| 1 | Supply, installation, testing & commissioning of addressable micro processor based 2 wire fault tolerant loop, required loop net workable type Single loop (each loop accessing maximum 99 detectors and 99 modules) fire alarm/detection control panel.The panel shall be able to give location of all fire/fault signal with address.The panel shall have rectifier, loop cards,LCD display unit to indicate Fire/Fault signal with address.The panel shall have a built in power supply and battery charger alongwith maintenance freeSMF lead acid batteries as per manufacturers design with battery charger complete as required and as per specifications duly approved by EN 54 complete including making connections all as specified and directed by Engr-in-Charge. Make :- Morley-IAS by Honeywellmodel Name/Number. DXc2/ 714-001-225 or Bosch model No. FPA-1000-V2 / Apollo model No. Elite RS 10860-10 |
| 2 | Supply, installation, testing and commissioning of surface / semi- flush mounted Dual Action Manual Pull Station \"Push In & Pull Down\" including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete all as specified and directed by engineer-in-charge. |
| 3 | Supply and fixing red colour PVC insulated PVC sheathed armoured copper conductor cable of size 2 Core x 1.5 Sqmm with casing capping including fixing on walls with saddles not more than 60 cm intervals complete all as specified and directed. |
| 4 | Supply and fixAddressable sounder range 90 dblwith strobe complete all as specified and directed |
| 5 | Supply and fixing detectors Complying with and type certified to EN - 45 Addressable type optical multi Sensor detector heat and smokecombination Photoelectric /Optical with base with self built intelligence as per IS: 11360 complete all as specified and directed. |
| 6 | Supply and fixing addressable fault Isolator suitable for fire alarm system complete all as specified and directed.Make :- Morley-IAS by Honeywell/Bosch/Apollo |
| 7 | Supply, installation, testing and commissioning of FM approved and UL listed addressable control module to provide FACP a circuit for notification appliances (e.g. Horns, Strobes, Horn Strobes, etc.) having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete all as specified and directed by engineer-in-charge.(Power shutdown to all lifts other than Fire lifts in case of fire alarm). |
| 8 | Supply and fixing MCB double pole 10 Amps, 10 KA, \"C\" series with factory made SS enclosure fixed on wall and making connections complete all as specified and directed. |
| 9 | Material & Labour for Point Wiring for one light Point/one fan point/ one call bell point, controlled by one switch with 1100 volts grade single core conforming to (IS:694 /1990) PVC insulated unsheathed 1.5 sqmm multi stranded copper conductor cable (FRLSH) with contineous earth wire of 1.5 Sqmm stranded copper conductor cable (FRLSH) PVC insulated unsheathed , drawn in and including PVC conduitMMS ,duly surface to wall/floor or above false ceiling with fittings(ISI marked) not less than 20 mm dia(Color coding of wires shall be Phase, neutral and earth wire all as specified ) sunk Metal flush box with and incl decorative polycarbonate frame for housing Modular Switches, sockets , fan regulators etc including white cover cover plate for one 3pin/5pin 5/6 Amps switch socket out let onindependent board with other switches, with cables 1.5 sq mm size,complete all as specified and directed. Note:- i) Cost of cutting chases of suitable girth where required on brick /concrete surface and making good disturbed surface shall be deemed to be included in quoted rates. Quoted rates also included for modular box with plate and conduit pipe. |
| 10 | Supply and fixing Switch socket combination 2 in 1, 3 pin, 5 and 15 Amp flushtype universal combined 2 module ISI marked 230 volts, 50Hs completeall as specified by Engr-in-charge . |
| 11 | Supply and fix Fire Alarm sounders / Sirens electronic type horizontal two stage continuous normal operation for at least 50 minutes with sound level 65 db to 120 db Measured at 1.5 m with sound output variation of + 5 db 1500m range complete all as specified and directed. |
| 12 | Supply, installation, testing and commissioning of FM approved and UL listed intelligent monitor module, with built-in type identification automatically identifying the device as addressable monitor module to the FCAP, to supervise a circuit of dry-contact input devices, powered directly by two-wire SLC loop, high noise immunity, SEMS screws with clamping plates for ease of wiring, direct-dial entry of addresses, LED indicators, etc. complete all as specified and directed by the Engineer-in-charge. |
| 13 | Supply and fix Beam Master detector with Transmitter and receiver |
| 14 | Supply & fix of Maintenancefreebattery duly charged12 V 7.2 AH, ISI marked complete all as specified and directed . |
| 15 | S&F Gl frame work for seamless ceiling comprising of Gl perimeter channnel 0.55 mm thick with two unequal flanges of 20 and 30 mm and web of 27 mm fixed to surrounding wall using nylon sleeves and screws at 450 mm centre to centre/intermediate channel 0.9 mm thick having two equal flanges of 15 mm each and web of 45 mm suspended from soffit at approx 900 mm centre to centre with Gl cleat and steel expansion fasteners with and including ceiling section (not exc 1.2 m length) of 0.55 mm thickness having kurled web of 50 mm and flange of 26 mm each with lips of 10.5 mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457 mm centre to centre. Hangers 6 mm dia. G.I. (upto 1200mm length) adjusting fixed to roof slabs by means ofceilling cleats made out of G.I. flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm longcomplete all as specified |
| 16 | M&L for 12 mmSeamless calcium silicate ceiling made out of 1800 x 1200 mm size board of siliceous and calcareous material reinforced with cellulose fibre fixed to the ceiling section with 25 mm long self drilling and tapping screws having phillips head with under head cutter at 200 mm centre to centre, including finshing the joint of face board with specially formulated jointing compound and 48 mm wide fibre tape to provide seam less finish (Frame work for ceiling shall be measured and paid separately) |
| 17 | M&L for preparation of new surface of ceiling and applying 2 coats of distemper over one coat of alkali resistant priming paint complete all as specified |