| 1 | Supply,fixing,testing and commissioning of Digital Power MetersA). All the electrical Parameters with Harmonic Measurement ( (THD-V%,THD-I%, up to 31th harmonic for current and voltage separately) 3 Phase 4 wire Digital Power Analyzer with following Features complete all as specified and directed.B). Meter Display Parameters: V, A, F, kW, KVA, kVAr, kWh, kVAh, kVArh, PF, Runhr, Onhr, Interupts,Phase angle, THD, Neutral current, Max Demand (with RTC) K FactorC). Meter Communication Enable: RS 485 Communication.D). Alarm Contact Output & 4-20mA Analog output for PLC\"s.E). Displays Maximum & Minimum Demand Values.F). Meter can be site selected for parameters and values - A THD, V THD, VA, W, under PF, under/over (VLL, A, F) with programmable trip time (1 to 180 sec) to protect the equipments from electrical abnormalities.G). Confirming IEC- 62053-24 |
| 2 | Supply,fixing,testing and commissioning of ACB, 4Pole of Microprocessor Based with breaking capacity of 50kA, Ics=100% Icu, Inbuilt or External Instantaneous Protection and Inbuilt Ground Fault Protection Individual Fault Indication LEDs incl Suitable size of CTs asper site requirement Suitable Size of ACB it must be minimum of 1.3 times of Tx. including Shunt Release system with suitable size of panel cabinet made of CRCA sheet of 2 mm thickness Loading Current where PTR 1.6 MVA (33/11KV) complete all as specified and directed. ACB Has Energy Metering and inbuilt RS485 Communication |
| 3 | Supply,fixing,testing and commissioning of MCCB, 4Pole of Microprocessor Based with breaking capacity of 50kA, Ics=100% Icu, Inbuilt or External Instantaneous Protection and Inbuilt Ground Fault Protection Individual Fault Indication LEDs incl Suitable size of CTs asper site requirement & Suitable Size of MCCB it must be minimum of 1.3 times of Tx. including Shunt Release system complete all as specified and directed. MCCB Has inbult RS485 Communication enabled. and inbuilt current metering display › Ics=100% Icu› Adjustable Overload Settings from 0.25 to 1 In (in steps of 0.01)› Adjustable Short Circuit Settings from 1.5 to 12 Ir (in steps of 0.1)› Adjustable Instantaneous Settings from 1.5 to 12 Ir (in steps of 0.1)› In-built Ground Fault Protection from 0.1 to 1 In (in steps of 0.05)› Adjustable Neutral Overload Protection from 50% to 160% of Ir› Local LCD Display Menu Navigation using Keypad› Modbus RTU Communication Capable› Switchable Thermal Memory› Provision for Release Testing› Variable trip class› Transparent sealable release cover› Compact size› Wide range of accessoriesNote :- Provn of suitable size of panel cabinet made of CRCA sheet of 3.15 mm thickness in case of non availibilty space for mounting arrangement of MCCB on existing Panel is deemed to be included in the quoted unit rate. |
| 4 | All as per item No. 03here-in-before but, 100 A ( Suitable for DTR 63 KVA (33/0.415 KV) |
| 5 | All as per item No. 03here-in-before but, 200 A (Suitable for DTR 100 KVA (11/0.415KV) |
| 6 | All as per item No. 03here-in-before but,250 A ( Suitable for DTR 160 KVA (11/0.415KV) |
| 7 | All as per item No. 03here-in-before but , 315 A (Suitable for DTR 200 KVA (11/0.415KV) |
| 8 | All as per item No. 03here-in-before but , 500 A (Suitable for DTR 250 KVA (11/0.415 KV) |
| 9 | All as per item No. 03here-in-before but , 630 A (Suitable for DTR 400 KVA (11/0.415 KV) |
| 10 | Supply,fixing,testing and commissioning of Energy Management System Software (SCADA) with Following Features:-Data base Integration Software,Monitoring of all connected meters, Daily/ weekly / Monthly Report generation for analysis Graphical Analysis of all electrical parameters of each meter & also main Meter,Alarms -User Define alarms for Low PF/ Maximum Demand overshoot etc complete all as specified and directed.Note :- OEM auth System Integretor shall ensure that the SCADA/EMS and RTU/Master Controll Unit should be same make asper mentioned in Tender documents. |
| 11 | Supply,fixing,testing and commissioning of Data Line Converter with Ethernet complete all as specified and directed. 4G IoT Gateway with Dual Sim (Modbus RS485, Modbus TCP/IP and MQTT support) (Advanced VPN Routing, Wide range of Industrial protocols support:IEC60870-5-101 Master / Slave ,IEC 60870-5-104 Master / Slave ,IEEE 62056-21 DLMS , DNP3 Slave) |
| 12 | Supply,fixing,testing and commissioning of Life Time License Software to Monitor and Control from Main Control Room PC as seen any abnormal condition occurs and technology must be used GPS/GPRS with VPN Network Creation SIM Charges Monthly/Yearly borne by Contractor complete all as specified and directed. |
| 13 | Supply,fixing,testing and commissioning of Desktop Mounted Industrial type PC: Processor: i7 /2.8GHz, PCI Slots and 2 LAN card, 4USB, VGA/HDMI, Hard disk: 1TB & 1TB Built-in SSD, RAM 16GB,with Monitor, Keyboard/Mouse, Window 7/10 operating System(OS) , With Antivirus, Fan Less Design complete all as specified and directed. |
| 14 | Supply,fixing,testing and commissioning of Online UPSBattery with2 Hrs backup incl battery rack & inter link Cable at master controll room as per master controll PLC Loading current complete all as specified and directed.Make : APC/BP/Microtek |
| 15 | Supply,fixing,testing and commissioning of Multi Option Laser Printer for report printing complete all as specified and directed. |
| 16 | Supply,fixing,testing and commissioning of Eathernet Network Switch of 8 ports complete all as specified and directed. |
| 17 | Supply,fixing,testing and commissioning of HD Smart LED Screen greater than 42” with HDMI/Communication Port complete all as specified and directed. |
| 18 | M & L for fixing of ISI marked Armoured Ethernet Cat 6 Wirefor network connection complete all as specified and directed. |
| 19 | Supply,fixing,testing and commissioning of RTU Units with required Digital I/Os and Analogue I/Os at each location with minimum 3hr backup complete all as specified and directed.Note :- System Integretor shall provide the OEM auth Certificate as mentioned in the Tender documents. |
| 20 | Supply,fixing,testing and commissioning of Master Control Units contains each RTUs with minimum 3 hr backup complete all as specified and directed.Note :- System Integretor shall provide the OEM auth Certificate as mentioned in the Tender documents. |
| 21 | M & L for PVC Insulated,shielded2 Core copper belden wire for meter Data communication connection as required complete all as specified and directed. |
| 22 | S & F of 25 mm heavy duty (HMS) PVC conduits,ISI marked concealed / surface in shaft as required including all accessories i.e. bends, junction boxes with cover plates of approved make and design (Wherever required) complete all as specified and directed.Make: Polycab / Jindal / Anchor |
| 23 | M & L for installation of Static IP at master controll room incl Network SIM cardat Each RTU location complete all as specified and directed. |
| 24 | Installation, commissioning & Training for complete SCADA system all as specified and directed. |
| 25 | M & L for Non Comprehensive Maintenance& Monitoring,mangement of SCADA Based EMS system for smoothly functioning of 3 Years AMC (Two year under warranty period and one year of non comprehensive type incl per month One Visit of Auth SCADA system integreator for routine maintainance and submit a log book report to the resp authurity and one tech rep detl in General Shift in daily basis ) including carrying out maintenance and servicing of PLC & SCADA Panel and all connected circuit and accessories as required for all the modernised electric supply system as described at SI Line under GE Bhopal - MP complete all as specified and directed.Note :- Comprehensive Maintenance thorugh OEM Authorised ISP Only |