| 1 | Supply, testing and commissioning of following capacity Sandwich Type Rising Main for use on 3 phase 4 wire 415 V, 50Hz A.C. supply with metal clad enclosure as integral earth having IP-54 for indoor after fixing the joints, tap off boxes and all accessories, made of 1.5mm/1.6mm thick GI sheet steel - IK10, duly painted with colour shade RAL-7035 or equivalent, complete with 4 Nos. aluminium bus bars within plating having class-F Insulation(155Deg C) and Impulse withstand 12KV, at nominal current rating. The system shall be complete with all necessary fittings, tap-off unit brackets, etc. with provision of tapping at every meter as required. 800A, SC 42KA for 1 sec,Complete all as specified and directed by Engr-in-Charge. |
| 2 | (a) Straight Length -IP65 (Outdoor) |
| 3 | (b) Straight Length with Plug in outlet IP55 (Indoor) |
| 4 | (c) Flange End IP65 (Fabrication Charges Only) |
| 5 | (d) Elbows IP65 (Fabrication Charges Only) |
| 6 | (e) Suspension Brackets |
| 7 | (f) Copper Flexibles |
| 8 | (g) Adaptor Boxes with Links |
| 9 | (h) Canopy For Outdoor |
| 10 | Supply, testing and commissioning of following capacity Sandwich Type Rising Main for use on 3 phase 4 wire 415 V, 50Hz A.C. supply with metal clad enclosure as integral earth having IP-54 for indoor after fixing the joints, tap off boxes and all accessories, made of 1.5mm/1.6mm thick GI sheet steel - IK10, duly painted with color shade RAL-7035 or equivalent, complete with 4 Nos. aluminium bus bars within plating having class-F Insulation(155Deg C) and Impulse withstand 12KV, at nominal current rating. The system shall be complete with all necessary fittings, tap-off unit brackets, etc. with provision of tapping at every meter as required. 630A, SC 36KA for 1 sec,complete all as specified and directed by Engr-in-Charge. |
| 11 | (a) Straight Length -IP65 (Outdoor) |
| 12 | (b) Straight Length with Plug in Outlet IP55 |
| 13 | (c) Elbows IP65 (Fabrication Charges Only) |
| 14 | (d) Suspension Brackets |
| 15 | (e) Canopy For Outdoor |
| 16 | Supply, testing and commissioning of following capacity Plug in / Tap off Box for use on 3Phase 4 wire 415 volts,50Hz A.C. supply made with1.5mm thick sheet steel enclosure (IP55) duly powder coated with provision of MCCB\"s (but without MCCB) with thermo magnetic release and terminal spreaders , complete all as specified and directed by Engr-in-Charge. |
| 17 | (a) 160A, 4P 25 KA |
| 18 | (b) 200A, 4P25 KA |
| 19 | (c) 400A, 4P 25 KA |
| 20 | Note for serial item No-1 and 2 :- (i)All necessary T&P will be brought/arranged by contractor with out any extra cost. The Cost is inclusive in the quoted rate of the respective items.(ii) Contractor shall ensure to make the entire elctric supply functional on each day before leaving from HQ NC.(iii) Price of refixing earthing strip along with fixing materialsdeemed to be inclusive in the quoted rates.(iv)Rates deem to be included for The Bus-duct enclosures shall be earthed by continuous existing AL/ GI , Eart strip as per specified, Running both sides of the enclosures through the entire length of Busbar. (v)Contractor must visit the site andascertain himself about the oversimplification of the work before quoting the rates.(vi) Drawings of the bus bar ducting shall submit the contractor as per the OEM recommendation and approved by the GE before placing the order.(vii)Entire work shall be supplied commissioned in accordance with detail drawing manufacturer\"s instructions and to the satisfaction of the site representative.(viii) At the time of installation of bus ducting, site engineer from OEM will be present at site for guidance for proper installation. (ix) Necessary Angle iron and PCC foundation shall provide by the contractor as per OEM recommendation to run the Bus bar trunking.(x) The rate is included all nuts , bolts and any other items pertains to Installation, testing and commissioning of Busbar trunking. |
| 21 | Supply , install , testing and commissioning of wire mesh cable tray hot dip galvanised type of size of 105 mm height X 600 mm width, 3 meter length each as per EN 12329 and IEC 61537 with wire diameter of 3.9 to 5.9 mm and having SST of 550 Hrs tested , having E30/E90 certification, with following specification, complete all as specified and directed by Egnr-in-Charge.Make: Legrand/C&S/L&Ti) C41S/RCSN/R35 (wall/celling/ground mounting supports) every after 1 meter distance.ii) Kitaster coupler (Jointing tray ) 5 sets per joint.iii) Down rod of 1 meter length each.iv) Nuts 3 nos for each rod.v) COUPFIL(Cutter) 01 No.vi) L supports for wall with all accessories such as nut ,bolt ,washers etc.Note :- a) Shifting of all existing HT and LT cables, Removing connections of these cables and refixing at its original position through cable trays in a proper manner all as directed by engr in charge is included in the quoted rates.b) All major and minor spares are required in laying of cables and fixing of cable trays which are not mention above are included in the quoted rates.c) All material such as cement ,concerete,tiles etc to make wall/roof /ground in its original shape after fixing of cable trays are included in the quoted rates. |
| 22 | Earthing complete with GI earth electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground surrounded from all sides by 15 CM thick and packed layer of charcoal dust and common salt filling in alternate layers cleaned connected to and including GI earth strip 32X6 mm size up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 20 mm bore for watering and including funnel wire mesh, RCC pit cover 50 mm thick and PCC chamber pit with PCC 1:3:6 type C-2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 meter) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 all as specified and directed.Note :- Contractor Shall provide earth pit chamber board of 3.15mm thick mild steel sheet of size 45cmX30cm fixed with12mm thick MS rod two nos up to 90 cm height by nuts/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letters 6cm height i.e Eart pit No, Location, Earthing test Value and date complete all as specified and directed by Engr-in-Charge. |
| 23 | Dismantling iron sections as in chequered plate and frame work to plates in any size and positioncomplete all as specified and directed by Engr-in-Charge. |
| 24 | S&F plates (plain or chequered) plate channels square cut or notched forming holes , without any attachment incl necessary welding, complete all as specified and directed by Engr-in-Charge. |
| 25 | S&F Rolled sections as in main and cross beam, frame work to ducts for laying chequered plates and similar work including necessary welding, grouting using PCC 1:3:6 and making good to surface as required, complete all as specified and directed by Engr-in-Charge. |