| 1 | Dismanting and removingexisting unserviceable central air conditioning AC plant having 3 X 30 TR capacity units with compressor, compressor motor, condenser, condenser water pump chiller with motor and all connection water pipe lines, cooling tower, AHU and ducting electrical control panel etc and depositing in MES store yard and making good disturbed surfaces of floor, roof etc complete all as specified and as directed. |
| 2 | Supply,installation,testingandcommissioningofWater Cooled Brine Scroll chiller unit total 03 ( 2 working + 1 standby) including PCC foundation, each having minimum capacity 30 TR with scroll compressor energy efficient and eco friendly R-410a / R-407 refrigerant and Chiller must be capable with MODBUS or BACNET Protocol(A)Mode:(i)Auto/Manual(ii)Singlephasingprotection(iii)Compressorrestart protection (iv) 10- sec time delay between system (v) Short circuit protection 5 degree C - Anti feeze protection (vi)Display on micro control indicating (vii) Display on micro control indicating compressor on/off(B) Refrigerant:(i) R-410a or any other non CFC/ non HCFC gas.(ii) Actual capacity as per ambient condition(C) Chiller:(i)Chilledwaterinlettemp.05degreeC(ii)Chilledwateroutlettemperature0 degree C |
| 3 | (D) Condensor :-(i) Condensor water inlet temp 32 degree C(ii) Condensor water outlet temp. 36 degree CNote:- (a) Plant offered by the tenderermust confirm to meet the desired condition as per the User requirement is Temp 15 to 22 Degree and RH50 % (+- 5%).(b) The water flow rate in GIN areappropriate & minorvariationasperOEMdesignofthechillerisacceptablewhilemeetingother criterias.(c) Inlet and outlet temp. conditions for the condenser water are appropriate and minor variation as per the design of equipment by OEM is allowed. (d) The system integratio shall be done and achieve the design condition as per given data sheet.(e) Making of all necessary civil foundation for equipments as pumps, panel, chiller, HWG, CT, AHU etc. Making opening and repairing of the sameas per OEM recommendation is included in unit rate quoted under this item. |
| 4 | Supply, Installation, testing and commissioning of 37 TR Cooling tower (03 Nos)induced draft top discharge counterflow type butonlang Tower of sufficient structural strength to withstand vibrations and wind velocity upto 60 m/s, (Rectangular/Round bottle shape), heat rejection capacity with uniform water distribution and optimal heat transfer with FRP body and base, water spray headers, cooling tower fills, fan with motor, supporting base frames, inlet valve with float assembly, overflow with drain connection with valve and complete fan motor energy efficient induced draught axial type fans with factory set and dynamically balanced blades pitch, IE3 TEFC squirrel cage induction motor, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 65 protection for enclosure, conforming to IS 12615 2018, ASHRAE standard 90.1-2014 & NFPA 214, FRP induced draft type CT of water from 97.5°F to 90° F at the design ambient wet bulb temperature of 83° F and the cooling tower shall be complete with casing hot water distribution system, fill, intake louver/drift eliminator(as applicable), fan assembly with fan & motor, FRP cold water water basin, Gi ladder, guard rail, direct drive, safety guard, SS sprinklers and non-clogging sprinkler pipes with necessary fittings viz necessary make up, quick fill, drain, over flow etc complete all as specified and as directed.Note:-(a). The cooling tower shall be assembled and fitted in presence of company representative and shall be tested as per company specifications.(b) Any spares required for assembling the cooling tower like nuts, bolts, rivets, gaskets etc shall be provided by the contractor and rates of the same are included in n quoted rate.(c) Rate quoted by the contractor shall be inclusive of foundation as per OEM recommendation |
| 5 | Water circulation Pumps : Supply,installation, testing and commissioning of vertical split casing end suction close coupled type water pump sets with factory mounted on a common base frame with electric motor for recirculation of chilled/ hot/ condenser water for the air-conditioning system. All pumps shall be aligned.The pump motor shall be IE-3&suitablefor415_+10%V,50cycles, 3 phase power supply.Theqoutedrates shallbe inclusive ofits insulation and cladding. Pumpperformancecharacteristics shall be as follows as per drawings and specifications. as mentioned below:- |
| 6 | Chiller waterPrimary Pumps (Qty 3 Nos):- Supply & fixing of chilled water mono block pump of capacity 5 HP ( 2 W, 1S), head 24 to 30 m having C.I. body, SS shaft & bronze impeller, Water flow Rate: 60US GPM complete all as specified and as directed. |
| 7 | Chilled water secondary Pumps with control panel & VFDs (Qty 3 Nos):- Supply & fixing of chilled water mono block pump of capacity 5 HP ( 2 W, 1S), head 24 to 30 m having C.I. body, SS shaft & bronze impeller, Water flow Rate: 60US GPM complete all as specified and as directed. |
| 8 | Condensorwaterpump(Qty3Nos):- Supply&fixing of condensor water mono block pump of capacity 5 HP (2W, 1S), head 14 to 24 m having C.I. body, SS shaft & bronze impeller, Water flow Rate: 105 US GPM complete all as specified and as directed. |
| 9 | Hot waterpump(Qty3Nos):-Supply&fixing of condensor water mono block pump of capacity 5 HP (2W, 1S), head 14 to 24 m having C.I. body, SS shaft & bronze impeller, Water flow Rate: 30 US GPM complete all as specified and as directed. |
| 10 | HOT WATER GENERATOR:- Supply, Installation, testing and commissioning of new Hot water Generator set of capacity 36 kW Vertical indoor type, working pressure 100, seamless copper tube, electric immersion (water resistance) type heater, test pressure 250, auto step controller, high/low level cut-off, water flow rate-103.2LPM, water holding cap-40ltr, 50mm resin bonded fiber glass wool insulation, 0.6mm aluminium sheet clading with all connected accessories, control panel accessories etc complete all as specified and as directed |
| 11 | AIR HANDLUNG UNIT: Supplying, installing, testing and commissioning of double skin Floor Mounted Air Handling Unit of nominal capacity-22500 CFM with insulated panel- 25mm thick, CFC free PUF injected of 40kg/Cum denisity 0.6mm pre coated Gl outer skin & 0.6 mm Plan Gl inner skin with 25mm thick hollow extruded Al profile with smart AHU Controllers) ( IP-55 and class F Insulation VFD compatible) along with all fixing accessories, angle iron work for base frame and necessary PCC work complete all as specified and directed by Engr-in-Charge and comprising of following:(a) EC fan section shall be equipped with a Single Inlet Centrifugal Impeller with High Efficiency Backward curved blades and external rotor EC (Electronically Commutated) motor, energy optimized for operation without spiral housing for high efficiency and favorable acoustic behavior. The high efficiency backward curved impeller made of welded aluminium sheet/ high performance composite material, with external rotor motor balanced together statically and dynamically according to DIN ISO 1940. The EC fan should be capable of being fitted in horizontal or vertical position in the AHU, depending on the application including with internal wiring.(b) 50mm thick Pre filter (EU-4) in supply air stream with efficiency 90% down to 10 micron & Media of filter-synthetic(non woven type) |
| 12 | (c) AHU with 6 row deep Chilled water cooling coil & 2 row deep Heating coil(AHRI certified as per test standard ARI-410 & UL Certified for safety)with plain aluminium fins of 0.15mm thickness (11/12 Nos of Fins per inch for CHW coil & 8/10 Nos of fins per inch for HW coil) unless specified otherwise Tube material shall be copper with dia of tube 12.7mm & thickness of tubes-0.41mm Coil casing/blank offs will be provides of Gl material. 20 Gauge SS304 tray duly insulated with 13 mm closed cell nitride insulation. Header material will be MS and unit base will be G.S.S. base channel. Drain pipe dia shall be 50mm with U-trap of same size.(d)The minimum efficiency class of the motor shall be equivalent to IE3. The motor shall be Permanent magnet external rotor motor with integrated electronics and suitable for continuous operation. The speed of the motor shall be varied with an external 0-10V/PWM control signal. The fan in totality shall be of most efficient type so that the power Consumption and noise level is minimal. The motor shall be minimum IP55 protection class.(e) Controller module with RS 485 port compatible with BMS, on board protocol following(i). EC fan operation status(ii) Chilled water valve operation status(iii). AHU Airflow (CFM)(iv) AHU power consumption(v). Controller shall also have fire trip alarm to shut AHU in case of signal from fire panel |
| 13 | (f) suitable Instrumentation measurement Kit also included in this quoted rate which will be provided by contractor without extra cost following:-(i). Supply and return air temperature kit with(ii). Chilled water in and out temperature kit with temp sensor(iii) DP switch across filter for filter clog(iv) DPT(v). Microprocessor controller with 7 inch touch screen HMI(vi). Suitable size of PICBU with connected accessories and control cable(vii). Air differential pressure switch(viii) Air differential pressure Transmitte(ix) Control Panel (BMS) for control/ Viewing above data (x) Temperature & Humidity sensor(xi) Provision for humidifer piping(g) Minimum 20-25 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. The Maximum Static not more than 65 MMWG(h) From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wirning from Terminal Box to multiple direct drive motors provided by contractor and shall be provided with factory fitted Electrical in AHU Casing Manual operated Supply air Damper with GI Construction.Note:- Contractor will submit AHU data and specification with parameters before place order of AHU for accepting |
| 14 | Air Distribution System/ Duct Work (Factory made/ Site Fabricated): Designing, supplying, fabrication, installation and testing of GSS sheet metal ducting complete with TDF flange rectangular/square duct made out of \"L\" shaped hollow profile, duly factory boxed, incl all accessories such as Comer, Cleat, Carriage bolt, EDPM rubberGasket and appropriate sealant on longitudinal joints etc complete with spliter damper, duct damper, vanes etc fabricated out of galvanised sheet class VII 120gm/ sqm zinc coating conforming to IS 277&IS 655 all as required and as per IS specification, complete with Gl nut bolts, supporting Structure, MS angle & rods work etc and as per approved drawings complete all as specified and directed for the following gauge:-Note: (i). The cost is inclusive of duct with reinforcement/ strengthening, ait tight joints including accessones painting with black colour paint for duct sides behind the grills (ii) The gasket should used in case for all duct shall be fire retardant type. |
| 15 | 24 SWG |
| 16 | 22 SWG |
| 17 | THERMAL DUCT INSULATION :-S & F of FM approved highly- flexible, closed-cell class O nitrile rubber elastomeric thermal insulation of elastomeric foam based on synthetic rubber (NBR), laminated with 12 micron aluminium foil facing with reinforced glass scrim tested for service temperature range 0-105 °C as per EN 14706, EN 14707 & EN 14304, thermal conductivity λ ≤ 0.037 W/mK at mean temperature θm = 20 °C as per EN 12667 & EN ISO 8497, water vapour diffusion resistance factor μ ≥ 12000 as per EN 12086 & EN 13469, water absorption by volume 0.2% as per ASTM C 1763 & ASTM C 209, Class 0 fire performance as per BS 476 Part 6: 1989, Class 1 surface spread of flame as per BS 476 7: 1997, flammability HB V-0 as per UL-94, having good resistance to mechanical impact, excellent resistance to ozone, oil and chemicals, zero ozone depletion potential along with adhesives and other necessary accessories having 13 mm thick thermal insulation (ForSupply/Return air duct) complete all as specified and directed. |
| 18 | CHILLED WATER PIPING: Suppy and laying of MS pipe, Class \"C\" confirming to IS 1239/3589, heavy class,chilled water piping including necessary fitings viz. bends tees, reducers, flanges, drain valves, strutural support, nessary clamps, vibration isolator duly insulated with insulation of External thermal insulation with Closed Cell Class O Nitrile Rubber Elastomeric Insulation of 25 mm thick Density 40-55 Kg/m3, Thermal Conductivity of 0.037 W/mk at 200 Celcius Mean Temp. and μ≥7000 (without any additional vapour bamer) and with Factory Laminated aluminium foil of minimum 60 microns thickness to be applied on MS Chilled water pipe using manufacturer\"s recommended Rubber based Adhesive in a blend of solvents complete and finally finished with 26 gauge aluminium sheet complete Pipe in excavated trenches or on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with necessary accessories complete all as specified and directed for following bore of pipe:-.Note: The cost of nitrile insulation and cost of MS pipe pipe included in the above relevant quoted rate |
| 19 | MS Pipe 100mm bore |
| 20 | MS Pipe 80mm bore |
| 21 | MS Pipe 65mm bore |
| 22 | MS Pipe 50mm bore |
| 23 | MS Pipe 40mm bore |
| 24 | CONDENSER WATER PIPING:- Supply, laying/fixing, testing and commissioning of MS pipe, Class \"C\" confirming to IS 1239/3589 completecondenser water piping including necessary fittings viz bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting/fixing the pipe in excavated trenches or on floor/wall/ ceiling with clamps, hangers, angles channels (using anchor fastners) with necessary accessories complete all as specified and directed for following bore of pipe:- |
| 25 | MS Pipe 100mm bore |
| 26 | MS Pipe 80mm bore |
| 27 | MS Pipe 65mm bore |
| 28 | MS Pipe 50mm bore |
| 29 | MS Pipe 40mm bore |
| 30 | Supply and fixing cast iron butter fly valves lever operated SS disc type nitrile/EPDM rubber lining PN 1.6 ofcomplete all as specified and directed for following sizes:- |
| 31 | 80mm bore |
| 32 | 65mm bore |
| 33 | 50mm bore |
| 34 | Supply and fixing cast iron Y strainer flanged ends with SS perforated sheet screen of complete all as specified and directed for following size:- |
| 35 | Size 80mm |
| 36 | Size 65mm |
| 37 | Size 50mm |
| 38 | Supply and fixing cast iron non retum valves ofpressure class PN 1.6 including nuts, bolts, washers, gaskets, etc for Central type AC plants complete all as specified anddirected for following sizes:- |
| 39 | 80mm bore |
| 40 | 65mm bore |
| 41 | 50mm bore |
| 42 | Supply, Installation, testing and commissioning ofPressure independent type 2 way Balancing and modulating Control valves (Globe Type) suitable for 80 mm bore mild steel pipein a single Unit. PN16 Rating. It should be diaphragm type & ressure balancing should be done with Delta P controller only (not cartridge / Insert). The Balancing shlould be within Valve the Body (not through Actuator). Also, the Valve should be selected for the lowest Pressure Drop (not more than 20 KPA for FCUs and 30 KPA for AHUs) to enable Recurring Energy Savings.DN 15 to DN 32 Brass Body Externally ThreadedDN 40 & DN 50 Cast Iron,DN 65 to DN 100 Cast Iron, Flanged,duly mounted with Modulating actuator As per specifications of following sizes:DN 15 mm dia ( Max 2 gpm),DN 20 mm dia ( Max 4.0 gpm),DN 25 mm dia (Max 8.0 gpm),DN 32mm dia ( max 15 gpm),DN 40 mm dia ( max 33 gpm),DN 50 mm dia ( max 55 gpm),DN 65 mm dia (max 88 gpm),DN 80 mm dia ( max 123 gpm),DN 100 mm dia ( max 167 gpm) |
| 43 | Supply, installation, testing and commissioning 25 mm dia Purge Valves duly insulated as per specifications and drawings complete all as specified and as directed. |
| 44 | Expansion Tank :- Supply, Installation, testing & commissioning of Open expansion tankof3/5plyPVCconstructionasperthespecificationcompletewithHeavy duty float valves, accessories & insulation with nitrile rubber as per specification. Capacity - 500 Litres - (Qty 01 Nos)Note:-(i) ItemssuchascontrolcablingandPVCdrainpipingrequiredforcomplete system shall deemed to be included(ii)The work shall be carried out through OEM/authorized agency. The contractor shall submit the line diagram and load calculation and necessary documents duly signed by OEM before starting the work. Any modification additional requirement if necessiated , the costof the same is deemed to be includedin quoted rate under this item.(iii) If required capacity not available, the next higher capacity shall be provided by the contractorwithoutany extra cost to the department..(iv) Any special items accessories left outrequired for successful completion of the work shall be provided by the contractor and the cost for the same deemedto be included in the unit cost.(v) Necessary PCC foundation/MS frames for indoor and outdoor units all be provided as per OEM specifications including cables for main power supply as per OEM and of lengthaspersiterequirement. Costof the same is deemed to be included in unit rate quotedunder this item.. |
| 45 | Supplying and fixing in replacement 5000 Litre capacity Rotational moulded polyethylene water storage tank, triple layered, food grain plastic (cylindrical, vertical with closed top), hoisted and fixed in position on existing wall, stage, roof or RCC staging complete all as specified in SSR Part-I including supply and connecting tank nipple, float valve etc., making complete connection of inlet and out let pipe, fixing of Gl pipe (over flow) & washout to the nearest rain water drain complete all as specified and as directed. |
| 46 | Supply, installation, testing and commissioning ofprecise balancing, double regulation type cast iron balancing valve having FG 200 cast iron body conforming to IS 210: 2009, copper alloy trim, stainless steel 2 Cr. 13 stem, 2.4 MPa body test pressure & PN 10, maximum working pressure and standard flange ends duly insulated with FM approved highly-flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of apppropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified for following sizes:- |
| 47 | Size 80mm |
| 48 | Size 65mm |
| 49 | Size 50mm |
| 50 | S&F of 4\" bourdon tube pressure gauge conforming to EN 837-1, having copper alloy process connection & pressure element, plastic black pointer & case, plastic crystal-clear window snap-fitted in case, accuracy class 2.5, scale range 0-25 bar with accessories, etc. complete all as specified and directed |
| 51 | S&F of 6\" dual scale (\"F/\"C), lower mount (radial), bimetal thermometer having 0.5 NPT process connection, Grade A accuracy class as per ASME B40.200, stem diameter 6.35 mm, laminated safety glass window, stainless steel 304 case, steam, process connection & joint, aluminium dial & pointer, IP67 protection, scale range 0-50 °C with accessories, etc. complete all as specified and directed. |
| 52 | M&L for frame work with angle iron for frame support, with fabrication, welding joining including cuting tops to shape as directed, drilling holes, notching for wire, etc. flatiron fillets (for securing wire mesh etc) including all necessary drilling, bolting or riveting etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and as directed. |
| 53 | S&F 25 mm borePVC drain pipecomplete all as specified and as directed. |
| 54 | S&FWater Flow Switchsuitable for80mm dia pipe including control wiringcomplete all as specified and as directed. |
| 55 | S&FWater Flow Switch suitable for65mm dia pipe including control wiring complete all as specified and as directed. |
| 56 | S&F Water Flow Switchsuitable for 50mm dia pipe including control wiring complete all as specified and as directed. |
| 57 | S&F of powder coated extruded aluminum rectangular diffusers of required sizes with black anodized extruded aluminum volume control damper, nuts, bolts, screws etc. complete all as specified and as directed . |
| 58 | S&F of powder coated extruded aluminum rectangular diffusers of required sizes without volume control damper with nuts, bolts, screws etc. complete all as specified and as directed. |
| 59 | S&F of powder coated extruded aluminum supply & return grills complete with fixing accessories like nuts, bolts, screws etc. complete all as specified andas directed. |
| 60 | HVAC LT PANEL:- Supply, installation, commissioning and testing factory made, CPRI approved indoor type LT panel board of suitable size confirming to IS: 5039 with IP-54 protection made out of 2 mm thick CRCA sheet 415 Volt, 3 phase, 50 HZ supply mounted on and including GTs with necessary items, MS angle section 45x 45 x 6 mm frame with both side openable. Dust & vermin proof gasket, TPN busbar shall be insulated with colour coated heat shinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated and foundation, cement work etc complete all as specified and directed & Consisting of the following equipments including(a) INCOMMING:-(i) MCCB, 4 Pole, 50 KA 400 Amps 415 volts fixed type with extended terminals-1 Nos(ii) Solid copper bus bar 630 Amp for 3 phase and same size for neutral(iii) Phase indication-RYB-01 Set(iv) Digital multifunction meter of size 96x96 mm to measure corrent, voltage, frequency and power factor with built in selector switch and programable CT ratio-01 Nos |
| 61 | (b) OUTGOING:-(i)MCCB, 4 Pole, 160A 36 KA, 415 volts fixed type with extended terminais (For chiller Units)-03Nos(ii) MCCB, 4 Pole 100A, 25 KA, 415 volts (For Hot water generator & AHU)-03Nos (iii) Provn of DOL starter with TP power contactors No/Nc Aux contact, O/L relay & SD timer, Single phase preventer etc suitable for Primary CHW Pump-3Nos, Secondary CHW Pump-3Nos, Condenser Water Pump-3Nos, Hot Water Generator-2Nos & Hot Water Generator Pump-2nos (iv) Start/Stop push buttons-16 Nos, Phase indication -RYB & Motor ON/OFF/Trip indicating lamps LED type-08 set of three, Control fuse with link--03 Nos(v) MCB 32A TPN-02Nos(vi) Digital Ammeter(0-150A)-10Nos(vii) Control wiring shall be carried out with 2.5 sqmm copper wire.Note:- (i) A clear space of 200mm shall be kept from floor level for switchgear compartment(ii) Each compartment shall be numbered/lettered as approved by GE(iii)LT panel shall be fixed in PCC foundation as per manufacturer recommendation and minimum height clearance of 45 cm from GL.Cost of PCC foundation shall deemed to be included in unitrate quoted under this item.(iv) Contractor shall submit the GA drawings of LT Panel for approval of GE before placing the order |
| 62 | S&F galvanised iron cable tray of size 150mm x 50 mm and thickness 3.00 mm includingapplying two coats of approved shade synthetic enamel paint over one coat of red oxide primer complete all as specified and as directed |
| 63 | Supply, Installation , commissioning and testing 36 KW( 12KW x 3 Nos) heater bank for de-humidification during the monsoon season mounted on suitable size of mild steel angle iron or flat ironin addition to the Hot water coil fixed in the Floor mounted AHU complete with supply of the panel andHumidistat to operate the heater bank as and when required.complete all as specified and as directed. |
| 64 | Supply,installation,commissioning and testing of flexible fire retardent Canvas connector clothe including fitting accessories complete all as specified andas directed |
| 65 | Supply only 10 mm thickrubber matsuitable for LT 1 1KV volt grade of size1m x 2mcomplete all as specified and as directed. |
| 66 | Supply and laying in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 240 Sqmm 3.5 core complete all as specified and as directed. |
| 67 | Supply and laying in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 120 Sqmm 3.5 core complete all as specified and as directed. |
| 68 | Supply and laying in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 50 Sqmm 4 core complete all as specified and as directed. |
| 69 | Supply and laying in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 24 Sqmm 4 core complete all as specified and as directed. |
| 70 | Supply and laying in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 16 Sqmm 4 core complete all as specified and as directed. |
| 71 | Excavation in trenches , not exceeding 1.5 m wide and not exceeding 1.5 m in depthfor founddationetc and getting out in soft/loose soil complete all as specified and as directed. |
| 72 | Returning, filling in, including spreading levelling watering and well ramming in layers not exceeding 25 cmas in soft/loose soil complete all as specified and as directed. |
| 73 | Removing excavated soilto a distancenot exceeding 50 m anddepositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. |
| 74 | M&L for sand cushioning for under ground cable with locally available sand for protection of cable 8cm before laying cable and 15cm deep over the cable including spreading and consolidation complete all as specifiedand as directed.Note:-Punned thickness shall be measured for payment purpose. |
| 75 | Supply and layingold size sub class \"B\" bricks laid in trenches perpendicular tocable as incable protection complete all as specified and as directed. |
| 76 | Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mmthick, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edged of the plate not less than 1.5 m below ground level connected to galvanised iron earth strip of size 32mmx6mm by means of bolt, nuts, check nuts and washer of galvansed iron or steel,protected by galvanised iron pipe of 40 mm bore medium grade including funnel, 20mm dia bore galvanised iron pipe medium grade for watering, wire mesh,adequate quantity of charcoal dust and common salt in alternative layers all around the earth electrode compacted thickness15 cm including excavation and earth work in soft/loose soil, PCC 1:3:6 type C-1 using 20 mm gradedaggregate as in chamber, 50 mm thick RCC 1:2:4 type B-1 using 20 mm graded stone aggregate as in cover reinforced with 8 mm TMT bar @100 mm C/C complete andtesting on completion complete allas shown in electrical plate No. 3 of MES SSR Part-I 2009.Note :- Cost of earth strip and GI protection pipe up to a distance 7.5 metre shall be included inthe quoted rate. |
| 77 | S&F 32x6mm galvanised iron stripburied in groundor fixed on wall complete all as specified and as directed. |