| 1 | Supply, Installation, Commissioning & Testing of Intelligent Addressable 4‑Loop Fire Alarm Control Panel, including all Interfaces, Power supply, Battery backup, Programming and Documentation. Panel Type :4‑Loop Addressable Fire Alarm Control Panel, Maximum Devices per Loop - 198 devices per loop (Detectors, Call points, Modules), Interfaces - (a) USB Programming Port (for configuration Upload / Download) (b) RS485 port for Repeaters, Power Supply - Built-in Power Supply / Charger - 24 V DC Output with required current rating for full system load, Battery backup - Sealed Lead Acid (SLA) batteries e.g. 2 × 17 Ah or as per actual site requirement to meet 24 Hrs Standby and 30 Min Alarm Condition), Display & User Interface - LCD or LED display with Zone Indicators (Optional : 6x40 character backlit display), Intuitive keypad for Alarm Acknowledgment, Reset, Silence and Programming Network & Expansion : Ability to Network multiple panels (if required), support for Repeater Panels over RS485, Standards & Compliance : EN54‑2, EN54‑4 compliant / BIS / IS certification incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 2 | Supply, Installation, Commissioning & Testing of Multi‑Sensor Addressable Detector with Detection Technology : Dual / Multisensor Photo‑electric LED Indication. Standards / Certification : Conforming to EN 54‑5 (heat) & EN 54‑7 (smoke) for relevant models, LPCB approved incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 3 | Supply, Installation, Commissioning & Testing of Addressable Manual Call point Dimensions (approx.): Semi‑flush: 89 mm × 93 mm × 27.5 mm (W×H×D); Surface mount: 89 mm × 93 mm × 59.5 mm, Activation Mechanism resettable element , Operating / Supply Voltage: 15 V DC to 32 V DC Maximum. Certification Type : EN 54‑11 compliant, LPCB approved incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 4 | Supply, Installation, Commissioning & Testing of Sounder‑Strobe (Hooter) having Flash Sound Output : ~97 dB(A) ± 3dB @ 1 Mtr (High volume mode), Operating Temperature : approx ‑ 25 °C to + 70 °C. Certification / Standards : Compliant with EN54‑3 (sounders), EN54‑17/23 (for sounder‑strobe versions) as applicable; LPCB approved incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 5 | Supply, Installation, Commissioning & Testing of Addressable LED Response Indicator. Colour / Finish : Red / White / Optional clear lens for visual signaling, Operating Mechanism : LED illuminates on addressable signal from panel, Certification Type : EN54‑23, LPCB Approved incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 6 | Supply, Installation, Commissioning & Testing of Addressable Loop Isolator Module, Operating Automatic loop isolation in case of short-circuit, Certification Type : EN54‑17, LPCB approved incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 7 | Supply, Installation, Commissioning & Testing of Conventional Multisensor detector with mounting base. Standard : 100mm base, Operating voltage : 9 ~ 33 V DC, Operating temperature : –10 °C to + 37.8 °C, Mechanical dimensions : approx height 60 mm with base & diameter 100 mm. Weight ~130 g with base. IP rating : IP42 incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 8 | Supply, Installation, Commissioning & Testing ofManual Call point with dimensions (approx.) : Semi‑flush: 89 mm × 93 mm × 27.5 mm (W×H×D); Surface mount : 89 mm × 93 mm × 59.5 mm, Activation Mechanism : Resettable element, Operating / Supply Voltage : 15 V DC to 32 V DC Maximum incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Siemens / Honeywell - Morley / Honeywell - Notifier / Ceasefire (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) |
| 9 | Supply, Installation, Commissioning & Testing of Loop Card for FC922 panel, Model : FCI2016-U1 (MAKE : SIEMENS) incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. |
| 10 | Supply, Installation, Commissioning & Testing of CPU for FC922 panel, Model : FCM2018-U3 (MAKE : SIEMENS) incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. |
| 11 | Supply, Installation, Commissioning & Testing of Power Supply Unit for FC922 panel, Model : FP2011-U1 (MAKE : SIEMENS) incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. |
| 12 | Supply, Installation, Commissioning & Testing of CPU Protection Device (MAKE : SIEMENS) incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. |
| 13 | Supply, Installation, Commissioning & Testing of Rechargeable Battery 7Ah 12 Volts for Fire Alarm Panels, Make : Exide / Amaron (Strictly as per existing Make / Model / System &/or as directed by the Engr-In-Charge) incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. |
| 14 | Supplying & laying of 2 x 1.5 sqmm Fire Survival Armoured Cable, 600 /1000 V rated with annealed copper conductor having Glass Mica Fire Barrier Tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, Steel Wire Armouring & LSZH outer sheath incl necessary fixing arrangements & testing complete incl taking down old / unsv / damaged one & depositing the same to MES Storeyard complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Make : Polycab / Finolex / KEI / Havells &/or as directed by the Engr-In-Charge. (NOTE : Payment will be done based on actual length of cable laid) |
| 15 | M&L for Comprehensive Annual Maintenance Contract (AMC) for the complete Fire Alarm & Detection System for 2 Years from the Certified date of Completion. The AMC shall cover Preventive Maintenance, Firmware Updates, Testing, Calibration and Corrective Maintenance of the complete system components listed below. All Fire Alarm & Detection systems must be visually inspected, functionally tested Quarterly As per IS 2189 : 2019. NOTE : Service Frequency and Duration - Quarterly i.e. 4 visits per year. For 2 Years - 8 visits Total. |
| 16 | Addressable 2 Loop Fire Alarm Panel (14 No\"s x 8 Visits) |
| 17 | Addressable 4 Loop Fire Alarm Panel (7 No\"s x 8 Visits) |
| 18 | Conevntional 4 Zone Fire Alarm Panel (1 No x 8 Visits) |
| 19 | Conevntional 8 Zone Fire Alarm Panel (1 No x 8 Visits) |
| 20 | Addressable Multi Sensor Detectors (800 No\"s x 8 Visits) |
| 21 | Conventional Multi Sensor Detectors (100 No\"s x 8 Visits) |
| 22 | Beam Detetcors(14 No\"s x 8 Visits) |
| 23 | UV / IR Flame Detetcors (48 No\"s x 8 Visits) |
| 24 | Manual Call Points (MCP\"s) (150 No\"s x 8 Visits) |
| 25 | Hooter Cum Strobe (40 No\"s x 8 Visits) |
| 26 | System Components Covered :A Addressable / Conventional Fire Alarm Control Panel (FACP) / Loop Tetsing B Smoke Detectors (Ionization / Photoelectric) C Heat Detectors (Rate of Rise / Fixed Temperature)D Manual Call Points (MCPs)E Sounders, Strobes, and HootersF Beam Detectors G UV / IR Flame DetectorsH Interface Modules (Input / Output Modules)J Loop Isolators and Power Supply Units |
| 27 | Maintenance Activities (To be Performed Quarterly). Each quarterly visit shall include the following :A Visual inspection of the Panels and EnclosuresB Checking for any Fault, Trouble & / or Supervisory SignalsC Verification of all LED indicators and Buzzer functionsD Testing Communication on all Loops and ZonesE Reviewing and updating Event LogsF Firmware Update and Configuration VerificationG Battery Voltage and Charger TestH Ground Faults Rectification |
| 28 | Detectors and Field Devices :A Functional Testing of all Detectors (Smoke, Heat, MCPs, Sounders etc.)B Cleaning of Detector Chambers using approved Air Blower or Vacuum methodC Testing of Manual Call Points for Alarm Activation and ResetD Checking Sound Level and Visual Indicators of Sounders / Beacons etc.E Loop Integrity Test and Device Address Verification |
| 29 | Beam Detectors :A Visual Inspection of Emitter and Receiver Units (or Reflective Prism)B Cleaning of Optical Surfaces (Lens / Prism)C Verification of Alignment using built-in Alignment Tools or Laser Alignment KitD Functional Test by introducing Controlled Obscuration to Simulate SmokeE Checking Sensitivity Setting and Alarm Threshold LevelsF Calibration if required and Documentation of Test Results |
| 30 | UV / IR Flame Detectors :A Inspection for Cleanliness and Obstruction-Free Field of ViewB Cleaning of Optical Windows with Non-Abrasive MaterialsC Testing using approved UV / IR Flame Simulator (No Open Flame to be Used on / at Site)D Verification of Detector Response Time and Alarm Relay FunctionE Firmware and Sensitivity Check where applicableF Documentation of Test Readings |
| 31 | Corrective Maintenance :A Rectification of Minor Faults detected during InspectionB Resetting, Configuration, and Replacement of Defective Devices C Troubleshooting of Communication Errors or Panel FaultsD Reporting of any Major Fault requiring Material Replacement |
| 32 | Documentation & Reporting :A Submission of a Detailed Service Report after each visitB Summary of Devices Tested, Faults Found, and Rectifications DoneC Recommendations for Replacement or Upgrade of Outdated or Faulty DevicesD Annual Performance Summary Report at the end of each Contract Year |
| 33 | Supply, install, commissioning & testing of Single Phase, Online UPS system of capacity 1 KVA, 24 V, Pure Sinewave, Indoor compact type complete with Inbuilt Battery System (12V 9 AH x 2 Nos) suitable for minimum 04 hour back-up, perfectly compatible for Generator Supply & for use in Fire Alarm & Detection System with & including by-pass arrangement & necessary electrical copper wiring, MCB Change-over Switch complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. Model : E2 1KVA 24V IB of Make Microtek or techno-commercially equivalent of Luminous / APC. |
| 34 | IMPORTANT NOTES FOR ITEM NOS 1 TO 16 :1) Design / Drawing / BOM / Make / Technical specifications etc. of the Items / Job of the complete Fire Alarm & Detection System showing the layout & other details etc. is to be obtained from OEM / Auth Channel Partner / Supplier & is to be got approved from Engr-in-charge & GE before placing final order. Techno-Commercial Comparative Analysis is also required to be submitted to Engr-In-Charge & GE whereever equivalency w.r.t. a given Make/Model/Cat-Part Ref is concerned.2) The complete Supply, Installation, Commissioning & Testing of the Items / Job of the Fire Alarm & Detection System incl the Comprehensive AMC for 2 Years from the Certified date of Completion is to be got done from the OEM or their Auth Distributor/Channel Partners only & Submission of Reports duly signed by all concerned including the User Concerned to Engr-In-Charge & GE in duplicate. The Contr / Firm needs to submit MoU with OEM in this regard duly signed by all concerned along with necessary docs / drawings / design etc. as applicable complete all as specified & as directed & to the entire satisfaction of the Engr-In-Charge.3) Any item/work etc. missed out in the technical specifications but technically required for efficient working of the Fire Alarm & Detection System is deemed to be included in the unit quoted rates.4) Contr/Firm is required to visit the site of work for any doubts/clarifications w.r.t. specifications / qty etc. before quoting of the Tender. Any query/clarifications etc. after conclusion of the Contract shall NOT be entertained & decision of the AO shall be final & binding.5) Cost of taking down old / unsv / obsolete items / spares etc. incl transportation of the same to the MES Storeyard is deemed to be included in the unit quoted rates.6) Cost of use / hiring / rent including transportation of Aluminum Ladders / Scaffolding arrangements etc. required for successful execution of the complete work / Job is deemed to be included in the unit quoted rates. Quoted rate is also deemed to be inclusive of all safety precautions / measures to be taken by the Contractor for labour / tradesmen employed at the site. 7) Purchase Vouchers / Test Certificates / Guarantee & Warantee Certificates is to be submitted in Original to the Engr-In-Charge for checking / records.8) The Contr / Firm shall attend any major system fault / breakdown within 24 Hrs & minor faults within 48 hours of intimation by any means incl electronic mode & restore the system at the earliest without any additional cost to the Dept during the AMC Period. In the event of non-attendance / non-rectification of the faults / breakdown within the stipulated 24 / 48 Hrs, Penalty @ Rs. 2500/- per day shall be recovered & the decision of the AO shall be final & binding in this regard.9) All the Repair / Maint / Servicing / Cleaning / AMC etc. activities within the scope of this Tender / Contract is to be carried out in the presence of User Rep & MES Rep & accordingly Reports generated duly signed by all concerned incl the User Rep. |