| 1 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth or n exc 10 Sqm on plan and n exc 1.5 m in depth & getting out, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes or for layingunderground cable, pipe lines etc. in soft/ loose soil, complete all as specified & directed. |
| 2 | Returning, filling in soil, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed. |
| 3 | Removing excavated material (soil) n exc. 50m distance and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and directed. |
| 4 | M&L dry river clean Sand filling in trenches around underground cables for earth cushion, complete all as specified and directed. (Depth of sand shall be measured after punning). |
| 5 | Supplying and laying in renewal of un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm laid dry and flat adjoining each other over sand cushion in trenches as protection to UG cable, complete all as specified and directed. |
| 6 | Dismantling old existing ACSR conductor of any type/size complete all as specified and directed. |
| 7 | M & L for hardcore broken stone or boulders crushed aggregate of size 25 to 40 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface at 4 Pole, 2 Pole strucutres and other E&M Installations complete all as specified and directed. |
| 8 | Demolition of old u/s existing transformer foundation and M & L for construction of plateform of size 2500 x 2500 x 1200mm with brick construction in cement mortar 1:4 PCC (M-10 nominal mix) in foundation, 100mm thick RCC M-25 grade slab, with & including 8mm MS TMT bars 120mm c/c on bothway, brick masonary steps on one side XPM Jali fixed on angle iron 40x 40x6 mm post upto height of 8 feet above ground level and openable gate with locking arrangment including making provision for entry and exit of HT/LT cables and steps made to access to the top of plateform including plastering to bricks masonary complete including painting with 2 coats of whitewash on plastered surface and painting steel surface with 2 coats of red oxide primer complete all as specified and as diredted. |
| 9 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending cold or hot, drilling holes for bolts, in any hape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint & including dismantling of old unserviceable cross arms of MS channel or angle sections etc complete all as specified and directed. |
| 10 | S& F in renewal of rolled mild steel as in plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, with rivetted /bolted .welded attachment used to cover ducts in HT installations complete all as specified and directed. |
| 11 | M&L for pin type, porcelain, vitreous, white, borwn or green insulator, including one galvanised mild steel spindle, two galvanised mild steel spindle, two galnvanised iron wahers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade & including dismantling of old unserviceable insulator, complete all as specified and directed. |
| 12 | M&L for insulator disc type porcelain, vitreous, 145 mm high and 255 mm dia ball and socket type, white, brown or green for tension with tension clamps for conductor, working pressure 11000 volts & including dismantling of old unserviceable insulator, complete all as specified and directed. |
| 13 | M&L for Loop type insulator, vitreous porcelain, white, brown or green, Large size, with overall dimensions 90mmx140mm, clearance of hole 25.5mm & including dismantling of old unserviceable insulator, complete all as specified and directed. |
| 14 | S&F in renewal of earth continuity conductor or main earthing lead 32x6mm galvanised iron or steel strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required completeall as specified and directed. |
| 15 | M&L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing earth strip of 32x6 mm galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion including 50 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth strip of 32x6 mm galvanised iron for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 2 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: -(a) Irrespective of whatever is shown in plate No 2 of SSR Part - 1 (2009), earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b)Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m. |
| 16 | M&L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing earth strip of 25x4 mm galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion including 50 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth strip of 25x4 mm galvanised iron for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 2 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: -(a) Irrespective of whatever is shown in plate No 2 of SSR Part - 1 (2009), earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b)Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m. |
| 17 | S&F in renewal of 80 mm bore steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed. |
| 18 | S&F in renewal of 100 mm bore steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed. |
| 19 | Supply, installing, testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 15 nos including200 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level, with locking arrnagments including Godrej pattern 65mm pad locks with two keys, suitable for HT 11 KV, 50 Hz AC supply & including necessary electric connections and taking down old unserviceable GOD complete all as specified and directed. |
| 20 | Supply, installing, testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 15 nos including400 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level, with locking arrnagments including Godrej pattern 65mm pad locks with two keys, completesuitable for HT 11 KV, 50 Hz AC supply including necessary electric connections and taking down old unserviceable GOD complete all as specified and directed. |
| 21 | Supplying, laying, jointing, testing and commisioning XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) withaluminium conductor, 11000 volts Earthed grade (ISI marked), laid in trenches / ducts / encased in GI pipe / fixed to pole/wall with necessary angle iron support, clamp, nut , bolts etc and including taking down of old unserviceable existing UG cables complete all as specified and directed for following cross sectional areas of cables :- Notes for Srl item Nos. 21.00 to 21.10 :-(i) Excavation, earth work, sand cushioning, cable protection cover & GI pipes shall be measured and paid for separately under respective items of BOQ. (ii) Quoated rate shall be deemed to be inclusive of connecting up with control gear including cable glands and cable lugs.Cross Sectional area of cable 95 Sq mm 3 core |
| 22 | Cross Sectional area of cable 185 Sq mm 3 core |
| 23 | Supply, transporting, erection and fixing steel tubular swaged pole, 11.00 metres long, type 410 SP-55, complete with cast iron base plate, pole cap, finial taper plug, bolts, nuts, washers etc including necessary earth work and excavation, PCC in foundation 1:3:6 type C2, using 40 mm graded stone aggregate and PCC 1:2:4 type B1, using 20 mm graded stone aggregate as in coping to the pole, disposal of surplus soil to a distance not exceeding 50 m, painting the pole with two coats of aluminium paint over one coat of red oxide primer including 3 nos band/straps with red post office box colour (300mm wide each) synthetic enamelled paint at a distance 300mm from plinth block and marking pole nos with black synthetic enamelled paint including tarring one coat on steel surface embedded in concrete & including taking down existing old unserviceable poles and complete all as specified and directed. |
| 24 | M&L for painting the external exposed surfaces of 2 pole structures ofsteel tubular swaged poles of 11 metres long alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters on black back ground and pasting radium red strickers/paint with 3 strips of width min 10 cm around the pole complete all as directed. |
| 25 | M&L for painting the external exposed surfaces of 4 pole structures ofsteel tubular swaged poles of 11 metres long alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters on black back ground and pasting radium red strickers/paint with 3 strips of width min 10 cm around the pole complete all as directed. |
| 26 | M & L for painting the external exposed surfaces ofPCC poles (4 Pole) of 11 metres with cement based paint alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters on black back ground and pasting radium red strickers/paint with 3 lines around the pole complete all as directed. |
| 27 | M & L for cutting of bushes and cleaning the area around the sub station & surface dressing n exc 15 cm deep & including two pole/four pole structures premises at southern sector and trimming the trees,complete all as specified and directed.Note : (i) Site shall beintimated tothe contractor on phone or writing between 8 am to 10 pm and will be attended by contractor within 24 hrs, failing which a penalty of Rs. 500 per day shall be imposed on contractor. |
| 28 | S&F in renewal of HT cable route indicator made of RCC M15 (Nominal Mix) using 12.5mm nominal size crushed stone aggregate of size 150mm (Length)X100mm (Width)X900mm (Height) duly painted with cement base and written in white colour with lettering \"MES HT cable\" and arrow indicating direction using two coats of synthetic enamel paint in black colour and including necessary earthwork and excavation, embedded in PCC M15(Nominal Mix) using 20mm nominal graded crushed stone aggregate of size 400mmx400mmx300mm complete all as specified and as directed. NOTE : (i)The reinforcement in RCC shall not be less than as minimum reinforcement required as per IS.(ii) Cost of pcc shall be included in the rate quoted. |
| 29 | Supply and fixingin renewal of danger notice plate of 1.5 mm thick mild steel sheet vitreous enanelled white of size 20 x 25 cm with figures letters and conventional skull bones in signal red colour and fixed with mild steeel clamps made of flat iron nuts bolts and washers etc for HT poles with voltage and danger indicated in hindi and english and local vernacular complete all as specified and directed. |
| 30 | M & L for horizental drilling under road/pavement hard standing with trenchless technology using machine 0.4 mpa working pressure for laying pipe line of size 80 mm bore complete all as specified and directed. Note:Drill hole (trenchless) shall be done without disturbing top surfaces of road by appropriate machine & no extra payment shall be given to contractor on this account. |
| 31 | M & L for horizental drilling under road/pavement hard standing with trenchless technology using machine 0.4 mpa working pressure for laying pipe line of size 100 mm bore complete all as specified and directed. Note:Drill hole (trenchless) shall be done without disturbing top surfaces of road by appropriate machine & no extra payment shall be given to contractor on this account. |
| 32 | Supply and fixing in renewal of 4 Sqmm GI wire as cable gourd to prevent accidental contact and improve safety straining properly on insulators and binding with aluminium tape/binding wire connectors, PG clamps, jumpers etc complete all as specified and as directed. |
| 33 | M & L in renewal of HT jumperingfrom HT 4/2 polestructure to bus bar to GOD 3 Nos with HT cable 70 sqmm not less than 3 mtrcomplete including connector and lugs of suitable size with provision of Nuts & bolts washeretc complete all as specified and directed.Note : 3 lengths i.e. for R,Y & B shall be measured as one unit. |
| 34 | M & L for repairing/overhauling of Air break switch and DO fuse unit up to 400 Amps capacity 11 KV triple pole Mechanically operted mounted on insulators and steel frame installed vertically/horizontally by oiling and greasing of mechanical moving parts smoothing and polshing of electric contacts and applying conducting jelly to contact and replacement of broken/worn out compenents ( if required) including testing after repair complete all as directed.Note :- Cost ofreplacement of following worn out components /parts/insulators etc (if required) shall be included in the rate quoted. Bidders may quote accordingly :-(a) Female contact or fixed contact of capacity up to 400 Amps, 11 KV heavy duty of gigh conductive metal.(b) Male contact or moving contact of capacity up to 400 Amps, 11 KV heavy duty of high conductive metal.(c ) Tinned copper flexible jumper up to 400 Amp.(d) Fixed top and bottom contact assembly 11 KV 400 Amp for DO fuse unit.(e) Fiber glass tube with metallic fittings both ends suitable for DO fuse 11 KV. |
| 35 | M & L for disconnecting all HT/LT connection of transformer, lifting it from its foundation/ structureusing fork lift/crane carefully, refixing it to plateform making all HT/LT connetions and charging the transformer to restore electric supply complete all as specified and as directed.Note :- (i) Any damage during shifting or lifting of transfarmer will be responsibility of contractor and contractor will be liable to repair the same at his own cost. (ii) Lowering and lifting of transformer shall be treated as single job.(iii) Contractor will provide unintrupted electric supply at his own arrangement for the period of Foundation construction without any extra cost. |
| 36 | M & L for Servicing of HT 11 KV VCBs including raking out of Breaker, lubrication /greasing of the mechanical parts including healthy check, cleanign of CT, caliberation after servicing reconnection in all respect along with replacement of unserviceable relays, levers, LED indicators, control wiring, insulators etc (if required), allas per existing arrangement and restore the supply complete all as specified and as directed.Note :- Cost of unsv minor parts/materials replaced shall be deemed to be included in the rate quoted. No extra claim shall be accepted by dept on this account. Bidders may quote accordingly & Any major parts replaced shall be paid under respective item of schedule (BOQ). |
| 37 | M & L for hiring of cable fault locator machine for HT cables working voltage 11 KV to find out the fault inunderground trench at different location up to 500 RM after locate fault filling the straight through joint and charging the cable and jointing the cable on both side in RMU/VCB/HT bus bar chamber or over head line all as directed.Note :- (i) Complaint shall beintimated to contractor on phone between 8 am to 10 pm and will be attended by contractor within 12 hrs, failing which a penalty of Rs. 5000 per day shall be imposed on contractor.(ii) Cost of joints shall be measured andpaid in respective item of Schedule.(iii) Machine hiring count shall be measured and paid as per number of arrivals of machine not as per no. of faults located in a single arrival. |
| 38 | M & L for Servicing of 11 KV 3 phase 50Hz 3 wire 630 Amp breaking capacitySF6 Ring Main Unitby cleaning and lubricating mechanical parts and checking functioning of springs levers on/off position after proper shut down of electric supply along with replacement of unserviceable relays, levers, LED indicators, control wiring, insulator etc(if required) and restore the supply after complete servicing complete all as specified and as directed.Note :- Cost of unsv materials replaced shall be deemed to be included in the rate quoted. No extra claim shall be accepted by dept on this account. Bidders may quote accordingly. |
| 39 | M & L in renewal of Master trip relay suitable for 24 Volt DC Supply crompton CGXH1 or equivalent, suitable for the existing VCBs complete all as specified and directed. |
| 40 | S & F inrenewal of Epoxy/porcelain or as suitable at site insulator suitable for VCB (indoor) 11 KV pressure range complete with nut bolt washer complete all as specified and directd. |
| 41 | Supply and fixing of covered XLPE 11 KV single core 50 Sqmm triple extruded longitudanally (AAAC) weather resistant,non tracking with uv stablized insulation to prevent accidental contact and improve safety straining properly on insulators and binding with aluminium tape/binding wire connectors, PG clamps , jumpers etc complete as required at site and all as directed by Engr-in-Charge.Note :- (a) Work will be executed through civil area (Two pole structure haldighati gate to chittorgarh gate two pole structure).(b) All type permissions required during execution of the work from State agency/Private party/Central Govt etc.(Except MES) will be responsibility of contractor. |
| 42 | M & L in renewal for lightening arresters expulsion type (set of three) complete with all fittings, transmission class, discharge capacity 65 kilo amp Suitable for 11000 volts complete all as specified and directed. |
| 43 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable & including excavation in any type of soil/strata, taking out cable & making disturbed surface after relaying the cable making joints suitable for aluminium conductor of following size complete all as specified and directed:- Note:- Unserviceable joint shall be replaced within 24 Hrs after intimation of failure & documentary proof kept in record duly signed by the Enginner-in-Charge for the same.A penalty of Rs. 1500 per day shall be imposed on contractor, if not attended timely. |
| 44 | 50 Sqmm to 95 Sqmm |
| 45 | 120 Sqmm to 185 Sqmm |
| 46 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size & including excavation in any type of soil/strata, taking out cable & making disturbed surface after relaying the cable making joints suitable for aluminium conductor of following size complete all as specified and directed:- Note:- Unserviceable joint shall be replaced within 24 Hrs after intimation of failure & documentary proof kept in record duly signed by the Enginner-in-Charge for the same.A penalty of Rs. 1500 per day shall be imposed on contractor, if not attended timely. |
| 47 | 50 Sqmm to 95 Sqmm |
| 48 | 120 Sqmm to 185 Sqmm |
| 49 | Supply and fixing in renewal of HT cable/route indicator cast iron of suitable size along HT cable trench including planting in ground with proper PCC complete all as specified and directed. Note :- Cost of pcc shall be included in the rate quoted. |
| 50 | Disconnecting defective outdoor/ indoor distribution transformer of various size from HT/LT sides taking out complete transformer oil storing the same in suitable containers (to be arranged by contractor) opening the top cover, lifting up the core assembly carefully to check the condition of transformer winding core retanking the same after repair refilling the transformer oil after dehydration and filteration (dehydration and filteration to be paid separately) inluding checking of leakage of transformer body and welding works required for making transformer body leak proof transportation of transformer to and from site to work shop and re-installation the same at any site as directed by Engr-in- charge for capacity of transformer 50 KVA to 200 KVA. |
| 51 | Description ditto all as per srl item No -45.00 (here-in-before) but of capacity 250 KVA and upto 500 KVA. Note for srl item Nos. 45 & 46 :- (i) The other materials required for rectification of defects such astransformer oil, bushes, bush rod etc. shall be measured and paid separately under respective item of this sch. |
| 52 | M & L in renewal of burnt /defective HT & LT copper coil with new made out ofsuper enamelled high quality copper wires of matching size to the existing one complete all as specified and directed. |
| 53 | M & L for replacement of existing defective HT tap changer of suitable size with tapping arrangement 2.5% to 7.5% and one normal tapping including connecting up with HT coil and testing of transformer 11/0.415 kV capacity up to 500 KVA complete all as specified and directed. |
| 54 | M & L for servicing/ over hauling including greasing of HT Tap chnager and with tapping arrangement 2.5% to 7.5% and one normal tapping including connecting up with HT coil and testing of transformer capacity up to 500 KVA complete all as specified and directed. |
| 55 | M & L for replacement of existing defective drain out oil outlet valve of any type & size suitable for outdoor/ indoor transformer type complete all as specified and directed. |
| 56 | M & L for replacement of existing synthetic rubberised cork sheet gasket 1/4\" thick suitablefor main body top cover of transformer of capacity up to 500 KVA complete all as specified and directed. |
| 57 | M & L for replacement of transparent type silica gel breather assy of suitable size of transformer capacity upto 500 KVA connected to air column with conservator tank complete all as specified and directed. |
| 58 | Supply and fixing in renewal of transformer oil temperature gauge 0 - 100 graduated Analogue dial type comlpete all as specified & as directed. |
| 59 | Dismantling and opening transformer tank cover removing of worn out transformer oil tank gasket and supply & fixing of new rubberised gasket sheet6.0 mm thick and to be pasted using gasket adhesive for transformer including refixing the top cover with conservator tank or transformer capacity up to 200 KVA complete all as specified and directed. |
| 60 | Description ditto all as per srl item No - 54.00 (here-in-before) but in transformer capacity above 200KVA and upto 500 KVA complete all as specified and directed. |
| 61 | M & L for replacement of defective/ cracked HT porcelain bushing (set of three) of suitable size for transformer upto 500 KVA including washers of good quality complete all as specified and directed. |
| 62 | M & L for replacement of defective/ cracked LT porcelain bushing (set of four) of suitable size of transformer upto 500 KVA including washers of good quality complete all as specified and directed. |
| 63 | M & L for replacement of defective/ wornout HT bush rod (set of three) made out of copper with brass nutsand washers of required length including connecting up with HT coil of transformer upto 500 KVA complete all as specified and directed. |
| 64 | M & L for replacement of defective/ wornout LT bush rod (set of four) made out of copper with brass nutsand washers of required length including connecting up with LT coil of transformer upto 500 KVA complete all as specified and directed. |
| 65 | Supply and filling as in replacement of silica gel inside the breather assembly and fixing properly with transformer complete all as specified and directed. |
| 66 | Cutting off worn out aluminium cable ternimal lugs from the LT cable and S & F of new aluminium cable lugs of suitable size and reconnecting the cablewith transfrormer, terminal stud including dressing of cable, excavation & surface dressing after providing sand cushioning and brick protection complete all as specified and directed. |
| 67 | Dehydration and filterationofexisting transformer oilusing transformer oil filteration plant to eliminate foreign particles and to improve di-electric strength upto 50 KV at 2mm electrode gap and to bring the acidity within the permissible limit complete all as specified and directed.Note :- Dehydration & filteration shall be done by using vehicle mounted setup cosisting of heating, filteration machine etcand oil shall be filtered/dehdrated in a closed circuit. |
| 68 | Supply & filling oil for distribution transformers for topping up/refillingtheoil having dielectric strength 40-60 KV during filling after initial filteration complete all as specified and directed. |
| 69 | M/L for painting of transformer up to 200 KVA capacity with good quality synthetic enameled paint using spray gun with compressed air on complete external portion of transformer including preparation of surface by scrubbing, cleaning ,stains greasy spots, dusts etc, The painting of transformer shall be carried out in situ ie. on four pole structure or in sub station at different places complete all as specified and directed. |
| 70 | Description ditto all as per srl item No 64 (here-in-before) but for capacity above 200 KVA up to 500 KVA complete all as specified and directed. |
| 71 | Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed. |
| 72 | Supply only PG clamps made out of brass suitable for connection of lugs with conductor to transformer LT and HT side bush rod to avoid direct connection of lugs with bush rod complete all as specified and as directed. |
| 73 | Material & labour in renewal for factory made precast RCC M-20 U-type drain of size 450mm width x 450mmdepth x 500mm length and wall thickenss not less than 75mm for E/M installation complete all as specified and as directed. |
| 74 | M & L of Acrylic sheet of 6 mm sheetincluding printing of line drawings/ Machine detailsas provided by Engr-Incharge/GE with size of 2 meter x 3 Meter of fixing arrangments at wall in E/M elect/ Water supply installations. Back ground of sheet should be in Blue in clolour complete all as specified & directed. |
| 75 | Supply and fixing in renewal of Hybrid solar street lights 50 watt capacity along with GI pIpeLight grade 50mm of height 9 metre fixing in PCCfoundation with (1:3:8) of that combines the use of solar energy and AC power. The lights use solar panels to charge a battery during the day, and then use the stored energy to power LED lights at night. They are also connected to the grid, which provides a backup power source in case the battery runs out of charge. The use of both solar and AC power allows these lights to have a longer operating time, especially during overcast days or in areas with less sunlight. The hybrid solar lights provide an efficient and reliable lighting solution that can save energy costs and also reduce the reliance on traditional power sources. Street lights with built in Mono Crystalline Panel, Lithium Ferro Phosphate (LiFePO 4) battery, MPPT charge controller , 50 watt capacity , 6000k, 150 lm/watt, complete all as specified and directed.Make: Bajaj , Wipro, Crompton, Philips.Note: (i) Cost of junction/ Polebox included in quoted rate.(ii) solar lights with GI pipe in cluding painting, fixing ,mounting deemed to be included in quoted rate. |
| 76 | Supply, installation, commissioning and testing in renewal of outdoor type, LT panel board of size 900 mm X 900 mm X 350 mm, CPRI approved factory made, powder coated suitable for 3 phase 4 wire 415 V, 50 Hz and provided with suitable \"U\" type gasket to make it dust/vermin proof & general construction confirming to IS: 8623/93, floor block mounting type made out of 3.15 mm thick CRCA sheet with using 45 mm X 45 mm X 5 mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front & back openable, lockable/ openable by keys from both sides louvers & air vent gasket for natural flow of air and to accommodate incoming/ outgoing MCCBs and TPN aluminium bus bar 400 Amp and alike complete all as directed & including fixing of undermentioned MCBs and alike as under:-(a) Ammeter size 96 mm X 96 mm, flush mounted digital type, three phase of class 1.0- 01 No.(b) LED Indicator lamp RYB- 01 No (c) Voltmeter size 96 mm X 96 mm, flush mounted digital type, three phase, class 1.0- 01 No.(Note: The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.) |