| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 × 4 sq. mm + 2 × 4 sq. mm earth wire |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 × 4 sq. mm + 1 × 4 sq. mm earth wire |
| 6 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (a) 3 x 2.5 sq. mm |
| 7 | 3 x 4 sqmm |
| 8 | 6 x 4 sq. mm |
| 9 | 3 x 6 sqmm |
| 10 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25mm |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16A modular switch, connections etc. as required. |
| 12 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 13 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 14 | Supplying and fixing5 A to 32 A rating, 240/415 V, 10 kA, “C”curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 15 | Single pole and neutral |
| 16 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A |
| 17 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal ( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 18 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range - 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/ 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screenprinting on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineerin-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminum Body (Thickness ≥ 1.20 mm)18-22 watt |
| 19 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 20 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 21 | Supply ofXLPE insulated,PVC sheathed Al.conductor Armoured Cable 1.1 KVgrade Conforming to IS 7098of following Sizes 2x6 sq mm |
| 22 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P.F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 50 watt |
| 23 | P/f of Hot press sheet moulded compound (SMC) Fire retardant (Temp. Resistance up to 200 C ) IP-55 weather proof pole box of inner dimension 200mm X 160mm X98mm complete with suitable arrangment for fixing of 2 no.s of 6 to32 Amp single pole MCB &63 AmpDouble Pole isolator (MCB/isolator exculded) with neutral link duly shorting on DIN channel with 2 nos. of MS clamps with SS back plate of suitalbe size with Danger monogramproperly printed on the cover etc as reqd. |
| 24 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 25 | Supply of 12\" (300mm) sweep 1400 rpm exhaust fan heavy duty complete with shutters, blades etc as reqd. |
| 26 | SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color |
| 27 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 12 way , Double door |
| 28 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 amps switch |
| 29 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 3 pin 5/6 A socket outlet |
| 30 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 15/16 amps switch |
| 31 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 6 pin 15/16 A socket outlet |
| 32 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 33 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 6 Module (200mmX75mm) |
| 34 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 8 Module (125mmX125mm) |
| 35 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 12 Module (200mmX150mm) |
| 36 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts C curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 37 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only. 1.5 TR with 5 Star BEE Rating |
| 38 | S/I/T/C of stand for split AC |
| 39 | S/I/T/C of copper pipe for split AC |
| 40 | S/I/T/C of Drain Pipe |
| 41 | Supplying and fixing of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as required. |
| 42 | Supplying AND Installation of Reverse Osmosis (RO) water purifier of capacity 50 ltr/hr complete as required. |
| 43 | Supplying, installation, Testing & Commissioning of following capacity at fullload (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS)system suitable for Single Phase input, Single Phase output AC Supply. TheUPS shall include a Rectifier, inverter, battery bank suitable for 30 minutesback up (Battery VAH capacity shall not be less than 1600 VAH per KVA ofUPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF inABS Container) and Static Bypass switch along with provision for manualbypass, suitable isolation transformer for additional protection againstneutral faults etc. The UPS systems shall be Microprocessor based DigitalControl, using Insulated Gate Bipolar Transistor (IGBT)\"s both for therectifier & inverter with PWM (Pulse Width Modulation) Technology. Thequality of design, manufacturing and inspection process should confirm tothe relevant Inter-national standards such as IEC/EN/VDE. The operatingefficiency of the UPS systems shall be >95% at 100% non-linear loads.Current total harmonic distortion (ITHD)/ total demand distortion (TDD) onthe input grid shall be < 5% at 100 %load. (The required LC filters shall beincluded in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature 0 to 40 deg C, Relative humidity 0-95% noncondensing, noise level less than 60db at 1 meter distance, Protection forUnder voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, CommunicationRS232/RS485/SNMP port open protocol for BMS integration as perapproved by Engineering in charge. Required battery racks, DC breaker ofsuitable rating and interconnecting copper conductor cable of suitable sizeand connectors and all required accoseries are inclusive in the cost. TheUPS should have QR code which should contain drawing, test report OEMmanual, Geo- Tag of manufacturing location etc. 3 KVA |
| 44 | Supply, Installation, testing and commissioning of power distribution board made out of 1.6 mm sheet steel, epoxy powder coated, specially designed Al bus bar 400 A to 630 A with heat shrinkable colour coded sleeves suitable for accommodating MCCBs/MCBs/lsolators as incoming and outgoing as required (without MCCBs/MCBs/lsolators) complete with digital meter Module, including Voltmeter, Ammeter with selector switch, CTs control fuse and indicating lights including connections etc. as required (conforms to 15:8623). I/c removing the existing panel etc and reconnecting the inputs to existing submain |
| 45 | Providing and fixing ABC (Aluminium Phosphate) power type fire extinguisher of 6 kgs capacity complete in all respect with ISI mark i/c fixing arrangement etc as required. |
| 46 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 47 | Supply, installation, testing and commissioning of vertical type, multistage, totally enclosed water filled deep well submersible pumping set complete i/c connection etc. as reqd. (a) single phase 1.5 HP having discharge of 72 LPM approx. at 49 M head |
| 48 | Supply, installation, testing and commissioning of cubical type control panel board for single phase & three phase submersible pumping set of following rating complete with contractor, relay, MCB, condensor, voltmeter, ammeter, and indication lamp, etc including connections etc as required. 1.5 HP |
| 49 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 125 A, 16 KA,TPMCCB |
| 50 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 250 A,50KA,FPMCCB |
| 51 | Supply of 3 mm thick phenolic laminated sheet |