| 1 | M & L for Comprehensive maintenance forchilling package of (350X2=700 TR)Screwtype refrigeration Compressor with R134A refrigerant with Microprocessor panel and suction and Discharge control valves including one annual and threeperiodical inspection during the contract period at approximately equal intervals by the OEM and the maintennace programm will proceed as and when required as per the inspection report provided by company reprenstative and servicing of complete power supply system of the AC Plant including sub panels complete all as specified and directed by the engineer in charge. |
| 2 | M & L for Comprehensive maintenance forchilling package of (50X3=150 TR)Scroll type refrigeration Compressor with R407C refrigerant with Microprocessor panel and suction and Discharge control valves including one annual and three periodical inspection during the contract period at approximately equal intervals by the OEM and the maintennace programm will proceed as and when required as per the inspection report provided by company reprenstative and servicing of complete power supply system of the AC Plant including sub panels complete all as specified and directed by the engineer in charge. |
| 3 | NOTE FOR SERIAL ITEM NO 01 & 02 ABOVE:-(a)Contractot should make AMC with OEM only, any requisite electrical/Mechenical parts etc for Chilling package catered in item No 1 & 2above or any other parts also are to be repair / replaced as & when it become unserviceable as per terms & conditions of AMC with OEM, of above chilling package under he AMC \"A\" type Contracts and material & Labour charge will shall be deemed to be included in quoted rate.(b) Contractor shall also enter into an agreement (MOU) with the OEM carrying out comprehensive maintenance of chilling package catered in item No 1 & 2 above and shall submit the agreement to the Garrison Engineer.(c)Carry the proper functioning of microprocessor panel and take the control test (d) Check the electrical panels for tripping, overheating, chattering in electrical partsand terminals for proper tightness.(e Check for proper working of all Ammeters, voltmeters, Hour mtrs, KWH Mtrs and overload relays,fan belt etc and replacing the same if found unserviceable(f) Checking the operation of MCCB\"s up to 250 Amps, MCB, Isolators, etc and replacing the same if found unserviceable. Proper load balancing should be carreid out by the contractor of electric supply system to the chiller machines and necessary arrangements will be carried out for measurement of electric load in all phases by the contractor at no additional cost and the subject report of load in the electrical panel will be submitted at the time of inspection report of the chillers.(g) Clean electrical panels and chiller machine periodically.(h) Check functioning of water flow switch and interlock in the system.(j) Check all safety and operating controls for proper functioning and replace if the same is defective for proper sequence of operation of the machine |
| 4 | (k) All the breakdowns including compressor failure will be attended and the visit shall not be counted in periodical inspection.(l) Check refrigerant filter and drier core, replace the same , if found necessary.(m)Check oil level and oil heater in the system.(n) Check chilled water flow by checking pressure drop across the chiller(o) Check evaporator and condenser approach and compare the chilled water temperature at full load with the chilled water temperature control(p) Seasonal adjustment of controls if required and software upgrade (q) Inspect entire system for any unusual condition such as noise, vibration etc(r) Supply of electrical parts except electrical spares for incoming panel. (Electrical Spares Like:- fuses, incoming electrical controls, flexible wire, All type of starter parts including wiring etc)(s) All changes/ repair shall be valid only after satisfaction of Engr-in-charge/GE. Contractor shall submit all related documents of expenditure of AMC time to time to avoid delay on payment(t) Checking theoperation of all suction and discharge control valves etcIf found faulty /leakage to be replaced by the contractor with out any extra cost.(u) Filling of oil.(v) The contractor shall also arrange require tools for attend routine services/minor breakdown call like an adjustable spanner, clamp meter, pressure gauge with garging line, digital tamperature gun, fix spanner set, Allen key set, serew driver set, cotton waste software support if require. |
| 5 | (w) The contractor shall also arrange require equipment\"s for attend major breakdown call like as a vaccum pump, Digital Vaccum gauge, Refrigerant recovery unit, Empty refrigerant cylinders, dehydration tank and require spanners.(x) clean the cooling tower and Drain the water and clean the sump of cooling tower, Clean pot stainer/y-stainer, check the condition of fills, if required, clean the fills with detergent, check for operation of shut off valves.(y) If AC Plant have occur any breakdown take immediate action arrange to provide all necessary material, T&P and labour, unable to provide material and delay in smooth operation/working of AC Plant/AHU etc recovery will be done on the based of Rs.3000/- per hourNote:- Descalingof condenser and chiller tubes, Checking leakage of refrigerant and nitrogen pressure testing including nitrogen,Gas (Refrigerant), Temperature sensor,Bellows, Differential pressure switch unit, Expansion Valve, Compressor Oil, Servicing ofSecondary pump, Servicing of primary & Secondary pump, Servicing of chiller water pumps/condensor water pump, Servicing of blowers for AHU\"s with induction motor,single phasing preventor, electronic timer will be under items of BOQ. |
| 6 | M & L for Descalingof 350X2=700 TR (chemical cleaning and physical cleaning) of condenser and chiller tubes all as specified and directed by Engr-in-Charge. |
| 7 | M & L for Descalingof 50X3=150 TR (chemical cleaning and physical cleaning) of condenser and chiller tubes all as specified and directed by Engr-in-Charge. |
| 8 | M & Lfor Checking leakage and shortage of refrigerant in the machines of 350X2=700 TR/ 50X3=150 TR with soap solution and rectify the system defect causing leakage rectification including topping up of refrigerant. If leakage is not rectified by the soap solution then nitrogen pressure testing will be carrid out to identify the refrigerant leakage through the chiller machine and refilling/topping up of refrigerant. Amount quoted by the contractor should be inclusive of cost of nitrogen pressure testing including Nitrogen complete all as specified and directed by Engr-in Charge |
| 9 | Supply& filling Gas R134A/ R407C of 350X2=700 TR/50X3=150 TR unit for AC Plant complete all as specified and directed by Engr-in Charge |
| 10 | Supply and fix in repair Temperature chilled water sensor/Temperature cooling water sensor as per exsisting sample ofAC Plant complete all as specified and directed by Engr-in Charge |
| 11 | S & F in repairBellows of size 250x200 mm as per existing complete all as specified and directed by Engr-in Charge. |
| 12 | S&F in repair differential pressure switch unit as per exsisting sample of350X2=700 TR/ 50X3=150 TR Ac plant complete all as specified and directed by Engr-in Charge. |
| 13 | S & F in repair Expansion Valve as per exsisting sample including all connected accessories of AC Plant complete all as specified and directed by Engr-in Charge. |
| 14 | Supply& fillingCompressor Oil of AC Plant complete all as specified and directed by Engr-in Charge. |
| 15 | M&L for servicing of back pull out primary chilled water pump with induction motorof Cap- 20 HP operated on 240V, 50 Hz with replacing of diffective parts such as box, mechanical seal , cut off switch, bearing , complete all as specified and directed by Engr-in-charge. |
| 16 | M&L for servicing of back pull out Secondary chilled water pump with induction motorof Cap- 30 HPoperated on 240V, 50 Hz with replacing of box set-04 nos, mechanical seal -01 no, cut off switch 01 no, bearing 02 nos, Air filling in tank complete all as specified and directed by Engr-in-charge. |
| 17 | M&L for servicing of back pull out condensor water pump with induction motorof Cap- 40 HP operated on 240V, 50 Hz with replacing of diffective parts such as box, mechanical seal , cut off switch, bearing , complete all as specified and directed by Engr-in-charge. |
| 18 | M&L for servicing of back pull out chiller water pumps/condensor water pump with induction motorof Cap- 5 HPoperated on 240V, 50 Hz with replacing of box set-04 nos, mechanical seal -01 no, cut off switch 01 no, bearing 02 nos, Air filling in tank complete all as specified and directed by Engr-in-charge. |
| 19 | M&L for servicing of blowers for AHU\"s with induction motorof Cap- 10 HPoperated on 240V, 50 Hz with replacing of diffective parts such as box, mechanical seal , cut off switch, bearing , Fan Belt complete all as specified and directed by Engr-in-charge. |
| 20 | Note for item No.13 to 17 : Following are deemed to be included in quoted rate. |
| 21 | (a) Check the alignment and conditions of coupling to prevent damage to shaft and impeller. |
| 22 | (b) Lubricate bearings with grease guns. |
| 23 | (c) Replace gland thread if required. |
| 24 | (d) Check lubricant oil level and make up the oil if required. |
| 25 | (e) Check packing and mechanical seals for leakage. |
| 26 | (f) Half yearlyinspection and service for pumps |
| 27 | (g) Inspect shaft sleeves,shaft, bearings , bearing housing and overhauling of all pumps. |
| 28 | (h) The impeller and shaft to be repaired and made functional. If they are found not repairable, then same will be replaced . |
| 29 | (i) The packing, mechanical seal, bush, bearing, Shaft sleeves, couplingFan belt etc. If found faulty to be replaced by the contractor with out any extra cost. |
| 30 | M&L for taking out & rewinding the existing unserviceable burnt motors of condensor/chillerwater pumps (Pressure pumps) of Cap 5 HP,Three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantlingthemotor and removing the old burnt copper winding & demoisturise, cleaning, rewindingthecoilswith same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, andreassembling by replacing bearings reinstalling at the installation andtesting, commissioning etc complete all as specified and directed by Engr-in-charge. |
| 31 | M&L for taking out & rewinding the existing unserviceable burnt motors of condensor/chillerwater pumps (Pressure pumps) of Cap 10 HP,Three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantlingthemotor and removing the old burnt copper winding & demoisturise, cleaning, rewindingthecoilswith same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, andreassembling by replacing bearings reinstalling at the installation andtesting, commissioning etc complete all as specified and directed by Engr-in-charge. |
| 32 | M&L for taking out & rewinding the existing unserviceable burnt motors of condensor/chillerwater pumps (Pressure pumps) of Cap from 20 HP,Three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantlingthemotor and removing the old burnt copper winding & demoisturise, cleaning, rewindingthecoilswith same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, andreassembling by replacing bearings reinstalling at the installation andtesting, commissioning etc complete all as specified and directed by Engr-in-charge. |
| 33 | M&L for taking out & rewinding the existing unserviceable burnt motors of condensor/chillerwater pumps (Pressure pumps) of Cap from30 HP,Three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantlingthemotor and removing the old burnt copper winding & demoisturise, cleaning, rewindingthecoilswith same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, andreassembling by replacing bearings reinstalling at the installation andtesting, commissioning etc complete all as specified and directed by Engr-in-charge. |
| 34 | M&L for taking out & rewinding the existing unserviceable burnt motors of condensor/chillerwater pumps (Pressure pumps) of Cap from 40 HP,Three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantlingthemotor and removing the old burnt copper winding & demoisturise, cleaning, rewindingthecoilswith same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, andreassembling by replacing bearings reinstalling at the installation andtesting, commissioning etc complete all as specified and directed by Engr-in-charge. |
| 35 | M & L for spray oil painting of AC plant including motor, pipe colling tower etc on existing colour complete all as specified and directed by Eng-in-charge. |
| 36 | M & L forCondensor and eddy current test complete all as specified and directed by Eng-in-charge. |
| 37 | M & L forEvaporator and eddy current test complete all as specified and directed by Eng-in-charge. |
| 38 | Supply and fixing drier filter core suitable for 350 TR chilling package complete all as specified and as directed by Eng-In-Charge. |
| 39 | Supply and fixing oil filter suitable for 350 TR chilling package complete all as specified and as directed by Eng-In-Charge. |
| 40 | Supply and fixing O ring suitable for 350 TR chilling package complete all as specified and as directed by Eng-In-Charge. |
| 41 | Supply and fixing Angle valve suitable for 350 TR chilling package complete all as specified and as directed by Eng-In-Charge. |
| 42 | Supply & fixin repair/replacement MCCB 3 pole 630 Amp, 50 KA, 415 volts 50 Hz including operating handle complete all as specified and directed by Eng-In-Charge. Make:- HPL |
| 43 | Supply & fixin repair/replacement MCCB 3 pole 250 Amp, 36 KA, 415 volts 50 Hz including operating handle complete all as specified and directed by Eng-In-Charge. |
| 44 | Supply & fixin repair/replacement MCCB 3 pole 125 Amp, 16 KA, 415 volts 50 Hz including operating handle complete all as specified and directed by Eng-In-Charge. |
| 45 | S&F in replacement of Thermometer guage with connected assembly as per exsisting sample including all electrical conections, testingcomplete all as specified and directed by Engr-in-charge. |
| 46 | S&F in replacement of AHU Micro Fiber Primary HEPA filter as per exsisting sample including allconections, testingcomplete all as specified and directed by Engr-in-charge. |
| 47 | M & L for repair of Motor starter of any type, carrying out repair and including replacement of defective minor spare parts such as connector, burn control copper cable, insulator, Terminal block, copper thimbles, NO NC aux blockand ON/OFF push button etc or if any other required minor spare parts at site for including testing to ensure efficientand smooth functioning of startercomplete all as specified and directed by Engr-in-charge. |
| 48 | S&F in repair contactor ofAC3, 10/20A 415 Volt, 50 Hz as per exsisting sample including all electrical conections, testingcomplete all as specified and directed by Engr-in-charge. |
| 49 | S&F in repair contactor ofAC3, 32/40A 415 Volt, 50 Hz as per exsisting sample including all electrical conections, testingcomplete all as specified and directed by Engr-in-charge. |
| 50 | S&F in repair single phasing preventor as per exsisting sample, including all electrical conections, testingcomplete all as specified and directed by Engr-in-charge. |
| 51 | S&F in repair electronic timeras per exsisting sample, including all electrical conections, testingcomplete all as specified and directed by Engr-in-charge. |
| 52 | S&F in repair overload relay, 14-23A 415 Volt, 50 Hz as per exsisting sample including all electrical conections, testingcomplete all as specified and directed by Engr-in-charge. |
| 53 | S&F in repair overload relay, 24-40A 415 Volt, 50 Hz as per exsisting sample including all electrical conections, testingcomplete all as specified and directed by Engr-in-charge. |
| 54 | Supply and fix in repair of puff insulation as per site requirement for chilled water piping and valves all as specified and diected by Engr-in-Charge |
| 55 | M & L for Comprehensive maintenance forchilling package of (72X2=144TR)Scroll type refrigeration Compressor (Model No.ACWCDS078DPMN3X2D Make-Voltas Ltd) with R407C refrigerant with Microprocessor panel and suction and Discharge control valves including quarterly visits and monthly periodical inspection with any nos of visits for attending emergency breakdowns of AC Plant during the contract period at approximately equal intervals by the OEMand the maintennace programme will proceed as and when required as per the inspection report provided by company representative and servicing of complete power supply system of the AC Plantcomplete all as specified and directed by Engr-in-charge. Following are deemed to be included in item in quoted rate :- |
| 56 | Descaling of condenser and chiller tubes to meet the designed specifications of flow of refrigerant in compressor and water in condenser. Descaling will be measured and paid under respective item of this schedule. |
| 57 | Check leakage and shortage of refrigerant in the machines with soap solution and rectify the system defect causing leakage including topping up of refrigerant.Cost of Refrigerant required for topping up will be measured and paid separately under respective item of this schedule. |
| 58 | Carry the proper functioning of microprocessor panel and take the control testquaterly and the report needs to be submitted at the time of RAR. |
| 59 | Monthly Checking for proper working of all Ammeters, voltmeters, Hour mtrs, KWH Mtrs and overload relays etc and replacing the same if found unserviceable |
| 60 | Monthly Cleaning of electrical panels and chiller machine periodically. |
| 61 | Monthly Checking of functioning of water flow switch and interlock in the system. |
| 62 | Monthly Checking of all safety and operating controls for proper functioning and replace if the same is defective for proper sequence of operation of the machine |
| 63 | All the breakdowns including compressor failure will be attended and the visit shall not be counted in periodical inspection. |
| 64 | Monthly Checking ofrefrigerant filter and drier core, replace the same , if found necessary. |
| 65 | Monthly Checking of oil level and oil heater in the system and top-up the oil if found necessary. |
| 66 | Monthly Checking of chilled water flow by checking pressure drop across the chiller |
| 67 | Monthly Checking of evaporator and condenser approach and compare the chilled water temperature at full load with the chilled water temperature control |
| 68 | Seasonal adjustment of controls if required and software upgrade once during the contract period |
| 69 | Inspect entire system for any unusual condition such as noise, vibration etc Contractor should be responsiblefor providing the itemsto the operators such as cotton waste, grease, oil, insualtion tape, temperature record instruments for AC, tool kit Ref Mect , Hand gloves, discharge Rod upto 11000 Volts, pipe wrench up to 300mm, taflon tape, Earth tester, multimeter, tounge tester respectively,fiirst aid kit with standard kit , proper sitting arrangement to operator at installation, torch light with cell , cleaning material etc all as directed by Engr-in-Charge |
| 70 | Supply of electrical parts except electrical spares for incoming panel. (Electrical Spares Like:- fuses, incoming electrical controls, cables etc) |
| 71 | Note: for item no 43 :-(a)Contractot should make AMC with OEM only, any requisite electrical/Mechenical parts for Chilling package catered in item No 43above or any other parts also are to be repair / replaced as & when it become unserviceable as per terms & conditions of AMC with OEM of above chilling package under the AMC \"A\" type contracts and material & Labour charge shal be deemed to be included in quoted rate.(b) Contractor shall also enter into an agreement (MOU) with the OEM carrying out comprehensive maintenance of chilling package catered in item No 43 above and shall submit the agreement to the Garrison Engineer.(c) The contractor should be responsibleto maintain the AC Plant in serviceable condition for entire contract period & additionalworn out spare parts of chilling water pumps and condenser pumps like couplings, belts, screws/fixing bolts, pipe, refrigerant & condensed water pressure gauges etc if foundunserviceable should be replaced by contractor without any additional cost .(d) Proper servicing certificate should be produced immediately after servicing(e) The authorised technician should visit once in two monthsfor preventive maintenance & any no of emergency breakdown. (f) No addition labour payment shall be entertained for replacement of any exclusive part of plant. |
| 72 | Note: for item no 43 :-(g) All type of valves including float valve, quick fill valves, drain valves and other associated items like gear box, strainer, eliminators if found faulty will be provided by the contractor at no additional cost (h) Repairs of FRP Cooling Tower/basin and replacement of HUB, blades of fan, fills, nozzle and distribution channels if found necessary will be done by the contractor at no additional cost(j) This is type \"A\" AMC i.e. \"ALL IN ALL\" (k) Quoted Rate should include repair and Maint before AMC (Pre AMC). (l) complaints should be attended and rectified in 24 hr otherwise a penalty of rupees 5000.00 Rs per day will be recoverd from the contractor. |
| 73 | Material and labour for maintenance and servicing of the chilled water motor pump assembly complete of cap 7.5 HP including replacement of all worn out belts of specified size, replacement of motor gaskets and greasing to moving parts all as specified and directed by Engr-In-Charge |
| 74 | Material and labour for maintenance and servicing of the condensor water motor pump assembly of cap 10 HPincluding replacement of all worn out belts of specified size, replacement of motor gaskets and greasing to moving parts all as specified and directed by Engr-In-Charge |
| 75 | Material and labour for maintenance, servicing of motors of AHU\"sof Cap10 HP with blowers including replacement of all worn out belts of specified size, replacement of motorgaskets and greasing to moving parts complete all as specified and directed by Engr-In-Charge |
| 76 | Note for item No 44 to 46 : following are deemed to be included in quoted rate :- |
| 77 | (a) Checking the alignment and conditions of coupling to prevent damage to shaft and impeller. |
| 78 | (b) Lubricate bearings with grease guns. |
| 79 | (c) Replace gland rope if required. |
| 80 | (d) Check lubricant oil level and make up the oil if required. |
| 81 | (e) Check packing and mechanical seals for leakage. |
| 82 | (f) Half yearlyinspection and service for pumps |
| 83 | (g) Inspect shaft sleeves,shaft, bearings , bearing housing and overhauling of all pumps. |
| 84 | (h) The impeller and shaft to be repaired and made functional. If they are found not repairable, then same will be replaced . |
| 85 | (j) The packing, mechanical seal, bushs, bearings, Shaft sleeves, coupling etc. If found faulty to be replaced by the contractor with out any extra cost. |
| 86 | M&L for taking out & rewinding the existing unserviceable burnt motors of condensor/chillerwater motors of Cap 10 HP,Three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantlingthemotor and removing the old burnt copper winding & demoisturise, cleaning, rewindingthecoilswith same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, andreassembling by replacing bearings reinstalling at the installation andtesting, commissioning etc complete all as specified and directed by Engr-in-Charge |
| 87 | M & L for Cleaning and spray Painting the surface of motors, condenser pipes, chilled water pipes, cable duct supports of angle iron and all other rough surfacesincluding all valves and fittings including pumps and cooling Tower with two coats of synthetic enamel paint of existing colour over a neat coat of redoxide primer over 10 cm width of girth and making good to the surfaces of all pipe and valves connections at certain places all as specified and directed by Engr-In-Charge |
| 88 | Supply and fix in repair of puff insulation as per site requirement for chilled water piping and valves all as specified and diected by Engr-in-Charge |
| 89 | M & L for Descaling of condenser tubes required to meet the designed pressure conditions and cooling specifications for desired rate offlow of refrigerant in compressor and water in condenser complete all as specified and directyed by Engr-In-Charge |
| 90 | M & L for Nitrogen Pressure testing for water cooled screw chillers including refrigerant Recovery, vacummising and recommissioning of chillers of condenser tubes required to meet the designed pressure conditions and cooling specifications for desired rate offlow of refrigerant in compressor and water in condenser complete all as specified and directyed by Engr-In-Charge |
| 91 | S&F in repair Refrigerant R407 C for topping up of refrigerant in the sytem to compensate any leakge qty of refrigerant. Complete all as specified and directed by Engr-in-Charge |
| 92 | S&F in repair thermometers as per site requirement to be fixed in chiller lines and condensor pipe lines complete all as specified and directed by Engr-In-Charge |
| 93 | S&F in repair automatic star delta starter in sheet steel enclosure AC-3 duty, 415 V, 10 HP,with ralay range 15-30 Acomplete all as specified and directed by Engr-In-Charge |
| 94 | Supply & fix in repair Contactor type- MCX13 of AC3 80 Amp, 415V, 50 Hz , Complete all as specified and directed by Eng-In-Charge |
| 95 | S&F in repair single phasing preventorType-ESP-2 , 415 Volt, 50 Hz . Complete all as specified and directed by Eng-In-Charge |
| 96 | S&F in repair electronic timerType-S/D-C-100 , 230/415 Volt,Complete all as specified and directed by Eng-In-Charge |
| 97 | M & L forRepairing / Servicing of complete all electric supply panels for AHU Rooms by cleaningall MCCB Connections and Bus barswith anti rust spray, replacing of nuts & bolts,washers, with suitable lugs of burnt/rust contacts & fitting of screws & rewiring with suitable guage copper conductor/flexible wires, all as required as per ground condition, with tightening of all loose connections, with testing complete on load all as directed by Engr-in-charge. . |
| 98 | S&F in repair pressure gauges 100 mm dia for condensor water lines and chiller water lines ,Complete all as specified and directed by Eng-In-Charge |
| 99 | Supply & fixin repair MCCB 4 pole 250 Amp, 25 KA, 415 volts 50 Hz including operating handle complete all as specified and directed by Eng-In-Charge. |
| 100 | Supply & fixin repair MCCB 4 pole 125 Amp, 16 KA, 415 volts 50 Hz including operating handle complete all as specified and directed by Eng-In-Charge. |
| 101 | Supply & fixin repairMCCB 4 pole 100 Amp, 16 KA, 415 volts 50 Hz including operating handle complete all as specified and directed by Eng-In-Charge. |
| 102 | Supply & fixin repair MCCB 4 pole 160 Amp, 25 KA, 415 volts 50 Hz including operating handle complete all as specified and directed by Eng-In-Charge. |
| 103 | M&L for repair of cooling tower PVC finse AC plant 144 TRcomplete all as specified and directed by Engr-in-Charge. |
| 104 | In case of any break down of AC plant/AHU etc the contractor shall take immediate action and arrange all necessary material, T&P and manpower to smooth operation/working of AC plant/AHU etc, otherwise penalty will be levised on account of non operation of the same @ Rs 10,000/- per hour till smooth functioning of AC plant/AHU etc and same will be recovered from contractor\"s dues. |