| 1 | Taking down copper/aluminium point wiring ( light, fan, socket, power ) complete, including fixture and fittings such as switches, ceiling roses, pendents, regulators, sockets etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately ) and making good disturbed surface of walls, floors, etc complete all as specifiedand directed by Engr-in-Charge. |
| 2 | Taking down carefully submain wiring any size complete all as specifiedand directed by Engr-in-Charge. |
| 3 | Taking down DB including MCCB/MCB any type any size complete all as specifiedand directed by Engr-in-Charge. |
| 4 | M & L for surface point wiringwith two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm (Nominal area) drawn in and including PVC casing caping of required size with all fittings and accessories alongwith one single core green colour PVC insulated 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm as earth lead and connected to earth dolly for one light point or one fan point or one call bell point controlled by one, one way switch including PVC switch board of required size or 3mm thick hylam sheet screwed with 04 nos cadmium coated screws & cup washer on existing MS concealled box for mounting of switch, regulators or bell push and casing caping terminal box for mounting ceiling rose/ holders etc incl dismentling taking down old unserviceable point wiring and making good to disturbed surfaces complete all as specifiedand directed by Engr-in-Charge.Make: Havells/KEI/RR Kabel/Polycab/Gloster |
| 5 | All as per item No.4 above but for one 5 amps socket point independent complete all as specifiedand directed by Engr-in-Charge. |
| 6 | All as per item No.4 above but for one 5 amps socket point on same board complete all as specifiedand directed by Engr-in-Charge. |
| 7 | All as per item No.4 above but forone two way light point controlled by two way switch complete all as specifiedand directed by Engr-in-Charge. |
| 8 | All as per item No.4 abovebutcable of size 2.5 sqmmfor one 16 amps socket (Power) point independent complete all as specifiedand directed by Engr-in-Charge. |
| 9 | M & L for surface submain wiringwith two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm (Nominal area) drawn through in and including PVC casing caping/PVC conduitsize with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm as earth lead and connected to earth dollyincl dismentling taking down old unserviceable wiring and making good to disturbed surfaces all as specified and directed. NOTE: (a) Two run of cable with one run of earth wire and one run of casing capping/conduit will be measured as one length complete all as specifiedand directed by Engr-in-Charge. Make: Havells/KEI/RR Kabel/Polycab/Gloster. |
| 10 | All as per item No.9 abovebutwith cable of size 2.5 sqmm |
| 11 | All as per item No.9 above but with cable of size 4.0 sqmm |
| 12 | All as per item No.9 above but with cable of size 6.0 sqmm |
| 13 | All as per item No.9 abovebut with cable of size 10.0 sqmm |
| 14 | S&F in replacement 5 Amp switch piano type single pole one way complete all as specifiedand directed by Engr-in-Charge. |
| 15 | S&F in replacement5 Amp switch piano type two waycomplete all as specifiedand directed by Engr-in-Charge. |
| 16 | S&F in replacementbell push piano type one way 240 voltcomplete all as specifiedand directed by Engr-in-Charge. |
| 17 | S&F in replacementsocket flush type 6 amps, 3 pin, 230v complete all as specifiedand directed by Engr-in-Charge. |
| 18 | S&F in replacementswitch socket combination multipurpose 2-in-1 flush type 3 pin5 amps, 230v complete all as specifiedand directed by Engr-in-Charge. |
| 19 | S&F in replacementswitch socket combination multipurpose 2-in-1 flush type 3 pin 16 amps and 3 pin 6 amps, 230v complete all as specifiedand directed by Engr-in-Charge. |
| 20 | S&F in replacementlamp Holder insulated body with back plate for batten fitting complete all as specifiedand directed by Engr-in-Charge. Make : Honeywell/Anchor/Cona |
| 21 | S&F in replacementLED lamp 12 watt, CDL, B-22 cap, (Pin type), 230V, PF-0.95 (min)complete all as specifiedand directed by Engr-in-Charge. Make : Bajaj/Philips/Wipro/CG |
| 22 | S&F in replacement ceiling rose surface Bakelite three terminal complete all as specifiedand directed by Engr-in-Charge. |
| 23 | S&F in replacementcall bell electric, ding dong, AC 240 volt, 50 HZ. complete all as specifiedand directed by Engr-in-Charge. |
| 24 | S&F in replacement flush type electronic fan regulator with 5 step type,100 W, AC 240 Volts, 50 Hzcomplete all as specifiedand directed by Engr-in-Charge. |
| 25 | S&F in replacement MCB, Single Pole, 6 to 32 amps, 240 Volts, 10 KA breaking cap, ‘’B” curvecomplete all as specifiedand directed by Engr-in-Charge. |
| 26 | S&F in replacement MCB, SPN 6 to 32 amps, 415 Volts, 10 KA breaking cap, ‘’B” curve complete all as specifiedand directed by Engr-in-Charge. |
| 27 | S&F in replacement MCB, Four Pole, 40 to 63 amps, 415 Volts complete all as specifiedand directed by Engr-in-Charge. |
| 28 | S&F in replacement MCB distribution board,Double door, metal enclosure, SPN, 230 Volts, 4 way complete all as specifiedand directed by Engr-in-Charge. |
| 29 | S&F in replacement MCB distribution board, Double door, metal enclosure, SPN, 230 Volts, 8 way complete all as specifiedand directed by Engr-in-Charge. |
| 30 | S&F in replacementMCB distribution board, Double door, metal enclosure, SPN, 230 Volts,12 way complete all as specifiedand directed by Engr-in-Charge. |
| 31 | S&F in replacementMCB distribution board, Double door, metal enclosure, TPN, 415 Volts, 4 way complete all as specifiedand directed by Engr-in-Charge. |
| 32 | S&F in repair Vertical MCB distribution board, as MCCB incomer, IP 43 protection, Double door, metal enclosure, TPN, 415 Volts, 4 way complete all as specifiedand directed by Engr-in-Charge.. |
| 33 | S&F in replacement MCCB 415 Volt 4 pole 16 KA 63 Ampscomplete all as specifiedand directed by Engr-in-Charge. Make : Legrand/ABB/Schneider |
| 34 | S&F in replacement MCCB 415 Volt 4 pole 16 KA 125 Ampscomplete all as specifiedand directed by Engr-in-Charge. Make : Legrand/ABB/Schneider |
| 35 | S&F in repair Metal plug and socket board with MCB SP 20 amp, 16 KAcomplete all as specifiedand directed by Engr-in-Charge.Make : Legrand/ABB/Schneider |
| 36 | S&F in replacement Round shapedsurface mounted LED downlighter Aluminium housing 12 watt complete with all fixing accessories and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cablecomplete all as specifiedand directed by Engr-in-Charge. Make : Wipro/Philips/Crompton/Jaquar |
| 37 | S&F in replacementrectangular shaped (4x1)recess/surfacemountedlinearLED Panel light fitting 30 watt, PF > 0.95 230 V complete with all accessories,connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cable complete all as specifiedand directed by Engr-in-Charge. Make : Wipro/Philips/Crompton/Jaquar |
| 38 | S&F in replacement square shaped2\"x2\" recess mounted LED Flat panel,PDC Aluminium housing36 watt suitable for falseceling complete with all fixing accessories and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cable complete all as specifiedand directed by Engr-in-Charge. Make : Wipro/CG/Philips/Jaquar |
| 39 | S&F in replacementLED batten 2 feet long, 10 watt, 230 Volts , complete with all accssories internally pre wired and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cable complete all as specifiedand directed by Engr-in-Charge. Make : Wipro/CG/Philips/Jaquar |
| 40 | S&F in replacementLED Tube light fitting, 20 watt,integrated LED batten With aluminium housing , 230 Volts, 4 feet long , complete with all accssories internally pre wired and including connecting up to ceiling rose with 0.5 sqmm twin core copper flexible conductor cablecomplete all as specifiedand directed by Engr-in-Charge. Make : Wipro/CG/Philips/Jaquar |
| 41 | S&F in replacementLED Bulk head luminaire 10 watt for surface/ wall mounting IP 65 rating 230 Volts, complete including connecting up to ceiling rose with 0.5 sqmm twin core copper flexible conductor cable complete all as specifiedand directed by Engr-in-Charge. Make : Wipro/CG/Philips |
| 42 | S&F in replacement1x18/20watts LED tube Rod with decorative end caps,white powder coated CRCA body 230 Volts, 4 feet long ,internally pre wired and including connecting up to ceiling rose with 0.5 sqmm twin core copper flexible conductor cable complete all as specifiedand directed by Engr-in-Charge. Make : Wipro/CG/Philips/Jaquar |
| 43 | S&F in replacementLED building security light 25 watt, 230V complete with all accessories and including connecting up to ceiling rose with 0.5 sqmm three core copper flexible conductor cablecomplete all as specifiedand directed by Engr-in-Charge. Make : Wipro/Philips/CG/Jaquar |
| 44 | S&F in replacementbldg light bracket made fromGI medium grade pipe 25 mm dia of total length 90 cm,fixed to wall with 2 Nos MS Clamp and anchorfastener complete all as specifiedand directed by Engr-in-Charge. |
| 45 | S&F in replacementLED post top lantern fitting 35 to 40 Watts having IP-65 protection,powder coated aluminium die-cast housing wider light distribution along with opal diffuser for uniform and low glare lightingincluding GI pipe light of suitable dia for mounting of fittingscomplete all as specifiedand directed by Engr-in-Charge.Make : Wipro/CG/Philips/Jaquar |
| 46 | S&F in replacement LED Bollard 10 watt warm white made of extruded aluminium housing having IP65 protection mounting on PCC 1:3:6 of450x450x450mm size complete all as specifiedand directed by Engr-in-Charge. Make : Wipro/CG/Jaquar/Philips |
| 47 | S&F in replacement square shaped recess mounted LED fittingflat panel, 15 watt ,with all fixing accessories and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cable complete all as specifiedand directed by Engr-in-Charge. Make:- Wipro/Philips/CG/Jaquar. |
| 48 | M&L for Rewinding of Ceiling fan 1200 mm/1400 mm sweep after dismenting complete motor assy, bearings, bushings, removal of burnt copper wire, cleaning of core, inserting proper insulating paper in slots, winding with and as per existing size/turn of super enamelled copper wire, heating, vernishing, replacement of unsv bearings / bushings, assemble of rotor and stator unit with capacitor, connecting wire, down rod, blades and testing complete all as specifiedand directed by Engr-in-Charge.Note: 1. Contractor will collect fans from the complaint cells of specified area and bring back to complaint cell after repair. Cost of transportation will be inclusive of quoted rate. 2. Spares require for replacement such as bearing, Bushing, capacitor shall be measured and paid separately as supply & Fixing only.3. Cost of Connector block and capacitor holder shall be inclusive of the quoted rate. |
| 49 | All as per item No.48 above but for Exhaust fan 250/300 mm sweep industrial type complete all as specifiedand directed by Engr-in-Charge. |
| 50 | All as per item No.48 above but for Exhaust fan 450 mm sweep industrial type complete all as specifiedand directed by Engr-in-Charge. |
| 51 | S&F in replacement ball bearing No 6201/6202/6203/6204 complete all as specifiedand directed by Engr-in-Charge.Make -SKF/Tata/NBC. |
| 52 | S&F in replacement G.M. Bush for ceiling fan as per existing pattern complete all as specifiedand directed by Engr-in-Charge. |
| 53 | S&F in replacement capacitor AC for 230 volts 50 Hz of capacity2.5 /2.0 Mfd complete all as specifiedand directed by Engr-in-Charge. |
| 54 | S&F in replacement capacitor AC for 230 volts 50 Hz of capacity 3.15 Mfd complete all as specifiedand directed by Engr-in-Charge. |
| 55 | S&F in replacement capacitor AC for 230 volts 50 Hz of capacity 4.0 Mfd complete all as specifiedand directed by Engr-in-Charge. |
| 56 | M&L for Painting of ceiling fan 1200/1400 mmincluding scrapping, cleaning and removing dust from the blade an body and applying two coat of enamel paint over & one coat of primer complete all as specifiedand directed by Engr-in-Charge. |
| 57 | S&F in replacement exhaust fan 300 mm PVC body with louvres, 230 voltincl dismentling taking down unsv fan any type complete all as specifiedand directed by Engr-in-Charge. Make : Usha/Bajaj/Havells/Crompton . |
| 58 | Description all as per item No.57 above but of size 200mm PVC body |
| 59 | S&F in replacementwallfan 450 mm sweep, 3 speed control ,PVCbody230 voltsincluding dismantling and taking down unsv wall fan complete all as specifiedand directed by Engr-in-Charge. |
| 60 | S&F in replacement exhaust fan 450 mm PVC body with louvres, 230 voltincl dismentling taking down unsv fan any type complete all as specifiedand directed by Engr-in-Charge. Make : Usha/Bajaj/Havells/Crompton . |
| 61 | S&F in replacementPVC insulated PVC sheathed round armoured copper flexible wire multistrand 4 sqmm 3 core, ISI marked complete all as specifiedand directed by Engr-in-Charge. Make : Havells/Finolex/RR Kabel/Polycab |
| 62 | S&F in replacement PVC insulated PVC sheathed round armoured copper flexible wire multistrand 2.5 sqmm 3 core, ISI marked complete all as specifiedand directed by Engr-in-Charge. Make : Havells/Finolex/RR Kabel/Polycab |
| 63 | S&F in replacement thermostat ISI marked suitable for geysers 25 Ltrs to 50 Ltrs Capacity as per sample complete all as specifiedand directed by Engr-in-Charge. |
| 64 | S&F in replacement heating element ISI Marked as per sample round/triangular base, push type or thread type including rubber washers for 1.5/2.0 KWcomplete all as specifiedand directed by Engr-in-Charge. |
| 65 | S&F in replacement heavy duty copper connections pipe with brass hexagonal adaptors at both side 15mm dia and 450mm long for hotwater complete all as specifiedand directed by Engr-in-Charge. |
| 66 | S&F in replacement heavy duty PVC connections pipe with brass hexagonal adaptor both side 15mm dia and 450mm long for cold water complete all as specifiedand directed by Engr-in-Charge. |
| 67 | M & L for PVC insulated, PVC sheathed twin flat core 1100 volts grade, 10 sqmm aluminium stranded conductor (incl wire guard where required)complete all as specified and directed by Engr-in-Charge. Make : Finolex/Polycab/RR cable/Gloster |
| 68 | All as per item No. 67 above but6 sqmm size. |
| 69 | All as sper item No 67 above but4 sqmm size. |
| 70 | S&F in replacement exhaust fan 450 mm ironbody with louvres, 230 voltincl dismentling taking down unsv fan any type all as specified and directed. Make : Usha/Bajaj/Havells/Crompton Note: Old UNSV item Head over to MES Stor Yard |
| 71 | M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 3 mtr longburied directly and vertically in ground with top edge at ground level after making bore hole of size not less than 300 mm dia and 3.0 Mtr long using suitable mechanical drilling rig (for drilling near the specified location), connected with galvanised steel earthing lead of 04 mm all as shown in Plate No-2, connected to the earthing test point, concrete pit in PCC 1:3:6 type C-2 with pit cover, funnel, wiremesh, 32 mm dia light grade GI tubing for protection of GI lead 04mm, charcoal and salt in alternate 150mm thick layers around GI earth pipe, including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including demoliton of old earthing andtesting of new earthingto achieve earth resistance value as per IS specification complete all as specifiedand directed by Engr-in-Charge. |