| Sl. No. | Item Description |
| 1 | Lump sum price worked out by the contractor for \"BUILDING WORKS\"as listed in Schedule ‘A’ Part-I representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum price prepriced by the MES |
| 2 | Lump sum price worked out by the contractor for \"INTERNAL WATER SUPPLY \"as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES |
| 3 | Lump sum price worked out by the contractor for \"INTERNAL ELECTRIFICATION\"as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES |
| 4 | Lump sum price worked out by the contractor for \"ROAD, PATH, CULVERT AND HARD STANDING\"as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES |
| 5 | Lump sum price worked out by the contractor for \"SEWAGE DISPOSAL\"as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES |
| 6 | Lump sum price worked out by the contractor for \"AREA DRAINAGE \"as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES |
| 7 | Lump sum price worked out by the contractor for \"FENCING\"as listed in Schedule ‘A’ Part-VII\" representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceprepriced by the MES |
| 8 | Lump sum price worked out by the contractor for \"EXTERNAL WATER SUPPLY\"as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES |
| 9 | Lump sum price worked out by the contractor for \"EXTERNAL ELECTRIFICATION\"as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES |
| 10 | Lump sum price worked out by the contractor for \" LIGHTING PROTECTION \"as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum price prepriced by the MES |
| 11 | Lump sum price worked out by the contractor for \"FIRE FIGHTING\"as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES |
| 12 | Lump sum price worked out by the contractor for \"LIFT WORK\"as listed in Schedule ‘A’ Part-XII representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES |
| 13 | Lump sum price worked out by the contractor for \"HOT WATER SUPPLY\"as listed in Schedule ‘A’ Part-XIII representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES |
| 14 | Lump sum price worked out by the contractor for \"DG SETS\"as listed in Schedule ‘A’ Part-XIV representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum priceof prepriced by the MES |
| 15 | Lump sum price worked out by the contractor for \"SITE CLEARANCE, SITE DEVELOPMENTAND EARTH WORK\"as listed in Schedule ‘A’ Part-XV representing percentage ( + or - denomination) derived under last column of this schedule above/belowthe lump sum price prepriced by the MES |
| 16 | Sch \"A\" Part-XVI MISC ITEMS (TO BE QUOTED BY CONTRACTOR) Notes:(i) This schedule is not pre-priced by MES and the pre-priced rate indicated as \"Rs 0.00\" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under SCH A PART-XVSITE CLEARANCE, SITE DEVELOPMENTAND EARTH WORK schedule). |
| 17 | INTERNAL WATER SUPPLYS&F for 15mm dia sink mixer (wall mounted) with 150mm long swivel spout,connecting legs and wall flangerswith complete accessories etc complete all as specified and directed.Make: CERA Cat Part No F2014511 / Hindware Cat Part No F690058 / Parryware Cat Part No G3335A1 or equivalent make as mentioned in Appx B. |
| 18 | S&F for 15mm dia single lever center hole basin mixerwith complete accessories etc complete all as specified and directed.Make: CERA Cat Part No F1015451 / Hindware Cat Part No F690012 / Parryware Cat Part No G4863A1 or equivalent make as mentioned in Appx B. |
| 19 | S&F for 15mm dia wall mixture with bend pipe for overhead showerwith complete accessories etc complete all as specified and directed.Make: CERA Cat Part No F2002401 / Hindware Cat Part No F330020 / Parryware Cat Part No G3316A1 or equivalent make as mentioned in Appx B. |
| 20 | INTERNAL ELECTRIFICATIONS&F ofmodular type 3 pin 20 A socket with SP MCB, conforming to IS 1293: 2005as specified in IS 732: 2019 etc complete all as specified and directed |
| 21 | S&F for modular type 1 module RJ-11 telephone socket with shutter etc complete all as specified and directed |
| 22 | S&F for modular type 1 module co-axial type TV socket etc complete all as specified and directed |
| 23 | S & F for 16 A, 230 V, 50 Hz, 2P MCB (\"B\" curve) MCB conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters,IS 732: 2019 etc complete all as specified and directed |
| 24 | S & F for 25 A, 230 V, 50 Hz, 2P MCB (\"B\" curve) MCB conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters,IS 732: 2019 etc complete all as specified and directed |
| 25 | S & F for 32 A, 230 V, 50 Hz, 2P MCB (\"B\" curve) MCB conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters,IS 732: 2019 etc complete all as specified and directed |
| 26 | S & F for 40 A, 230 V, 50 Hz, 2P MCB (\"B\" curve) MCB conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters,IS 732: 2019 etc complete all as specified and directed |
| 27 | S&F forSingle Phase Dual Source Pre Paid Meter, Class 1.0, RS485,10/60A Direct,with followingspecification as under : (i) Communication options:, RS485 and RF(ii)Three in one option:Integrate gas & waterupto 4 DI(iii) Programmable tariff for EB, DG and DI for automatic reduction of balance even server is offline(iv) Configurable Holidays,Happy hours to avoidload switching on Holidays/Night(v) Alarm notifications for low credit balance(vi) Eliminate tenantdisputes, meter tampering & manualtariff reading errors |
| 28 | S&F forThree Phase Dual Source Pre Paid Meter, Class 1.0, RS485, 5A CT operated,with followingspecification as under : (i) Communication options:, RS485 and RF(ii)Three in one option:Integrate gas & waterupto 4 DI(iii) Programmable tariff for EB, DG and DI for automatic reduction of balance even server is offline(iv) Configurable Holidays,Happy hours to avoidload switching on Holidays/Night(v) Alarm notifications for low credit balance(vi) Eliminate tenantdisputes, meter tampering & manualtariff reading errors |
| 29 | S&F of Sheet metal enclosure distribution board VTPN4 way, 415 voltdouble door powder coated, protection class IP-54 isolated neutral bar, mechanical impact strength IK 09 suitable for mounting MCB & MCCB DBs confirming to IS - 13032, IS-8623, BS EN60898 with min 200 Amp rating copper bus bar and grouting, fixing on wall with nut bolts washers proper with PCC works complete all as specified and directed |
| 30 | S&F of Sheet metal enclosure distribution board VTPN6 way, 415 voltdouble door powder coated, protection class IP-54 isolated neutral bar, mechanical impact strength IK 09 suitable for mounting MCB & MCCB DBs confirming to IS - 13032, IS-8623, BS EN60898 with min 200 Amp rating copper bus bar and grouting, fixing on wall with nut bolts washers proper with PCC works complete all as specified and directed |
| 31 | S&F of 160A, 4 pole moulded case circuit breaker (MCCB) with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% = Icu = 16 kA as per IEC 60947-2 and suitable for 3-Phase, 415 V, 50 Hz electric supply etc complete all as specified and directed by engineer-in-charge. |
| 32 | S&F for 12W LED Downlight having Luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hz etc complete all as specified and directed . |
| 33 | S&F for LED light fitting with high 10 watt 220 V AC decorative wall type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size etc complete all as specified and directed . |
| 34 | S&F for 10W LED bulk head light having Luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hz etc complete all as specified and directed. |
| 35 | Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 600 mm sweep. Min air delivery 115 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) etc complete all as specified and directed by engineer-in-charge. |
| 36 | Supply and fix Wall Mounting Fan, steel body AC single Phase, 230V,With Sweep Size, 200mm ; Motor Speed 84CMM, 3 blades, and frame and louvers etc complete all as specified and directed by engineer-in-charge. |
| 37 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type BUILDING PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge.The BUILDING PANEL shall comprise of the following:(A) Bus bar Chamber(i) 01 Set (3L + N) of copper busbar of rated capacity 400A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connections. |
| 38 | (B) Incoming:- (i)320A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 No.(ii) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 No.(iii) LED phase indicators (Red, Yellow, Blue)- 01 Set |
| 39 | (C) Outgoing:-(i)40A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, havingtrip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 08 Nos(ii) LED phase indicators (Red, Yellow, Blue)- 08 Sets |
| 40 | SEWAGE DISPOSALS&F for DWCPE (SN8) 180mm outer dia and 163 inner dia of pipe for depth 0.70mm to 1.65m, laid on 150 mm thick bed (1:4:8)with excavation in any type of soil including manholes/drop manhole of standard sizemade of brick mosonary /RCC/Precast RCC with SFRC ventilating cover and frame,includes all items and activities to execute and make sewer line functionaletc complete all as specified and directed. |
| 41 | S&F for DWCPE (SN8) 200mm outer dia and 175 inner dia of pipe for depth 0.70mm to 1.65m, laid on 150 mm thick bed (1:4:8) with excavation in any type of soil including manholes/drop manhole of standard sizemade of brick mosonary /RCC/Precast RCC with SFRC ventilating cover and frame,includes all items and activities to execute and make sewer line functionaletc complete all as specified and directed. |
| 42 | S&F for DWCPE (SN8) 300mm outer dia and 260 inner dia of pipe for depth 1.65mm to 2.3m, laid on 150 mm thick bed (1:4:8) with excavation in any type of soil including manholes/drop manhole of standard sizemade of brick mosonary /RCC/Precast RCC with SFRC ventilating cover and frame,includes all items and activities to execute and make sewer line functionaletc complete all as specified and directed. |
| 43 | Supply, lay, commissioning, jointing and testing ofcentrifugally cast (spun) ductile iron pipes of 150mm bore class K-7 with spigot and socket ends conforming to IS 8329/2000, IS: 12288 : 1987 code of practice for laying in trenches complete all as specified and directed.Note: The rate quoted by contractor are inclusive of all type of Joints. |
| 44 | S&F forNonclog submersible (sewage disposal), pump set, electric driven 415 Volts 3 Phase 50 Hz, supply comprising of pump with cast iron impellors, submersible motor of suitable capacity, coupling, at discharge 3360 to 480 LPM and minimum discharge should be less than 480 LPM at minimum head 14 m.including chain pully block of two MT capacity 01 Noandsuitable arrangement for hanging the motor through chain of requirement of delivery of pump connected to main pipe line by suitabe HDPE pipe of size 150mm Dia for required length with necessary connection etc all as specified and as directed. |
| 45 | Supply,installing, testingand commissioningout door type LT feeder piller box of suitable size 750X750X450 mm, pedestal mounted, CPRI type test totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with 50 x50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and paintedto both internal and External surfaces with powder coating paint in heatprocess of sheet and suitable for 415 volts, 50 Hz, 3 phase 4 wire system and comprising with and includingfollowing accessories and mounted on PCC Platform made out of100 mm thick PCC (1:3:6),0.45 Mtr all round the panel board etc complete with the following items :- |
| 46 | Incoming:- (i) Copper bus bar made up of copper strip100 amps duly mounted on bakelite insulatorssleevings of standard colour code - 01 Set. (04 No strips for Phases & Neutral)(ii) MCCB TPN 415 Volts,63 Amps, 50 Hz, breaking capacity 25 KA with fixed thermal & magnetic setting ( For Incomming ) - 01 No.Outgoing:-(i) MCB TP 415 volts 32 Amps, breaking capacity 16 KA with fixed thermal & magnetic setting ( For FPB2 ) - 03 Nos(2 nos for pump 1 nos for spare). (ii) FASD Starter for 15 HP Motor with single phase preventer, OLP and dry run protector- 02 Nos |
| 47 | (iii) Analogue type modular volt meterof range 0-500 volts -01 No(iv)Volt meter selector switch-01 No.(v) Analogue typeAmmeter of range 0-200 Amp-01 No(vi) Ammeter selector switch-01 No(set of three)(vii) Indicator lamp with integral circuit (230/240 volt) and cluster LED (Red, Orange, Blue) - 01 set(viii) CT 200/5 Amps - 3 Nos |
| 48 | Supply and FixingDI/CI special fittings of any size,type,radius angle,tapers increasing decreasing sockets,tees,tail piece and collars etc complete upto 200 mm dia etc complete all as specified and directed. |
| 49 | S&F forPVC insulated and sheathed 1100 volts grade flat type submersible 06 sqmm cable three core multi stranded conductor etc complete all as specified and directed . |
| 50 | M&L for Making drill hole by trenchless technologyof suitable size under road for laying pipe line of size150mm bore at 1 metre depth from the road level etc complete all as specified and directed.Note :- Drill hole (trenchless) shall be done without disturbing top surfaces of road by appropriate machine. |
| 51 | M&L for steel gate 5.45 m wide and 2.70 m height with RCC pillar including excavation in any type of soil, plastering, painting, etc complete all as specified and shown in TD/2008/101 sheet No 1/3 to 3/3 |
| 52 | EXTERNAL WATER SUPPLY \"Supply, lay, commissioning, jointing and testing ofcentrifugally cast (spun) ductile iron pipes of 100mm bore class K-9 with spigot and socket ends conforming to IS 8329/2000, IS: 12288 : 1987 code of practice for laying in trenches complete all as specified and directed.Note: The rate quoted by contractor are inclusive of all type of Joints. |
| 53 | Supply, lay, commissioning, jointing and testing ofcentrifugally cast (spun) ductile iron pipes of 150mm bore class K-9 IS: 12288 : 1987 code of practice for laying in trenches complete all as specified and directed.Note: The rate quoted by contractor are inclusive of all type of Joints. |
| 54 | Supply and FixingDI/CI special fittings of any size,type,radius angle,tapers increasing decreasing sockets,tees,tail piece and collars etc complete upto 200 mm dia etc complete all as specified and directed. |
| 55 | Supply and fix CI foot valve with leather washer, ofsize 100 mm , lift and swing, single door, IS 4038 marked one with each pump suction line complete all as specified and directed. |
| 56 | M&L for construction of valve chamber of brick masonry from the top of surface with MS covers 3.15 mm thick and 40x40x6 mm MS angle with hinges for locking arrangement including excavation and earth works PCC (1:3:6) type C2 for foundation PCC bed/coping in cement concrete (1:2:4) type B1, plastering in CM 1:3 painting with two coats of synthetic enamel paint over a coat of red oxide primerfor the size of chamber 1200 mm x 1200 mm x 1200 mm (internal dimention) complete all as specified and directed. |
| 57 | Supply, install,commissioning and testing of Horizontal split case cetrifugal pump set 1450 RPM having an output of minimum 1100 LPM at a head of 45 mtr coupled to 3 phase 415 volt squirel case induction motor of adequate capacity complete all as ditected by Engr-in-charge with and including following :-(a) Necessary cable for interconnection between starter panel & pump set with 1100 volt rated copperinsulated unarmoured cable of minium 10 sqmm 3 core cable(b) Single phase preventer (current sensing type)(c) Necessary light grade GI pipe protection for cabling from pump set to LT panel.(d) Bourden pressure gauge.(e) MS pipe flanged type class B of size 100 mm bore upto foot valve from suction end of pump.(f) PCC foundation in type B-2, 1:2:4 using 20mm graded aggregate, 20cm above ground level and 30cm below grond level including grouting of eye bolts nut etc. for pump set of adequate size or as per manufacturers recommendations.Note: All other items/material requiredfor fixing pumpset shall be included in cost quoted.(ii) Foundation drawing shall be approved by GE/ Eng-In- Charge before fixing the pump set. |
| 58 | Supply, installations, testing and commissioning of factory made LT Indoor cubical typepanel boardhaving 150 Amp rated copper bus bar with neoprene rubber gasket and locking arrangement, dust,weather and verminproof , free standing, floor mounting type self ventilation with wire mesh,totally enclosed busbar chamber fully comparted type, front openable hinged independent door for each compartment with locking arrangement and common openable hinged door from rear side of suitable size made out of 2mm thick CRCA sheet duly painted with seven tank process,415 V,TPN,50Hz both side properly welded MS angular supported with chanel frame of size 50mm,at all vertical corner grouted in PCC 1:3:6 (Type-C1 using 20mm graded stone aggregate) and connecting the incomming/outgoing feeder by providing brass cable glands and Lugs complete all as specified and directed comprising of followings accessories:- |
| 59 | Incoming:- (i) MCCB 4 Pole 100 amps ,415 Volt of breaking capacity not less than 36 KA (Ics=100 % of Icu) with adjustable thermal Setting-01 No.Outgoing:-(i)MCCB 3 Pole 63 amps ,415 Volt of breaking capacity not less than36 KA (Ics=100 % of Icu) with adjustable thermal Setting - 02 Nos (ii) Single phase preventor -02 Nos(iii) On load Change over switch 4 pole of current raring 63 A (open execution type) - 01 No(iv)MCB SPN 10 Amp C curve, 10 KA capacity - 01 No(v) fully automatic Star-delta starter 15 HP or recommended by manufacturer of motor -02 Nos(vi) LED Indicator lamp (R,Y,B)- Set of Three.(vii) Multifunctional meterDigital type showing V,A,F,Pf,KW,KWH inbuilt selector switch with CT coiles for three phase -0 1No. |
| 60 | M&L for construction of header of ERW pipe having size dia 300 mm and length 2.5 m with two inlet connection of size 100 mm & three otlet connection having size 150 mm complete monting on RCC base/plinth etc complete all as specified and as directed by Engr-in-charge. |
| 61 | EXTERNAL ELECTRIFICATIONBoring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine for laying under ground pipe upto 100mm dia complete all as specified and directed.Note :- GI pipe shall be measured and paid separately. |
| 62 | Taking out existing HT XLPE U/G cables, 11000 V grade from trenches/ducts/ poles etc of size 120 Sq. mm 3 Core etccomplete all as specified and directed. |
| 63 | Dismantling and taking down existing transformer mounted on four pole structure and shifting to nearest suitable location including its fixing on newly constructed platform and making all connection, testing as per requirementetccomplete all as specified and directed. |
| 64 | Dismantling and taking down existing 4-pole structure etccomplete all as specified and directed. |
| 65 | Dismantling and taking down existing 03 Nos of LT Panels, refixing at specified locationincluding connecting etc complete all specified and directed. |
| 66 | Taking out existing LT XLPE U/G cables, 1100 V grade from trenches/ducts/ poles etc of size 240 Sq. mm 3.5 Core etc complete all as specified and directed. |
| 67 | Taking out existing LT XLPE U/G cables, 1100 V grade from trenches/ducts/ poles etc of size 185 Sq. mm 3.5 Core etc complete all as specified and directed. |
| 68 | Taking out existing LT XLPE U/G cables, 1100 V grade from trenches/ducts/ poles etc of size upto 95 Sq. mm 3.5 Core etc complete all as specified and directed.Note For item No. 57 to 63 :- The old material obtained from site shall be deposite by contractor in MES store yard without any extra cost as directed by GE. |
| 69 | M&L for construction of plateform of size 3500 x 3500 x 1200mm with brick construction in cement mortar 1:4 PCC (M-10 nominal mix) in foundation, 100mm thick RCC M-25 grade slab, with 8mm MS TMT bars 120mm c/c on bothway, brick masonary steps on one side XPM Jali fixed on angle iron 40x 40x6 mm post upto height of 8 feet above ground level and openable gate with locking arrangment including making provision for entry and exit of HT/LT cables and steps made to access to the top of plateform including plastering to bricks masonary complete including painting with 2 coats of whitewash on plastered surface and painting steel surface with 2 coats of red oxide primeretc complete all as specified and directed. |
| 70 | Supply & fix HT 11 KV, outdoor type gang operated air-break switch suitable for horizontal or vertical mounting rotating type complee with drop out fuse having 12 insulators of rating upto 200 Amps etc complete all as specified and directed. |
| 71 | Supply and fixing lightning arrestor HT 11 KV, 10 KA station class etc complete all as specified and directed. |
| 72 | Supply & errect 2 pole structure on 11 mtr PCC pole consisting of pole with anti-climbing device, PCC foundation & cross arms (Bracings) etc for one incoming and one out going. etc complete all as specified and directed. |
| 73 | Supply, installation, testing & commissioning of package type/unitised 11kV / 433 V Outdoor sub-station (CSS) ,315KVA made from G. I. enclosure complete as required conforming to IEC 62271-202 only and relevant IS specifications including K-10 Temperature Class as applicable for the rating, Internal Arc of 21 KA/1 Sec. IAC AB on 1:2:4 (1 cement :2 cores and : 4 Graded stone aggrregate of 40 mm nominal size) PCC foundation of suitable size extending 500 mm all around the outdoor enclosure and 1000 mm height (above ground level) complete with suitable sizes of GI Pipes for incoming/outgoing cables/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 40x40x5mm NS all along the corner of the foundation CSS shall be from OEMs only . Licensed System Integrators of approved OEM are not allowed to supply .Package substation will have the following equipment :- |
| 74 | HT SWITCHGEAR11kV 630Amps 21KA/3 sec. Non-Extensible Ring Main Unit Compact switchgear consisting of1 no. fixed motorized Vacuum Circuit Breaker Moduleand 2 nos. fixed morotized Load break switch module in SF6 insulated stainless steel enclosure with series trip, self powered microprocessor based numerical over current and earth fault relay protection. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. Interconnection between HT Switchgear and primary of transformer shall be done through 1C x 3R x 95 sq.mm Aluminium XLPE cable. - 1 No.Vacuum Interrupter,RMU,LT Switchgear and CSS Enciosure shall be of same make to ensure life cycle optimization.(i)Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil (Modbus RS485 complaint)(ii)Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder.(iii)SF6 Gas pressure indicator.(iv)Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO(v)Protection CT shall be minimum 40/1A ,2.5VA ,5P10. - 3 Nos |
| 75 | (vi)All modules of the RMU shall be suitable for cable termination of 3C x 300 sq.mm Al XLPE Cable, incoming cable termination is included within the scope of work - 1 SetTRANSFORMER315 KVA 11KV/433V DYN-11 Oil type, hermetically sealed energy efficiency level-2 transformer (BEE Star Rated-2) with corrugated wall, without conservator, type of design & Top Bushings for HT & LT with Off load tap switch of rating +5% to -5% @2.5%. Temp Rise - Oil/Winding 40/45 Deg cel. Losses (As per IS-1180 amended up to date)Max Losses @ 50% Load 955W and Max Losses @ 100% Load 2750 KW and Impedance of 4.5% (Subject to IS Tolerance (as per IS1180-2014) The transformer shall be conforming to IS: 2026 and IS: 1180(part-I). amended up to date. (i)01 No. Winding Temperature Indicator with Alarm and trip Contact.LT PANELLVS PANEL 500 AMPS 4 pole Aluminium BUSBAR (100% FOR PHASES AND 100% FOR NEUTRAL) - CURRENT DENSITY OF Aluminum as 1 A/sq.mm. ; LT panel made up of 1.5/2 mm thick CRCA sheet INCOMER CUM OUTGOINGS FROM TRANSFORMER(i)500 Amps 433V 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB)(ii) Multifunction meter with Modbus RS485 port & class 0.5 accuracy with Suitable CT. - 1 set |
| 76 | (iii)Hard wiring from each equipment inside CSS for scada connectivity (monitoring & control)to be brought to one set of TBs and a space for FRTU to be given. Supply of FRTU is not in scope. (iv)All Civil works such as PCC/RCC foundation, Plateform, Filling trench and pedestal etc as per CSS manufacturer\"s recomandation are included in scope of work.OUTDOOR ENCLOSUREOutdoor type encloser of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of Galvanised Sheet Steel in suitable design for better heat dissipation and providing robust. |
| 77 | construction. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure exterior shall be painted with epoxy based powder paint (colour RAL 7032). Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitablly handling any arcing inside the compartment for providing better safety to the operator. The compartment illumination lamp with door operated switch shall be provided for each compartment.Vacuum Interrupter,RMU,LT Switchgear, Multifunction meterand CSS Enciosure shall be of same make to ensure life cycle optimization. |
| 78 | Supply, installation, testing & commissioning of package type/unitised 11kV / 433 V Outdoor sub-station , (CSS) 400KVA made from G. I. enclosure complete as required conforming to IEC 62271-202 only and relevant IS specifications including K-10 Temperature Class as applicable for the rating, Internal Arc of 21 KA/1 Sec. IAC AB on 1:2:4 (1 cement :2 cores and : 4 Graded stone aggrregate of 40 mm nominal size) PCC foundation of suitable size extending 500 mm all around the outdoor enclosure and 1000 mm height (above ground level) complete with suitable sizes of GI Pipes for incoming/outgoing cables/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 40x40x5mm NS all along the corner of the foundation CSS shall be from OEMs only . Licensed System Integrators of approved OEM are not allowed to supply.Package substation will have the following equipment :-HT SWITCHGEAR11kV 630Amps 21KA/3 sec. Non-Extensible Ring Main Unit Compact switchgear consisting of1 no. fixed motorized Vacuum Circuit Breaker Moduleand 2 nos. fixed morotized Load break switch module in SF6 insulated stainless steel enclosure with series trip, self powered microprocessor based numerical over current and earth fault relay protection. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the |
| 79 | RMU to OEM Works. Interconnection between HT Switchgear and primary of transformer shall be done through 1C x 3R x 95 sq.mm Aluminium XLPE cable. - 1 No.Vacuum Interrupter,RMU,LT Switchgear and CSS Enciosure shall be of same make to ensure life cycle optimization.(i)Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil (Modbus RS485 complaint)(ii)Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder.(iii)SF6 Gas pressure indicator.(iv)Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO(v)Protection CT shall be minimum 40/1A ,2.5VA ,5P10. - 3 Nos.(vi)All modules of the RMU shall be suitable for cable termination of 3C x 300 sq.mm Al XLPE Cable, incoming cable termination is included within the scope of work - 1 Set |
| 80 | TRANSFORMER400 KVA 11KV/433V DYN-11 Oil type, hermetically sealed energy efficiency level-2 transformer (BEE Star Rated-2) with corrugated wall, without conservator, type of design & Top Bushings for HT & LT with Off load tap switch of rating +5% to -5% @2.5%. Temp Rise - Oil/Winding 40/45 Deg cel. Losses (As per IS-1180 amended up to date)Max Losses @ 50% Load 1150W and Max Losses @ 100% Load 3330 KW and Impedance of 4.5% (Subject to IS Tolerance (as per IS1180-2014) The transformer shall be confirming to IS: 2026 and IS: 1180(part-I). amended up to date. (i)01 No. Winding Temperature Indicator with Alarm and trip Contact.LT PANELLVS PANEL 630 AMPS 4 pole Aluminium BUSBAR (100% FOR PHASES AND 100% FOR NEUTRAL) - CURRENT DENSITY OF Aluminum as 1 A/sq.mm. ; LT panel made up of 1.5/2 mm thick CRCA sheet INCOMER CUM OUTGOINGS FROM TRANSFORMER(i)630 Amps 433V 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB) (ii) Multifunction meter with Modbus RS485 port & class 0.5 accuracy with Suitable CT. - 1 set |
| 81 | (iii)Hard wiring from each equipment inside CSS for scada connectivity (monitoring & control)to be brought to one set of TBs and a space for FRTU to be given. Supply of FRTU is not in scope. (iv)All Civil works such as PCC/RCC foundation, Plateform, Filling trench and pedestal etc as per CSS manufacturer\"s recomandation are included in scope of work.OUTDOOR ENCLOSUREOutdoor type encloser of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of Galvanised Sheet Steel in suitable design for better heat dissipation and providing robustconstruction. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure exterior shall be painted with epoxy based powder paint (colour RAL 7032). Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitablly handling any arcing inside the compartment for providing better safety to the operator. The compartment illumination lamp with door operated switch shall be provided for each compartment.Vacuum Interrupter,RMU,LT Switchgear, Multifunction meterand CSS Enciosure shall be of same make to ensure life cycle optimization. |
| 82 | Supply, installations, testing and commissioning factory made out door cubical typeLT panel board dust and verminproof , free standing, floor mounting type mounted on and incluidng1:3:6 PCC foundation as requried at site and of fabricated by 3.0mm thick CRCA Sheet over MS 50 X 50 x 6 mm thick angle iron frameof requriedtype for support with double door both sides open type with necessarylockingarrangement with sloppedroof on top duly paintedwith two coatsof powder coated semense gray paint complete and having separatedoors inside for accomodatingall incomming / outgoing feeders of suitable sizes all as specified and directedby Engr-in- Charge(Panel 1 - Near mains transformer GTC Area):- |
| 83 | INCOMING :-(i) S&F ACB 4 Pole 630 amps ,415 Volt electrical drawout type of breaking capacity not less than50 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 01 Nos Incommer.(ii) Aluminium electrolite Busbar 750 Amps current rating duly sleev insulated for set of 3 phase, 4 wire system and branch connection of suitable size of outgoing current rating of MCB/MCCBsOUTGOING:-(i) S&F MCCB 4 Pole 315 amps ,415 Volt of breaking capacity not less than16 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 01 No (for LT distribution panels of block )(ii) S&F MCCB 4 Pole 200 amps ,415 Volt of breaking capacity not less than16 KA (Ics=100 % of Icu) with adjustable thermal Setting (Optium 2.0) -02 Nos(for LTP Pump Motor, lift, fire fighting, stree light etc + spare).(iii)Digital Ammeter 0-500 A with selector switch & CTs of suitable capacity - 01 set.(ivDigital volt meter 0-400 V with selector switch - 01 No.(v)LED Indicating Lamps R,Y,B - 01 Set of three |
| 84 | Supply, installations, testing and commissioning factory made out door cubical typeLT panel board dust and verminproof , free standing, floor mounting type mounted on and incluidng1:3:6 PCC foundation as requried at site and of fabricated by 3.0mm thick CRCA Sheet over MS 50 X 50 x 6 mm thick angle iron frameof requriedtype for support with double door both sides open type with necessarylockingarrangement with sloppedroof on top duly paintedwith two coatsof powder coated semense gray paint complete and having separatedoors inside for accomodatingall incomming / outgoing feeders of suitable sizes all as specified and directedby Engr-in- Charge:- (Panel 2 - Near Chambal Vihar Main Tfr Panel):-INCOMING :-(a) S&F MCCB 4 Pole 500 amps ,415 Volt of breaking capacity not less than36 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 01 Nos Incommer.(b) Aluminium electrolite Busbar 600 Amps current rating duly sleev insulated for set of 3 phase, 4 wire system and branch connection of suitable size of outgoing current rating of MCB/MCCBs |
| 85 | OUTGOING:-(i) S&F MCCB 4 Pole 250 amps ,415 Volt of breaking capacity not less than25 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 01 No (for LT distribution panels of blocks)(ii) S&F MCCB 4 Pole 160 amps ,415 Volt of breaking capacity not less than25 KA (Ics=100 % of Icu) with adjustable thermal Setting (Optium 2.0) -02 Nos(for LTP Pump Motor, lift, fire fighting, stree light etc + spare).(iii)Street light timer using Power contactor 32 Amps, (1-NO) 3 pole, 415Volt, DIN Type digital programable time switch 230V AC, Auto/Manual selector switch, MCB 4 pole 25 Amps C-range, ON/OFF indicator all prewired and making provision for fixing outgoing cables- 01 Set complete.(iv)Digital Ammeter 0-500 A with selector switch & CTs of suitable capacity - 01 set.(v)Digital volt meter 0-400 V with selector switch - 01 No.(vi)LED Indicating Lamps R,Y,B - 01 Set of three |
| 86 | Supply, installations, testing and commissioning factory made out door cubical typeLT panel board dust and verminproof , free standing, floor mounting type mounted on and incluidng1:3:6 PCC foundation as requried at site and of fabricated by 3.0mm thick CRCA Sheet over MS 50 X 50 x 6 mm thick angle iron frameof requriedtype for support with double door both sides open type with necessarylockingarrangement with sloppedroof on top duly paintedwith two coatsof powder coated semense gray paint complete and having separatedoors inside for accomodatingall incomming / outgoing feeders of suitable sizes all as specified and directedby Engr-in- Charge:- (Panel 1A - LT PANEL FOR 3 X BLOCKS GTC):-INCOMING :-(i) S&F MCCB 4 Pole 315 amps ,415 Volt of breaking capacity not less than36 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 01 Nos Incommer.(ii) Aluminium electrolite Busbar 400 Amps current rating duly sleev insulated for set of 3 phase, 4 wire system and branch connection of suitable size of outgoing current rating of MCB/MCCBs |
| 87 | OUTGOING:-(i) S&F MCCB 4 Pole 125 amps ,415 Volt of breaking capacity not less than25 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 04 No (for 3 X Blocks+spare)(ii) Digital Ammeter 0-500 A with selector switch & CTs of suitable capacity - 01 set.(iii)Digital volt meter 0-400 V with selector switch - 01 No.(iv)LED Indicating Lamps R,Y,B - 01 Set of three |
| 88 | Supply, installations, testing and commissioning factory made out door cubical typeLT panel board dust and verminproof , free standing, floor mounting type mounted on and incluidng1:3:6 PCC foundation as requried at site and of fabricated by 3.0mm thick CRCA Sheet over MS 50 X 50 x 6 mm thick angle iron frameof requriedtype for support with double door both sides open type with necessarylockingarrangement with sloppedroof on top duly paintedwith two coatsof powder coated semense gray paint complete and having separatedoors inside for accomodatingall incomming / outgoing feeders of suitable sizes all as specified and directedby Engr-in- Charge:- (Panel 2A - LT PANEL FOR 2 X BLOCKS CHAMBAL VIHAR):-INCOMING :-(i) S&F MCCB 4 Pole 250 amps ,415 Volt of breaking capacity not less than36 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 01 Nos Incommer.(ii) Aluminium electrolite Busbar 400 Amps current rating duly sleev insulated for set of 3 phase, 4 wire system and branch connection of suitable size of outgoing current rating of MCB/MCCBs |
| 89 | OUTGOING:-(i) S&F MCCB 4 Pole 125 amps ,415 Volt of breaking capacity not less than25 KA (Ics=100 % of Icu) with Adjustable TM Range (Optium 2.0) - 03 No (for 3 X Blocks+spare)(ii) Digital Ammeter 0-500 A with selector switch & CTs of suitable capacity - 01 set.(iii)Digital volt meter 0-400 V with selector switch - 01 No.(iv)LED Indicating Lamps R,Y,B - 01 Set of three |
| 90 | Supply, installations, testing and commissioning factory made out door cubical typeLT panel board dust and verminproof , free standing, floor mounting type mounted on and incluidng1:3:6 PCC foundation as requried at site and of fabricated by 3.0mm thick CRCA Sheet over MS 50 X 50 x 6 mm thick angle iron frameof requriedtype for support with double door both sides open type with necessarylockingarrangement with sloppedroof on top duly paintedwith two coatsof powder coated semense gray paint complete and having separatedoors inside for accomodatingall incomming / outgoing feeders of suitable sizes all as specified and directedby Engr-in- Charge:- (Panel 1B & 2B):-INCOMING :-(i) S&F MCCB 4 Pole 200 amps ,415 Volt of breaking capacity not less than25 KA (Ics=100 % of Icu) with Adjustable TM Range-01 No incoming.(ii) Aluminium Electrolite Busbar 300Amps current rating duly sleev insulated for set of 3 phase, 4 wire system and branch connection of suitable size of outgoing current rating of MCB/MCCBs-01Set |
| 91 | OUTGOING:-(i) MCCB 4 pole 63 Amp, 415 V, 16 KA, C-series. - 01 Nos (for PH Panel)(ii) MCCB 4 pole 40 Amp, 415 V, 16 KA, C-series- 02 Nos (sewage PH +spare).(iii) MCB TPN 25Amp, 230 V, 10 KA, C-series - 07 Nos (Lifts+fire fighting+Street lights)(iv)Street light timer using Power contactor 25 Amps, (1-NO) 3 pole, 415Volt, DIN Type digital programable time switch 230V AC, Auto/Manual selector switch, MCB 4 pole 25 Amps C-range, ON/OFF indicator all prewired and making provision for fixing outgoing cables- 01 Set complete.(v) Digital Ammeter 0-150 A with selector switch & CTs of suitable capacity - 01 set.(vi) Digital volt meter 0-500 V with selector switch - 01 No. (vii) On load Change over switch 4 pole of current raring 63-100 A (open execution type) - 01 No.(viii)LED Indicating Lamps R,Y,B - 01 Set of three |
| 92 | Supply, installations, testing and commissioning factory made out door cubical typeLT panel board dust and verminproof , free standing, floor mounting type mounted on and incluidng1:3:6 PCC foundation as requried at site and of fabricated by 3.0mm thick CRCA Sheet over MS 50 X 50 x 6 mm thick angle iron frameof requriedtype for support with double door both sides open type with necessarylockingarrangement with sloppedroof on top duly paintedwith two coatsof powder coated semense gray paint complete and having separatedoors inside for accomodatingall incomming / outgoing feeders of suitable sizes all as specified and directedby Engr-in- Charge:- (Panel D - DOE Area):-INCOMING :-(i) S&F MCCB 4 Pole 100 amps ,415 Volt of breaking capacity not less than16 KA (Ics=100 % of Icu) with adjustable thermal Setting (Optium 2.0)-01 No incoming.(ii) Aluminium Electrolite Busbar 150 Amps current rating duly sleev insulated for set of 3 phase, 4 wire system and branch connection of suitable size of outgoing current rating of MCB/MCCBs-01Set |
| 93 | OUTGOING:-(i) MCCB 4 pole 63 Amp, 415 V, 16 KA, C-series - 02 Nos (for Bldg + Spare)(ii) MCB SPN 10 Amp, 415 V, 10 KA, C-series - 02 Nos (Garages + Spare).(iii) MCB SPN 10 Amp, 230 V, 10 KA, C-series - 02 Nos (Security light + Spare)(iv) Digital Ammeter 0-150 A with selector switch & CTs of suitable capacity - 01 set.(v) Digital volt meter 0-500 V with selector switch - 01 No.(vi)LED Indicating Lamps R,Y,B - 01 Set of three |
| 94 | M&L for factory made busbar box 750 Amps rated Aluminium busbar, 3 phase, 4 wire, 415 Volt of size not less than 300mm x 200mm x 100mm, fabricated using 1.6mm MS sheet, duly painted with smoke gray powder coated over a coat of red oxide primer suitable for fixing on wal by using wall fastners 10mm dia and making necessary incomming and outgoing connection of electric cables using aluminium lugs etc complete all as specified and diected. |
| 95 | M&L for factory made busbar box 600 Amps rated Aluminium busbar, 1 phase, 245 Volt, size not less than 200mm x 150mm x 100mm, fabricated using 1.6mm MS sheet, duly painted with smoke gray powder coated over a coat of red oxide primer suitable for fixing on wall by using wall fastners 10mm dia and making necessary incomming and outgoing connection of electric cables using aluminium lugs etc complete all as specified and diected. |
| 96 | Supply and fixing poly carbonatejunction box , weather and vermin proof of size 250X250X160 including provn of 4 Nos aluminium strip 25x3.15 mm size bus bar single phase and neutral suitabely mounted on bus bar insulators ,including one No. MCB SP 6 Amps for light control,drilling of holes.Provn of suitable size of GI nuts, bolts, double washer and FI clamps ofsuitable sizefor taking connections and fixing on LT steel tubular poles complete with locking arrangementcomplete all as specified and directed. |
| 97 | Supply and connecting three core cord flexible wire, copper conductor multistranded, PVC insulated and overall PVC sheathed of size 1.5Sqmm 1100 Volt , draw through LT steel tubular polesfor connection to street light from junction boxetc complete all as specified & directed. |
| 98 | S&F for Cable route indicator, duly engraved with \"LT CABLE 1100 VOLT\" on cast iron round plate 150 mm dia with provision of 500 mm long (minimum) single leg/stand of flat iron 40 x 5 mm, welded/riveted on back side of plate, fixed and grouted in position with PCC 1:3:6 type C-1, block of suitable size etc complete all as specified & directed. |
| 99 | M&L for Precast PCC (1:2:4) type B-1 cable path indicators of size 300x100x500mm rounded top having engraved in capital letters \"HT Cable\" embedded in position in PCC(1:3:6) Type C-1, using necessary formwork and including provision of two coats of cement base paint on exposed concrete surface and writing HT Cable in black synthetic enamel paint etc complete all as specified & directed. |
| 100 | M&L fordecorative LED post top lantern (PTL) luminior with die cast aluminium spigot, spun aluminium powder coated top cover clear/opal acralic difusser LED light fitting of 25 watts including LED lamp etc complete all as specified & directed. |
| 101 | M& L for shifting of 33 KV HT cable to a safe distance from proposed building, supply, laying, testing & commisioning of 33 KV cable in replacement with new as per estimate provided by State electricity deptetc etc complete all as specified & directed. |
| 102 | FIRE FIGHTINGS&F forAutomatic air release valve 50mm dia suitable for domestic water with 25mm gun metal stop valveetc complete all as specified & directed. |
| 103 | S&F forbranch pipe with nozzle of 20mm dia for hose reel conforming to IS 8090etc complete all as specified and directed. |
| 104 | S&F forfix Valve, stop, screwed, 25 mmdia pipeetc complete all as specified and directed. |
| 105 | S&F for6 kg capacity Multipurpose dry chemical powder (ABC) type(IS-15683) fire extinguishers consisting of welded MS cylindrical body fabricated from 1.6 mm MS sheet internally protected with anticorrosive treatment and hydraucally tested. Extinguisher externally painted with red enamel and fixed to wall with bracket complete with initial filled/charged .etc complete all as specified and directed. |
| 106 | S&F forCO2 type fire extinguisher of 3 Kgs capacity with steel cylinder with a discharge valve and confirming to IS : 15683.Extinguisher shall be painted with red enamel apint and fixed to wall with bracket etc complete all as specified and directed. |
| 107 | S&F for9 Ltr capacity Foam type(IS-15683) fire extinguishers consisting of welded MS cylindrical body fabricated from 1.6 mm MS sheet internally protected with anticorrosive treatment and hydraucally tested. Extinguisher externally painted with red enamel and fixed to wall with bracket complete with initial filled/chargedetc complete all as specified and directed. |
| 108 | S&F fortesting of Star-Delta starter Panel for fire fighting pump motor etc complete all as specified and directed. |
| 109 | Supply, installation, testing & commissioning ofFIRE SIGNAGES for indication/information of fire exit, alarm panel, fire extinguishers fire axe, hose reel, hydrents, lifts of size 300mmx100mm etc complete all as specified and directed. |
| 110 | DG SETSSupply, installation, commissioning and testing complete of Manufacturer of OEM (Original Eqpt Manufacturer) manufactured and tested static Diesel Engine driven generating set capable of delivering 180 KVA continuous rating, (10% overload for 1 hour in 12 hours of operation), 415 volts (AC 3 phase, 4 wire system of supply), 50 Hz at power factor 0.8 minimum. The DG set shall consist of a diesel engine coupled directly to a matching alternator, and mounted on Dunlop metallastik foundation pads on a common base frame and thereafter installed in the CPCB approved acoustic enclosure complete with control panel standardised by manufacturer, fuel tank with mounting arrangement and inlet, outlet, return oil arrangement, flexible exhaust pipe complete all as specified and directed and shall include comprise of the following :- |
| 111 | (A) Engine (prime mover) : Diesel engine 1500 RPM, of suitable HP as recommended by manufacturer, water cooled, turbocharged, 12 volts electric battery start, complete with fly wheel and torsional vibration damper, rediator and all standard fittings/fixtures as per standard manufacturing practices and including suitable instrument panel with RPM meter, lub oil temp and pressure gauge, water temp gauge and frequency meter (digital type), battery charging ammeter and fuses, and also including self starter (12V), battery charging alternator, fuel tank etc and complete with HWT and LLOP alarm and shut down safeties complete with first fill of Lub oil and Coolent. (B) Alternator : AC alternator, brushless, 415V AC 50 Hz, 3 phase, 4 wire type, rated for continuous output of 63 KVA, PF 0.8 (lag), 1500 RPM insulation class \"H\"; enclosure SPDP (IP 22/23), self excited & self regulated with AVR for + 1% voltage regulation, coupled directly/suitably to and to match the above engine and conforming to BS 5000/IS 4722. |
| 112 | (C) Dunlop Metallastik anti-vibration of pads for mounting engine - alternator assembly on the base frame/plate.(D) Base plate : Made out of structural steel as per manufacturer\"s recommended design/specifications.\"(E) Enclosure : Provision of an integral type, approved/certified acoustic enclosure as per latest CPCB norms, for the DG set to restrict the noise level to 75 DB (A) at one metre and ensure that temperature rise within the canopy shall not exceed 5 - 7 degree celsius, It shall be made of 16 SWG CRCA MS sheet with powder-coated finish on outside and high quality noise absorbent and fire retardant grade acuoustic insulation material duly provided with EPDN gasket lining. There shall be four hinged doors out of which one shall be with a glass window.(i)Silencer : Absorption type, non-resistance, residential.(ii) Internal wiring with PVC copper conductor cables, IS 694 marked, FRLS in conduit and suitable light fittings.(iii)Fuel tank to be provided as per OEM specificaton.(iv)Safeties for high enclosure temperature and emergency shut-down from outside.(v) 1No 12V of suitable AH lead acid batteries and adequate size copper conductor cable leads, housed on & including suitable size MS angle iron frame and necessary clamps, nuts, bolts, washers all as required & as per manufacturer design/specifications.(F) Control panel : Control panel made out of 14 gauge CRCA sheet, powder coated and shall consists of the following: - |
| 113 | (i) Ps 0500 Controller (ii) Aluminium Bus bars with suitable capacity incoming & outgoing terminals.(iii) Indicating lamps for load on and \"set running\" (iv) Instrument fuses duly wired and ferruled. (v) Circuit breaker(MCCB) of suitable rating with overload and short circuit protections. Note: To be mounted inside enclosure. (G) Automatic mains failure (AMF) control panel fabricated from CRCA sheet steel of thickness not less than 3.15 mm, suitable for outdoor installation (including CPRI type test certified), dust & vermin proof, protection class I P-54 suitable for 415 volts, 3 phase, 4 wire, 50 Hz, AC supply system with adequate layers of power coating floor mounting type with front opening, the AMF panel shall comprise the following indicating instruments & switches:- |
| 114 | AC voltmeter - 01NoVoltmeter selector switch OFF/RY/YB/BR - 01NoFrequency meter - 01NoAC voltmeter of suitable scale - 01NoAmmeter selector switch OFF/R/Y/B - 01NoCurrent transformers of suitable ratio - 01NoBattery charger consisting of - 01No(aa) Transformer / Rectifier unit (bb) DC ammeter /DC voltmeter(cc) Charging rate selector switch OFF/Trickle/BoostMains supply air break contactor, 3 pole of suitable raing - 01NoAlternator air break contactor, 3 pole of suitable rating and provided with a separate overload relay for overload protection - 01NoMains supply voltage monitor - 01NoSet of DC control relays and timers - 01NoSet of push buttons, START, STOP, ACKNOWLEDGE, RESET, MAINS BREAKER, CLOSE/TRIP, ALTERNATOR BREAKER CLOSE / TRIP - 01No |
| 115 | 01 Set of indicating lamps for the following :-LOAD ON MAINS, LOAD ON SET, SET FAILS TO START, LOW OIL PRESSURE, HIGH TEMPERATURE ALARM, HIGH TEMPERATURE TRIP, ALTERNATOR OVERLOAD.Audio - alarm hooter - 01NoKWH meter - One Set of Bus bars - 01NoThe control cubicle will be furnished complete with the necessary control circuit fuses, etc. and will have provisions for making incoming and outgoing connections.KW meter - 01Noset of bus bar - 01NoThe control cubical will be furnished complete with the necessary control circuit fuse etc and will have provision for making incoming and outgoing connectionsOne - set of bus bar - 01NoThe control cubicle will be furnished complete with the necessary control circuit fuses, etc. and will have provisions for making incoming and outgoing connections.Note :(i) In case AMF panel included instead of Standard Control Panel, then Battery charging alternator with inbuilt regulator and battery charging ammeter should be deleted from engine specifications since Battery charger included under AMF Panel specifications. |
| 116 | (ii) Platform : PCC foundation /plinth/baseshall be provided as per drawing No: TD/2010/109, Sheet No 1/1.(iii) Tool kit, Operation and Maintenance catalogue, 1 year spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacturer standard practices. |
| 117 | Supply, installation, commissioning and testing complete of Manufacturer of OEM (Original Eqpt Manufacturer) manufactured and tested static Diesel Engine driven generating set capable of delivering 125 KVA continuous rating, (10% overload for 1 hour in 12 hours of operation), 415 volts (AC 3 phase, 4 wire system of supply), 50 Hz at power factor 0.8 minimum. The DG set shall consist of a diesel engine coupled directly to a matching alternator, and mounted on Dunlop metallastik foundation pads on a common base frame and thereafter installed in the CPCB approved acoustic enclosure complete with control panel standardised by manufacturer, fuel tank with mounting arrangement and inlet, outlet, return oil arrangement, flexible exhaust pipe complete all as specified and directed and shall include comprise of the following :- |
| 118 | (A) Diesel engine 1500 RPM, of suitable HP as recommended by manufacturer, water cooled, turbocharged, 12 volts electric battery start, complete with fly wheel and torsional vibration damper, rediator and all standard fittings/fixtures as per standard manufacturing practices and including suitable instrument panel with RPM meter, lub oil temp and pressure gauge, water temp gauge and frequency meter (digital type), battery charging ammeter and fuses, and also including self starter (12V), battery charging alternator, fuel tank etc and complete with HWT and LLOP alarm and shut down safeties complete with first fill of Lub oil and Coolent. (B) Alternator : AC alternator, brushless, 415V AC 50 Hz, 3 phase, 4 wire type, rated for continuous output of 63 KVA, PF 0.8 (lag), 1500 RPM insulation class \"H\"; enclosure SPDP (IP 22/23), self excited & self regulated with AVR for + 1% voltage regulation, coupled directly/suitably to and to match the above engine and conforming to BS 5000/IS 4722. (C)Dunlop Metallastik anti-vibration of pads for mounting engine - alternator assembly on the base frame/plate. |
| 119 | (D) Base plate : Made out of structural steel as per manufacturer\"s recommended design/specifications.(E) Enclosure : Provision of an integral type, approved/certified acoustic enclosure as per latest CPCB norms, for the DG set to restrict the noise level to 75 DB (A) at one metre and ensure that temperature rise within the canopy shall not exceed 5 - 7 degree celsius, It shall be made of 16 SWG CRCA MS sheet with powder-coated finish on outside and high quality noise absorbent and fire retardant grade acuoustic insulation material duly provided with EPDN gasket lining. There shall be four hinged doors out of which one shall be with a glass window.(i)Silencer : Absorption type, non-resistance, residential.(ii) Internal wiring with PVC copper conductor cables, IS 694 marked, FRLS in conduit and suitable light fittings.(iii)Fuel tank to be provided as per OEM specificaton.(iv)Safeties for high enclosure temperature and emergency shut-down from outside.(v) 1Nos 12V of suitable AH lead acid batteries and adequate size copper conductor cable leads, housed on & including suitable size MS angle iron frame and necessary clamps, nuts, bolts, washers all as required & as per manufacturer design/specifications. |
| 120 | (F) Control panel : Control panel made out of 14 gauge CRCA sheet, powder coated and shall consists of the following: - (i) Ps 0500 Controller (ii) Aluminium Bus bars with suitable capacity incoming & outgoing terminals.(iii) Indicating lamps for load on and \"set running\"(iv) Instrument fuses duly wired and ferruled. (v) Circuit breaker(MCCB) of suitable rating with overload and short circuit protections. Note: To be mounted inside enclosure. (G) Automatic mains failure (AMF) control panel fabricated from CRCA sheet steel of thickness not less than 3.15 mm, suitable for outdoor installation (including CPRI type test certified), dust & vermin proof, protection class I P-54 suitable for 415 volts, 3 phase, 4 wire, 50 Hz, AC supply system with adequate layers of power coating floor mounting type with front opening, the AMF panel shall comprise the following indicating instruments & switches:- AC voltmeter -01 NoVoltmeter selector switch OFF/RY/YB/BR - 01 No |
| 121 | Frequency meter - 01 NoAC voltmeter of suitable scale - 01 NoAmmeter selector switch OFF/R/Y/B - 01 NoCurrent transformers of suitable ratio - 01 NoBattery charger consisting of - 01 No(aa) Transformer / Rectifier unit (bb) DC ammeter /DC voltmeter(cc) Charging rate selector switch OFF/Trickle/BoostMains supply air break contactor, 3 pole of suitable raing - 01 NoAlternator air break contactor, 3 pole of suitable rating and provided with a separate overload relay for overload protection - 01 NoMains supply voltage monitor - 01 NoSet of DC control relays and timers - 01 NoSet of push buttons, START, STOP, ACKNOWLEDGE, RESET, MAINS BREAKER, CLOSE/TRIP, ALTERNATOR BREAKER CLOSE / TRIP - 01 No01 Set of indicating lamps for the following :-LOAD ON MAINS, LOAD ON SET, SET FAILS TO START, LOW OIL PRESSURE, HIGH TEMPERATURE ALARM, HIGH TEMPERATURE TRIP, ALTERNATOR OVERLOAD.Audio - alarm hooter - 01NoKWH meter - One Set of Bus bars - 01NoThe control cubicle will be furnished complete with the necessary control circuit fuses, etc. and will have provisions for making incoming and outgoing connections. |
| 122 | KW meter - 01Noset of bus bar - 01NoThe control cubical will be furnished complete with the necessary control circuit fuse etc and will have provision for making incoming and outgoing connectionsOne - set of bus bar - 01NoThe control cubicle will be furnished complete with the necessary control circuit fuses, etc. and will have provisions for making incoming and outgoing connections.Note :(i) In case AMF panel included instead of Standard Control Panel, then Battery charging alternator with inbuilt regulator and battery charging ammeter should be deleted from engine specifications since Battery charger included under AMF Panel specifications. |
| 123 | (ii) Platform : PCC foundation /plinth/baseshall be provided as per drawing No: TD/2010/109, Sheet No 1/1.(iii) Tool kit, Operation and Maintenance catalogue, 1 year spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacturer standard practices. |
| 124 | Supply, installations, testing of electric chimney of size 60cm havingsuction capacity of 1200 cum per hour with filterless technology sealed motor and insulationfor oil deposit and water vapour alongwith self autoclean feature after 30 cycles of operation and minimum 5 year warranty etc etc complete all as specified and directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail