| 1 | (i) Providing IEIWiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed medium class PVCconduit, with modular switch, modular plate, suitable GI boxand earthing the point with 1.5 sq.mm FRLS PVC insulatedcopper conductor single core cable etc. as required.a)Group A |
| 2 | b) Group C |
| 3 | Wiring for twin control light point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface /recessed medium class PVC conduit, 2 way modular switch,modular plate, suitable GI box and earthing the point with 1.5sq.mm FRLS PVC insulated copper conductor single core cableetc. as required |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVCinsulated copper conductor single core cable in surface/recessed medium class PVC conduit along with 1 No. 4 sq. mmFRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.a) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | b) 4 X 10 sq. mm + 2 X 6sq. mm earth wire |
| 7 | Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing andfixing 3 pin 5/6 A modular socket outlet and 5/6 A modularswitch, connections etc. as required. |
| 8 | Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing andfixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 Amodular switch, connections etc. as required. |
| 9 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in theexisting surface/ recessed Steel/ PVC conduit as required.a)1 run of cable |
| 10 | Supplying and drawing following pair 0.5 mm dia FRLS PVCinsulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit asrequired.a)1 Pair |
| 11 | Supplying and fixing of following sizes of medium class PVCconduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessedconduit as required.a)20 mm |
| 12 | Supplying and fixing following size/ modules, GI box along withmodular base & cover plate for modular switches in recess etc.as required.a) 1 or 2 Module (75mmX75mm) |
| 13 | Supplying and fixing following piano type switch/ socket on theexisting switch box/ cover including connections etc. as requireda) Telephone socket outlet |
| 14 | b) RJ45 LAN Socket |
| 15 | Supplyingof surface mounted LED batten Fitting powder coated CRCA sheet for 20 Watt T8 Lamp similar to Luker Code LLTB with 20W Retrofit LED glass tube light Havells Cat No. CRYSTALT81213SSTL20WLED865SGLASS or its equivalent. |
| 16 | Installation,testingand commissioning of pre-wired,fluorescent fitting / compact fluorescent fitting of all types,complete with all accessories and tube/lamp etc. directly onceiling/ wall, including connections with 1.5 sq. mm FRLS PVCinsulated, copper conductor, single core cable and earthing etc.as required. |
| 17 | Supplying of BLDC Ceiling Fan 1200mm Sweep (Colour: White/Brown) similar to Orient Hector-500 BLDC, 5 Star & ISI without remote or its equivalent. |
| 18 | Supplying and fixing two module stepped type electronic fanregulator on the existing modular plate switch box including connections but excluding modular plate etc. as required |
| 19 | Installation, testing and commissioning of ceiling fan, includingwiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cableetc. as required |
| 20 | Supplying of Exhaust Fan 300 mm Sweep (Metal Type). Make:-Orient/Usha/ Bajaj/ Havells or its equivalent with the approval of Engineer-in-charge. |
| 21 | Supplying of Exhaust Fan 150mm Sweep with an automatic front shutter with low noise feature. Similar to USHA model:-Crisp or its equivalent. |
| 22 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioningetc. as required.a)Upto 450 mm sweep |
| 23 | Supplying and fixing of 400 mm Wall Fan similar to USHA Maxx air super wall fan:-400 mm or its equivalent with the approval of Engineer-in-charge. |
| 24 | Supplying and fixing PVC batten/ angle holder includingconnections etc. as required. |
| 25 | Supplying of 9W LED Lamp similar to Crompton, Cat No. LED 9W-B22-CDL or its equivalent as required. |
| 26 | Supplying and fixing of 15W LED round surface mounted down light similar to BajajCat No. BPSLR Surface 15W LED WH RD SD or its equivalent complete with all accessories etc. as required. |
| 27 | Supplying and fixing of Mirror Light 10W LED Batten (Integrated) fitting similar to BajajCat No. BCLSB 10W NW or its equivalent complete with all accessories etc. as required. |
| 28 | Supplying and fixingof surface mounted LED Bulkhead fitting similar to Polycab Code PLT0101316, Bulkhead 10W- BHE10W60,or its equivalent. |
| 29 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 30 | Supplying and fixing 3 pin, 5 A ceiling rose on the existingjunction box/ wooden block including connections etc. as required |
| 31 | Supplying and fixing of 100A, 415Vac, TPN Busbar Chamber with 4 o/g way on the wall, making connections, etc.as required similar to Indoasian, or its equivalent. |
| 32 | Supplying and fixing following way, horizontal type three poleand neutral, sheet steel, MCB distribution board, 415 V, onsurface/ recess, complete with tinned copper bus bar, neutralbus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But withoutMCB/ RCCB/Isolator)a) 8 way (4 + 24), Double Door |
| 33 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single Pole |
| 34 | Supplying and fixing following rating, four pole, 415 V, isolatorin the existing MCB DB complete with connections, testing and commissioning etc. as required.a) 63 A |
| 35 | Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2 mtr, outer dia 50 mm, inner dia 19 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok)(Proof/ Test Certificate should be enclosed) |
| 36 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 37 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 38 | Lighting ConductorsProviding and fixing of lightning conductor finial, made of 25mm dia 300 mm long, G.I. tube, having single prong at top, with85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 39 | Jointing copper / G.I. tape (with another copper/ G I tape, baseof the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 40 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet orsurface of wall for lightning conductor complete as required.(For horizontal run |
| 41 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet orsurface of wall for lightning conductor complete asrequired.(For vertical run) |
| 42 | (III)Solar Photo Voltaic Power Generation SystemSupply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:-a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency.c) Data Monitoring System complete with accessories.d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection.f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required. |