitable Alarm for trip indication(F) LED indicator lamps fot indicating \"ON\", \"OFF\", \"TRIP\", \"EARTH\", \"TRIP CKT HEALTHY\" |
| 6 | Transformer (i) 11 KV/ 433 V, 315 KVA, 3 phase, 50 Hz epoxy cast resin dry type copper wound transformer/ Oil cooled with vector group DYN11 as per IS:11171 of make: ECS/ IMPEX/ Voltamp (Vadodara) or as recommended by OEM of CSS and subsequently approved by dept(ii) Off load tap changer with +5% to -10% in steps of 2.5%(iii) Winding temperature indicator with alarm and trip arrangement(iv) Surge arrestor metal oxide type for primary side(v) Full load and No load losses as per latest relevantIS / ECBC |
| 7 | LT Section (i) Incoming Air Circuit Breaker Draw out 415 volt grade 630 Amps, 4 pole, 50 kA, manual fixed (MF) type microprocessor release with overload, short circuit, earth fault, over and under voltage protection, High short time withstand capacity Icu = Ics = Icw for 1 sec, 100% rated neutral pole,Test button for on-load testing complete of make: ABB/ Siemens/ Schneider/ Crompton Greaves/ L&T - 01 No(ii) Copper busbar 1000 Amp rated for main bus and suitable copper busbar for main bus to incoming side of MCCBs and internal control wiring with copper cables(iii) Three phase multi-function with LED display meter for indication of Current, Voltage, Frequency, Power Factor, KW, KVA, KVAR, KWH, KVAH, KVARH, fault data memory etc(iv) Current Transformers for 03 phases (03 Nos) with ratio : 630/5 A, 5 VA, class 1.0(v)) Phase indicator LED lamps R, Y, B |
| 8 | Interconnection (i) RMU to transformer with 3 run of single core 95 sqmm copper conductor duly PVC 11KV insulation sleeve and other necessary accessories(ii) Transformer to LT Panel incomer with copper busbar 1000 amp duly PVC insulation sleeve(iii) Earth continuity conductor between integral components with 50 x 6 mm GI strip(iv) Suitable termination points for connecting external earth strips to the CSS |
| 9 | Miscellaneous (i) Make of complete CSS shall beABB/ Siemens/ Schneider/ Crompton Greaves/ L&T/ ITE. The make of components shall be as mentioned against each component. The make of components not mentioned in the schedule shall be as recommende/ selected by the OEM. The tenderer need to submit complete specification, make of each component and GA Drgs for approval before confirming order to the OEM. (ii) The foundation of the CSS shall be as recommended by the manufacturer. The OEM should submit structural and architectural drg of foundation. The cost of foundation deemed to be included in the quoted rate.(iii) Earth continuity conductor between integral components with 50 x 6 mm GI strip.(iv) Suitable termination points for connecting external earth strips to the CSS shall be provided.(v) The cable terminations shall be executed by certified/ licensed cable jointers to avail the guarantee/ waranty of the CSS. The tenderer shall submit the license/ certificate from competent authority of the cable jointer.(vi) Any parts/ components not mentioned in the specification but forming integral part of the CSS as per standard specification of the OEM shall also be provided and the cost thereof deemed to be included in the quoted rate.(vii) The factory acceptance test shall be done by representative of accepting officer in presence of the contractor before dispatch of the CSS from the factory of OEM. The pre-commissioning test after installation shall also be done by Senior Electrical Inspector/ Electrical Inspector detailed by appropriate departmental authority. The instruments and other accessories required at the time of inspection shall be arranged by the contractor and the cost deemed to be included in the quoted rate. |
| 10 | Excavation in trenches in hard / dense soil n exc 1.5 metre wide and not exc 1.5 metre deep and getting out including forming bottom surface for laying HT cable, foundations etc complete all as specified and directed . |
| 11 | Excavation in trenches in hard / dense soiln exc 1.5 metre wide but exc1.5 metre and n.exc 3.0m deep and getting out including forming bottom surface for laying UG cable, foundation for poles etc complete all as specified and directed. |
| 12 | Returning filling in including spreading levelling watering and well ramming in layer not exceeding25 cm thick complete all as specified and directed. |
| 13 | Removing excavated material (soil) to a distance n.exc 50 m and depositing where directed at alevel n exc 1.5 metre above the starting point complete all as specified and directed. |
| 14 | Supply and laying DWC (double Wall corrugated) HDPE polyethiline pipe Outer dia of 120 mm and inner dia 103.5 mm including couplers, bends, cap etc. with smooth internal and profiled external surface for non pressure under ground cable complete all as secified and directed. |
| 15 | M & L for hard surface cutting as in road, pavement etc for laying of cables, pipes etc of any size up to approximate width of 45 cm and depth 60 cm, returning filling and making good to surface with PCC 1:3:6 type C-2 using 40mm graded stone aggregate complete after laying of cable, pipe etc as required and as specified & directed. |
| 16 | M & L for making horizontal bore by suitable means for insertion of GI pipe 80 mmbore for passing cable across the road without cutting the road complete all as specified& directed. |
| 17 | M & L for80mm bore galvanised iron tubing light grade laid in trenches or fixed to pole and / or laid under road in any position with necessary clamp nut and bolt for cable protction complete all as specified& directed. |
| 18 | Supply, laying, connecting and testing XLPE HT UGinsulated (Earthed) screened, PVC bedded, galvanised steel striparmoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, cross sectional area 95 sqmm,3 core conforming to IS-7908(Part-I) 1988, laid in trenches/down through pipe fixed to walls/poles or laid under roads/drains/ path/ culverts complete all as specified and directed.(Note : Excavation & earth work, sand, cable protection shall be measured and paid seperately). |
| 19 | M & Lfor cablejointing kitfor 11 KV grade (Earthed) HT cable for outdoor end terminationheat shrinkabletype complete with jointing material and accessories suitable for 95 sqmm3 core XLPE armouredaluminium conductor cable complete all as specified and directed. |
| 20 | Supply, laying, connecting and testing XLPE insulated armoured heavy duty electric LT cable with aluminium conductor, 1100 volts grade, cross sectional area 400 Sqmm, 3.5 core complete all as specified and directed. |
| 21 | Supply, laying, connecting and testing XLPE insulated armoured heavy duty electric LT cable with aluminium conductor, 1100 volts grade, cross sectional area 300 Sqmm, 3.5 core complete all as specified and directed. |
| 22 | Supply, erecting and fixing steel tubular swaged pole 11 m long Type -410 SP-55 conforming to IS-2713 part I to III 1980 with and including cast iron base plate, finial taper plug,nuts, bolts and washers etc. and fixed into plain cement concrete foundation duely painted with two coats of aluminium paint over one coat of red oxide primer including preparetion of surfaces and making strip 150mm wide upto 1.50m( above PCC coping) by black , yellow paint in alternate layers and pole nos complete all as specified and directed. (Note : Earth work, PCC will be measured and paid seperately) |
| 23 | M & L for vertical isolation air break gang operated switch HT 11 KV triple pole mechanically operated out door type and rated capacity 200 Amp with 9 insulator and steel frames mechanically operated mechanism consisting of three male contacts & threefemale contacts of tinned copper, three arching horns, three MS jumper carrier equipped with braided copper belt, operating rod of heavy grade 32/25mm bore GI pipe of suitable length worked from ground levelwith locking arrangementwith clamp of flat iron50X6 mm including testing after installationcomplete all as specified and directed. |
| 24 | M & Lfor cross arms bracing supports clamps and back plate fabricated from structural steel section including nuts bolts washers welding bending cold or hot drilling holes for bolts in any shape & size as indicated or directed and including of one primer coat one under coat one finishing coat with aluminium paint complete all as specified and directed. |
| 25 | M & Lfor anti climbing device on HT/LT poles comprising of 2.24 mm dia galvanised steel 2 strand barbed wire with 2 mm dia wire wrapped spirally around poles to a length of 0.5 to1.0 metre clamped and properly secured complete all as specified and directed. |
| 26 | M&L for Lightening arrestor single pole zinc oxide (gap less) surge type heavy duty complete with all fittings, station class, discharge capacity 10 KA for 11 KV, 50 Hz conforming to IEC 99-4/1991 standardcomplete all as specified and directed. |
| 27 | S&F Aluminium conductors, reinforced (ACSR) conductor of any size Rabit 6/3.35 no/dia steel 1/3.35 no/dia for as per site requirement including stretching, binding with aluminium binding wire, jumpers, line taps etccomplete all as specified and directed. |
| 28 | M&L for expulsion fuse assembly single pole vertically mounted on MS channel 11000 volts grade above 25A & upto 50 Amps capacity including making connections with HT cables/GOD with provision of jumper suitable crimped/fixed with appropriate size of lugs/connectorscomplete all as specified and directed. |
| 29 | S&F pin type, procelain, vitreous white,brown or green insulator including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, 150mm height, 150 mm dia, 11000 Volts grade complete all as specified and as directed. |
| 30 | S&F \"Two in series\" disc assembly with disc type insulator, procelain, vitreous, 145 mm high and 255 mm dia ball and socket type, white, brown or green with tension clamps for conductors with working presure 11000 Volts complete all as specified and as directed. |
| 31 | S&F aluminiam clamp and connectors parellel grove (PG) clamp 11000 Volts complete all as specified and as directed. |
| 32 | M & L for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled/ paintedwhite with letters figures and conventional skull and bones in signal red colour and fixed with M.S. clmps , bolts and nuts of approved size, for HTof size 25 X20 cm complete all as specified and directed. |
| 33 | S&F RCC cable route indicator (75x75x600mm) with base foundation 300 x 300 x 400 mmdepth below ground level, embossed with letters \" MES 11 KV HT\" complete all as specified and directed. |
| 34 | M&L for PCC (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate) as in foundation forpole and stay, filling in and mass concrete complete all as specified and directed. |
| 35 | M&L for PCC (1:2:4) type B-1(using 20 mm graded crushed stone aggregate)as in coping of pole etc including form work complete all as specified and directed. |
| 36 | M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SSR Part I all as specified and testing on completion includingprovisionof earth lead protected by 50 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade and charcoal & salt around earth plate in alternate layers of 15 cm [v]. GI protection pipe of size 50 mm bore light grade upto 7.5 m. |
| 37 | M & L for earthing complete with copper earth plate 600 x 600 x 3mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to copper strip of size 20X3 mm by means of bolts, nuts, check nuts and washers as per SSR Part I all as specified and testing on completion includingprovision of earth lead protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 4 0mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade and charcoal & salt around earth plate in alternate layers of 15 cm [v]. GI protection pipe of size 40 mm bore light grade upto 7.5 m. |
| 38 | M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth wire of 4mm dia by means of bolts, nuts, check nuts and washers as per SSR Part I all as specified and testing on completion includingprovisionof earth lead protected by 15 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C1 using 40mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade and charcoal & salt around earth plate in alternate layers of 15 cm [v]. GI protection pipe of size 15 mm bore light grade upto 7.5 m. |
| 39 | Supply, instalation, testing and commissioning ofLTPANEL, TPN 415 Volts, 50 Hz,out door cubical type floor mounted CPRI approved factory made,double doordust and vermin proofIP-54, fabricatedout of CRCA sheet not less than 3.15 mm thickwith 2mm thick for internal compartment duly powder coated fixed on angle iron pedestalmade out of 50x50x6 mm with cable chamberfor individual feeders for incommingand outgoing connections,one set of LED indicator lampRYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley copper bus bar suitable for carrying of current600 Amps with suitable connections from MCCB out going to main bus bar shall be carried out with TPN copper bus bars of suitable rating and connections from main bus bar to out going MCCB\"s (intake point) will be carried out with TPN copper bus bar as per MCCB rating duly insulated and colour coded heat shrinkable sleeve and shall be rigidly mounted on suitable size of bridge insulator including necessary PCC foundation of minimum 0.35 m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal all as specified and directed comprising of the following :- |
| 40 | (a) MCCB 630 Amps 4 Pole 50 Hz 415 V with thermal magnectic release having rupturing capacity 50 KA - 1Nos (Incomer). |
| 41 | Outgoing :-(a) MCCB 400 Amps 4 Pole 50 Hz 415 V with thermal magnectic release having rupturing capacity 25 KA - 1 Nos ( Ext Lt panel 400 amp MCCB Foot Ball Ground)(b )MCCB 125 Amps 4P 50 Hz 415 V with thermal magnectic release having rupturing capacity 16 KA - 1 No (IB bldg-01)(c)MCCB 100 Amps 4P 50 Hz 415 V with thermal magnectic release having rupturing capacity 16 KA - 2 Nos ( sup sec-01, spare-01)(d) Current transformer 300/ 5 A - 3 Nos(e) Three phase LED multi-function meter for indication of Current, Voltage, Frequency, Power Factor, KW, KVA, KVAR, KWH, KVAH, KVARH, MD etc - 1 No(f) Phase Indicating lamp LED type (R, Y, B) - set of three. |
| 42 | M&L for construction of transformer platform of size 3.0x3.0x1m high from ground level including excavation and earth work in trenches in any type of soil, PCC 1:5:10 type E-2 for foundation, brick work in CM 1:6, PCC 1:2:4 type B-1 as in coping, plaster 10mm thick in CM 1:6 on bricksurface complete with 75mm thick PCC 1:4:8 type D-2 as in sub base of floor with topping of PCC 1:2:4 type B-1, 100mm thick in floor and finished even and smooth (without using extra cement) including returning, filling in and removal of surplus spoil to a distance n.exc 50m including chain link fencing 1.8 m height made out of 4mm dia GI wire 150 x 100 mm mesh with mild steel angle iron 50 x 50 x 6mm as in fencing post and embedded inPCC 1:2:4 type B-1, 30 x 23 x 30cm block at1.5 mtr interval each side as approved with 1 No steel gate (3.5 m clear) span with locking arrangement made out of 15mm dia mild steel rod50x50x6mm angle iron frame and painting the steel surface with 2 coats of aluminium paint over a coat of red oxide primer and 3 coats of white washing on cement work including ISMB 100mm channel 02 Nos for fixing transformer, complete all as specified and as directed. |
| 43 | Supply and installation of Servo Voltage Stabilizer capacity 500 KVA with self-lubricating Carbon Roller Assemblies suitable for unbalanced load. Output Line Voltage 400 Volts +/ - 1% for input line voltage of (319-478)VAC i.e. 400 volt+-20% fluctuations Output Phase Voltage 230 volt +/- 1% for input phase voltage of 184-276 volt i.e. 230volt with +-20% fluctuations Output voltage range If input phase voltage is less than 184 volt or more than 276 volt, output voltage should be as close as possible to 230 volt. However, under any circumstances, output voltage should not be below 180 volt or more than 250 volt. The stabilizer can be disconnected if the output voltage goes below 180 volt or above 250 volt.Type Suitable for Unbalanced Phase 3-Ph, 4 Wire Frequency 50 Hz Cooling Oil Cooled Mode of Operation Automatic/Manual CORE CRGO M4 Grade Copper Electrolytic Grade Rate of correction (7-8)Volts / Sec Temp. Rise at 100% load 35°C Deg. Cent. Above Ambient Winding Temp. Rise 40°C Deg. Application OUTDOOR TYPE (IP 55) Transformer Oil IS 335 making Output Accuracy +/- 1% from No load to full load Response Time 20 milli secs Overload Capacity Shall withstand 50% over Load for 30 seconds & 75% overload for 10 Seconds. Wave Form Distortion Should be Nil Losses at No Load Less than 0.25% of the total capacity Losses on load Losses on full load: Less than 1% at full load Losses on 30% load: Less than 0.5% at 30% load Losses on 70% load: Less than 0.75% 0.5% at 70% load Metering Analog Metering for Phase & Current flow Terminations Aluminium Bus Bars to be provided In the Termination Box Expected Working Life >15- 20 years Control Panel Suitable Controller with display of the various parameters and selector switch controlled bypass arrangement Protections 1.Cut-Off with alarm 8 window annunciation 2.Input High voltage 3.Input Low Voltage 4.Output Short Circuit 5.Output Overload 6.Surge Protection Effect of unbalance onNeutral Should be nil Standards applicable IS:9815 Guarantee Unconditional for 3 years from the date of Commissioning LT Panel Provision 1. Incomer - 800A, 50KA FP Microprocessor based withOverload, ShortCircuit and Earth fault protection. 2. Outgoing - 800A FP Microprocessor based with Overload,Short Circuit and Earth fault protection.3. Bypass Arrangement – Using a suitable FP ACB. In case of maintenance of the servo, we have to safely bypass theservo so that the supply to the unit is restored. 4. Annunciation of the faults 5. Communication capable metering to monitor the incomingand outgoing parameters 6. Aluminium Bus with Panel fabricated in 14/16SWG CRCA sheet 7. Suitable earthing arrangement along the length of the Panel. 8. Doors to be earthed using green/yellow coloured wire 9. Control cabling to be wired using 2.5sqmm copper. 10. Panel shall be powder coated with RAL7035with complete fixing arrangement complete all as specified and as directed. |