| Sl. No. | Item Description |
| 1 | Supply, fixing, testing and commissioning of ceiling mounted mini-pleat type upstream gel seal filter module (terminal filter hood) of size 4 feet x 2 feet (OEM standard size) with HEPA filter of efficiency 99.995 % down to 0.3 micron as per class H14 of EN 1822 or equivalent efficiency conforming to IEST practiceall as specified and / or directed etc., complete. |
| 2 | Supply, fixing, testing and commissioning of ceiling mounted mini-pleat type upstream gel seal filter module (terminal filter hood) of size 2 feet x 2 feet (OEM standard size) with HEPA filter of efficiency 99.995 % down to 0.3 micron as per class H14 of EN 1822 or equivalent efficiency conforming to IEST practiceall as specified and / or directed etc., complete. |
| 3 | Supply and fixing of 50 mm thick double skin wall panel sandwiched with PUF including bottom floor track, top runner, \"U\" channels, sealant, etc., all as specified and/or directed etc., complete. Note: 1) The inner and outer skin of the panel shall be made of steel sheet as per technical specification. |
| 4 | Supply and fixing of 100 mm thick double skin wall panel sandwiched with PUF including bottom floor track, top runner, \"U\" channels, sealant, etc., all as specified and/or directed etc., complete. Note: 1) The inner and outer skin of the panel shall be made of steel sheet as per technical specification. |
| 5 | Supply and fixing of 100 mm thick double skin wall panel sandwiched with PUF, aluminium return air duct riser of size not less than 900 mm x 98 mm including bottom floor track, top runner, \"U\" channels, sealant, etc., all as specified and/or directed etc. complete. Note: 1) The inner and outer skin of the panel shall be made of steel sheet as per technical specification. |
| 6 | Supply and fixing of true horizontal level walkable false ceiling consisting of80 mm thick double skin panel sandwiched with PUF including T-grid, suspender rod, turnbuckle, nuts, bolts, etc., all as specified and/or directed etc., complete. Note: 1) The inner and outer skin of the panel shall be made of steel sheet as per technical specification. |
| 7 | Supply and fixing of 100 mm thick double skin fire rated wall panel sandwiched with rockwool including bottom floor track, top runner, \"U\" channels, sealant, etc., all as specified and/or directed etc., complete. Note: 1) The inner and outer skin of the panel shall be made of steel sheet as per technical specification.The panel should be fire rated of 120 minutes. |
| 8 | Supply and laying of Electrostatic Conductive vinyl floor tile with flexible homogenous compressed tiles of minimum size 610 mm x 610 mm x 2 mm. The ESD tiles shall have electrical resistance in the range of 10^4ohm to 10^6 ohms and shall have body voltage generation of <=70V, dimensional stability of 0.05% and shall be resistant to acids, chemicals and fire. Necessary preparation of sub floor surface should be done using Self-Leveling compound. The flooring should be laid using approved conductive adhesives. Joint between the tiles shall be grooved, PVC welded using automatic equipment and copper tape shall be provided and laid all as per manufacturer’s specification & same shall be connected to the copper strip which is running on side walls with requisite accessories / banana sockets. The tiles will have permanent conductivity and ESD properties to be independent of humidity due to homogenous nature of product as it is sliced from pressed vinyl block. Scope of supply should include laying of tiles, self levelling compound to level the floor to maximum possible extent, Conductive adhesive, copper tape shall cross each tiles in both the direction at site, grooving / welding of joints with automatic equipment as per manufacturers specifications. Certification of Electrical resistance such as Point to Point, Point to Ground and Body to Ground resistance, Combination resistance of the installed system and Body voltage generation, meeting to international standards and duly tested and authorized by a Certified ESD engineer who has received his Certificate from an internationally reputed certifying organization. Note: Rate to be quoted for complete finished work including all materials and labour and necessary preparation of surface including removal of existing PVC flooring, cleaning etc. Actual area of flooring as laid will be measured for payment. |
| 9 | Supply of Air Shower shall have working space not be less than 800 mm (W) X 900mm (D) X 2100mm (H), all as specified and / or directed etc., complete. |
| 10 | Supply, installation, testing and commissioningof Air Curtain suitable for single leaf door of size 1000mm (W) x 2100 mm (H) with necessary fixtures all as specified and / or directed etc., complete. |
| 11 | Supply, installation, testing and commissioningof Air Curtain suitable for double leaf door of size 1800mm (W) x 2400 mm (H) with necessary fixtures all as specified and / or directed etc., complete. |
| 12 | Supply and fixing of aluminium powder coated covingR 50 for wall, ceiling, floor, corners, etc all as specified and / or directed etc., complete. |
| 13 | Supply and fixing of clean room compatible single door of clear size 1000 mm x 2100 mm sandwiched with PUF all as specified and / or directed etc.,complete. |
| 14 | Supply and fixing of clean room compatible double door of clear size 1800mm x 2400 mm sandwiched with Rockwool (density min. 96kg/m3), fire reterdant for emergency exit along with panic bar and all accessories, all as specified and / or directed etc.,complete. |
| 15 | Supply and fixing of clean room compatible double door of clear size 1500mm x 2400 mm sandwiched with Rockwool (density min. 96kg/m3), fire reterdant for long with panic bar and all accessories, all as specified and / or directed etc.,complete. |
| 16 | Supply and fixing of Double glass view panel of size not less than 1500 mm x 1200 mm, glass thickness not less than 5 mm all as specified and/or directed etc.,complete. |
| 17 | Supply and fixing of Stainless steel return air grills with GI volume control damper, prefilter with magnetic lock all as specified and/ or directed etc.,complete. |
| 18 | Supply, fixing, testing and commissioning of SS static pass box of inner working dimension not less than 600 x 600 x 600 with lights, door interlocking system all as specified and/or directed etc., complete. |
| 19 | Supply and fixing / positioning of Shoe rack inside Change room with siting arrangement for 24 people, SS 304 material 1.5 mm thickness, all three side close, front side open, Bottom close Type, with 50 mm Legs. Individual compartment size shall not be less than 225 (W) x 380 (D) x 156 (H) in mm. Overall size shall be approximately 1800 (W) x 450 (D) x 520 (H) in mm. Mirror / Matt Finish & Argon Welding. |
| 20 | Supply and fixing / positioning of Shoe rack outside Change room (Lobby area) for 24 people, polypropylene material, all three side close, front side open, Bottom close Type, with 50 mm Legs. Individual compartment size shall not be less than 225 (W) x 380 (D) x 156 (H) in mm. Overall size shall be suitable for site. |
| 21 | Supply and fixing Locker cum germent storage made of powder coated 18G GI of size (individual compartment) 300 (W) x 600 (D) x 1050 mm (H), overall size 1200 x 600 x 2100 mm for 8 compartments, all three side close, front side small lockers with separate door with louvers, handle & locking arrangement, each locker inside top hanger pipe & bottom sheet shelf with locking facility, bottom close Type. |
| 22 | Supply and fixing / positioning of automatic shoe cover dispenser made of SS 304 of thickness 1.2 mm with all the necessary accessories. Single Shoe can be accomodated at time. |
| 23 | Supply and fixing / positioning of manual type Glove Dispenser made of SS 304 of thickness 1.2 mm with all the necessary accessories. |
| 24 | Supply of Dustbin of size 12\" Dia. x 15\" height made of SS 304 material 1.2 mm thickness, Top Lid with handle, bottom stacking ring, with bottom paddle foot operated. Mirror / Matt Finish & Argon Welding. |
| 25 | Supply and fixing of Sticky mat of size 600 x 600 (in mm)-10 pc of Black or approved colour with all necessary accessories, etc. |
| 26 | Supply and fixing / positioning of Storage for used garments of size 15\" x 15\" x 33\" made of SS 304 material 1.2 mm thickness, all side open, top side handle & hooks arrangement, structure made in ¾\" dia Round Pipe, bottom cross patti, with bottom fitted 2\" x 1\" PU Wheel. Mirror Polish & Argon Welding. |
| 27 | Supply and fixing of Dressing Mirior of size 450 x 1200 (in mm), wall mounting type shall be fixed of wall panel with all necessary accessories, etc. |
| 28 | Making cutout in wall panel and ceiling panel for various items/components pertaining to utility services like nitrogen gas, compressed air, electrical bus bar, speaker, sensor, LAN items, cleam room equipment / components etc., of any size with length of maximum side upto 350 mm all as specified and / or directed etc., complete. |
| 29 | Making cutout in wall panel and ceiling panel for various items/components pertaining to utility services like nitrogen gas, compressed air, electrical bus bar, speaker, sensor, LAN items, clean room equipments / components etc., of any size with length of maximum side above 350 mm and less than 650 mm all as specified and / or directed etc., complete. |
| 30 | Making cutout in wall panel and ceiling panel for various items/components pertaining to utility services like nitrogen gas, compressed air, electrical bus bar, speaker, sensor, LAN items, cleam room equipments / components etc., of any size with length of maximum side above 650 mm all as specified and / or directed etc., complete. |
| 31 | Supply, erection, testing and commissioning of clean room & BMS compatible Magnahalic guage of 100 mm dia, range 0 to 50 Pa, ± 3% accuracy with SS mounting / box all as specified and / or directed etc., complete. |
| 32 | Supply and fixing clean room & BMS compatible Digital temperature and RH indicator of 100 mm dia, range 0 to 50 degC, 0 to 90% RH, ± 3% accuracy with display all as specified and / or directed etc., complete. |
| 33 | Testing and Validation of the clean room by carrying out performance tests as indicated in the detailed technical specification during handing over of the clean room all as specified and / or directed etc., complete. Note: The contractor shall furnish the validation document consisting of design qualification, installation qualification and performance qualification. |
| 34 | Supply, installation, testing and commissioning of factory built floor mounted horizontal double decker type double skin type Air Handling Unit (AHU) for Clean room of capacity not less than 17 TR, Total CFM 6800 CFM ; Dehumified CFM 6800, 85 MM ESPcomplete with PLUG type fan with VFD compatible motor, Motor class- IE3, internal power/ control cabling,pre filters with 90% efficiency down to 10 μm (EU -4), fine filters with 95% efficiency down to 5 μm, DX cooling coil 8 rows deep of copper tubes with aluminium fins compatible to connect DX ODU, min. 1.2 mm thick SS-304 drain pan with 13 mm nitrile rubber insulation, fire proof flexible connection at outlet. AHU outerskin shall be 0.8 mm pre-coated GSS, inner skin shall be 0.6 mm pre-coated GSS with thermal break profile. Panels shall be 43± 2 mm thick with PUF injected with density not less than 38 Kg/m3, Mixing box with provision for connecting return air and fresh air with damper, Bypass damper arrangement, internal power / control cabling, belt drive system, spring type isolation system (min. vibration isolation efficiency 90%). The AHU shall have an additional fresh air plenum with minimum 3TR DX type cooling coil (in addition to 17 TR DX type cooling coil), separate 430 cfm, 10 mm ESP fresh air blower unit and prefilter. The outside fresh air shall be filtered and cooled first by the 3TR DX type cooling coil before it enters and mixes with the return air in Mixing Box. AHU shall have supply air plenum provided with fine filter at the outlet of the main Blower unit.Note:1) The capacity indicated above is for reference only, the contractor shall design and indicate the actual size, if higher size units are required.2) The rate quoted for the AHU shall be excluding the cost of MS frame / brackets / supports. TheMS frame / brackets / supports will be measured and paid separately under the relevant item of SOQR. |
| 35 | Supply, erection, testing and commissioning of 9 KW finned type electric strip air heaters in THREE banks (3 KW in each bank) complete with thermostat, humidistat,safety thermostats, air stat complete with fixing frame etc.,. all as specified and/or directed etc., complete. |
| 36 | Supply, erection, testing and commissioning of pan humidifier made of stainless steel sheet of minimum 2 mm thick with steam generation capacity not less than 4 kg/hr and heater capacity not less than 3 KW complete with steam outlet nozzle, immersion heaters, low level cut out, humidistat, saftey stat, float valve, sight glass, ball valve for drain connection etc., including GI pipes ( as applicable) all as specified and/or directed etc.,complete. Note:The PCC pedestal / bed, if provided for installation of humidifier will be measured and paid under the relevant item of SOQR. |
| 37 | Supply, Installation, testing and commissioning of air cooled interver type Condensing unit of capacity not less than 8.5 TR suitable to connect DX Air Handling Unit mentioned in SOQR No 34, complete with scroll compressor, R407C/ R410A refrigerant gas, thermostatic expansion valves, condenser coil with suitable size fan & motor, all necessary controls/protection viz., thermostat, HP/LP cut out, microprocessor based control unit including first charge of refrigerant gas & oil, necessary power and contol wiring between DX Air Handling Unit and Condensing units, all as specified and/or directed etc.Note: 1) The PCC pedestal/ bed/ MS frame/ brackets/ supports provided for installation of condensing unit will be measured and paid under the relevant item of SOQR |
| 38 | Supply, Installation, testing and commissioning of air cooled interver type Condensing unit of capacity not less than 3 TR suitable to connect DX Air Handling Unit mentioned in SOQR No 34, complete with scroll compressor, R407C/ R410A refrigerant gas, thermostatic expansion valves, condenser coil with suitable size fan & motor, all necessary controls/protection viz., thermostat, HP/LP cut out, microprocessor based control unit including first charge of refrigerant gas & oil, necessary power and contol wiring between DX Air Handling Unit and Condensing units, all as specified and/or directed etc.Note: 1) The PCC pedestal/ bed/ MS frame/ brackets/ supports provided for installation of condensing unit will be measured and paid under the relevant item of SOQR |
| 39 | Supply installation testing commissioning of manual temperature controller foroutdoor condensing unit including 3 nos. temperature sensor ,with 3 Nos NO - NC switches.(Controller should have display to set temperature).Rate to be quoted along with SS front frame box that can accomodate 3 nos. of NO-NC switch. |
| 40 | Supply installation testing commissioning of manual humidity controller (1 No.) with 3 nos. of sensor 3 nos. ofwith of sensor ofNO - NC switch.(Controller should have display to set relative humidity)Rate to be quoted along with SS front frame box that can accomodate 3 nos. of NO-NC switch. |
| 41 | Supply, erection, testing and commissioning of suitable size refrigerant grade copper piping between DX AHU and 8.5TR outdoor condensing unt for suction, liquid and discharge lines including all fittings, accessories, tube type nitrile rubber insulation with factory laminated Glass cloth over insulation from indoor to outdoor unit with UV resistant paint orclosed cell physically crosslinked polyolefin foam with factory laminated Glass cloth with UV resistant paint (for both suction and liquid line), sleeve (wall crossing), supports, core cutting in brick/ concrete wall as required and making surface good, etc., all as specified and/ or directed etc., complete. Note: 1. The scope include Communication / Control cable connecting the Indoor units / Outdoor units / Controller of suitable size as recommended by the OEM. The external communication / control cabling shall be run inMS conduit and inside building control cabling shall be run in PVC conduit including all clamps, screws, fittings, supporting items etc., all as specified and/or directed etc., complete2. Both suction and liquid piping will be treated as one unit and will not be measured separately. Also irrespective of number of pipes/ circuits the measurement of pipes will be made only once between 8.5 TR capacity Condensing unit (SOQR No. 37) and AHU (SOQR No. 34). |
| 42 | Supply, erection, testing and commissioning of suitable size refrigerant grade copper piping between DX AHU and 3.0TR outdoor condensing unt for suction, liquid and discharge lines including all fittings, accessories, tube type nitrile rubber insulation with factory laminated Glass cloth over insulation from indoor to outdoor unit with UV resistant paint orclosed cell physically crosslinked polyolefin foam with factory laminated Glass cloth with UV resistant paint (for both suction and liquid line), sleeve (wall crossing), supports, core cutting in brick/ concrete wall as required and making surface good, etc., all as specified and/ or directed etc., complete. Note: 1. The scope include Communication / Control cable connecting the Indoor units / Outdoor units / Controller of suitable size as recommended by the OEM. The external communication / control cabling shall be run inMS conduit and inside building control cabling shall be run in PVC conduit including all clamps, screws, fittings, supporting items etc., all as specified and/or directed etc., complete2. Both suction and liquid piping will be treated as one unit and will not be measured separately. Also irrespective of number of pipes/ circuits the measurement of pipes will be made only once between 8.5 TR capacity Condensing unit (SOQR No. 38) and AHU (SOQR No. 34). |
| 43 | Providing and laying of cPVC (SDR11) pipes of 32 mm dia, with 9 mm thick elastomeric nitrile rubber tubular insulation with factory laminated glasscloth for condensate water drain from the AHU & Cassette AC to nearest drain point, fittings, supportincluding core cutting in brick/ concrete wall as required and making surface good etc. complete |
| 44 | Providing and laying of cPVC (SDR11) pipes of 40 mm dia, with 9 mm thick elastomeric nitrile rubber tubular insulation with factory laminated glasscloth for condensate water drain from the AHU & Cassette AC to nearest drain point, fittings, supportincluding core cutting in brick/ concrete wall as required and making surface good etc. complete |
| 45 | Supply of Aluminium Cladding with 0.7 mm thick Aluminium sheets rivets, silicon sealant and toggle clips with necessaryaccessories for Ref. copper piping exposed to ambientcomplete in all respect as per technical specifications |
| 46 | Supply, fabrication, installation, testing and commissioning of factory fabricated GI sheet metal ducts of 22 Guage (Birmingham Gauge) (0.8 mm) and zinc coating not less than 120 g/m2 in accordance with approved drawings including necessary hangers, rubber gaskets, rivets, flanges, scaffolding required for work, etc., all as specified and/or directed etc.,complete Note: 1) The rate quoted for the GI ducting shall be includingthe cost of scaffolding, steel supports, nuts, bolts, etc. and the same will not be measured and paid separately. |
| 47 | Supply, fabrication, installation, testing and commissioning of factory fabricated GI sheet metal ducts of 20 Guage (Birmingham Gauge) (1.0 mm) and zinc coating not less than 120 g/m2 in accordance with approved drawings including necessary hangers, rubber gaskets, rivets, flanges, scaffolding required for work, etc., all as specified and/or directed etc.,complete Note: 1) The rate quoted for the GI ducting shall be includingthe cost of scaffolding, steel supports, nuts, bolts, etc. and the same will not be measured and paid separately. |
| 48 | Supply, fabrication, installation, testing and commissioning of factory fabricated GI sheet metal ducts of 18 Guage (Birmingham Gauge) (1.2 mm) and zinc coating not less than 120 g/m2 in accordance with approved drawings including necessary hangers, rubber gaskets, rivets, flanges, scaffolding required for work, etc., all as specified and/or directed etc.,complete Note: 1) The rate quoted for the GI ducting shall be includingthe cost of scaffolding, steel supports, nuts, bolts, etc. and the same will not be measured and paid separately. |
| 49 | Supply, fabrication, installation, testing and commissioning of site fabricated GI sheet metal ducts of 22 Guage (Birmingham Gauge) (0.8 mm) and zinc coating not less than 120 g/m2 in accordance with approved drawings including necessary hangers, rubber gaskets, rivets, flanges, scaffolding required for work, etc., all as specified and/or directed etc.,complete. Note: 1) The rate quoted for the GI ducting shall be includingthe cost of scaffolding, steel supports, nuts, bolts, etc. and the same will not be measured and paid separately. |
| 50 | Supply, fabrication, installation, testing and commissioning of site fabricated GI sheet metal ducts of 20 Guage (Birmingham Gauge) (1.0 mm) and zinc coating not less than 120 g/m2 in accordance with approved drawings including necessary hangers, rubber gaskets, rivets, flanges, scaffolding required for work, etc., all as specified and/or directed etc.,complete. Note: 1) The rate quoted for the GI ducting shall be includingthe cost of scaffolding, steel supports, nuts, bolts, etc. and the same will not be measured and paid separately. |
| 51 | Supply, fabrication, installation, testing and commissioning of site fabricated GI sheet metal ducts of 18 Guage (Birmingham Gauge) (1.2 mm) and zinc coating not less than 120 g/m2 in accordance with approved drawings including necessary hangers, rubber gaskets, rivets, flanges, scaffolding required for work, etc., all as specified and/or directed etc.,complete. Note: 1) The rate quoted for the GI ducting shall be includingthe cost of scaffolding, steel supports, nuts, bolts, etc. and the same will not be measured and paid separately. |
| 52 | Supplying and fixing thermal insulation for supply air ducts with 19 mm thick self adhesive closed cell elastomeric (nitrile rubber) sheet reinforced with aluminium foilor closed cell physically crosslinked polyolefin foam reinforced with aluminium foil complying to ASTM E84 Flame spread Index < 25, Smoke developed index < 50 all as specified and/ or directed etc., complete |
| 53 | Supplying and fixingthermal insulation for return air ducts with 13 mm thick self adhesive closed cell elastomeric (nitrile rubber) sheet reinforced with aluminium foilor closed cell physically crosslinked polyolefin foam reinforced with aluminium foil complying to ASTM E84 Flame spread Index < 25, Smoke developed index < 50 all as specified and/ or directed etc., complete |
| 54 | Supplying and fixing acoustic insulation for ducting with open cell nitrile rubber insulation or open cell physically crosslinked polyolefin foam insulation of thickness not less than 15 mm complying to ASTM E84 Flame spread Index < 25, Smoke developed index < 50, density of open cell nitrile rubber insulation shall not be less than 130 kg/m3 including adhesive or density of open cell physically crosslinked polyolefin foam shall not be less than 25 kg/m3 including adhesive, fixing accessories all as specified and/or directed etc., complete |
| 55 | Supply, installation, testing and commissioningofvolume controldamper (VCD) forducts made of GI sheet of thickness not less than 18 G including neoprenerubber gaskets, nuts, bolts,screwslinkages,flanges etc., all as specified and/ or directed etc., complete. |
| 56 | Supply, installation, testing and commissioning of combined fire and smoke damper to be fitted at AHU (inlet and outlet duct) / supply air duct and return air duct/ path wall openings (inside wall). These dampers shall be made from GI sheet in multi blade construction. The dampers shall be provided with seal on sides to prevent spread of smoke and fire. Testing of fire damper shall be as per UL 555 and certified by CBRI. all as specified and/or directed etc., complete. |
| 57 | Supply, installation, testing and commissioning of control instruments and sensorsrequired for Combined fire and smoke damper including actuators, temperature sensor and duct mounted smoke sensor and auxiliary switch with all the necessary accessories for fire & smoke damper (item no. 57 of SOQR) all as specified and/or directed etc., complete.Note: 1) The item shall be complete with in-built temperature sensor and duct mounted smoke sensor and auxiliary switch to close the dampers simultaneously. 2) The components provided under this item shall be such that the dampers also actuate in response to signal from central fire alarm system which shall trip the indoor unit along with closing the damper.3) The cabling from the central fire alarm system upto the combined fire and smoke damper will be provided by the fire alarm system contractor.4) The damper will be measured and paid under the relevant item of SOQR. |
| 58 | Supply, erection, testing and commissioning of 350mm Dia. - Butterfly damper should constructed with not less than 0.8mm thick galvanized steel sheet, with single flap, necessary stopper, flanges for fastening on to the duct surface and with grooves for clamping the flexible ducts securely all as specified and/ or directed etc., complete |
| 59 | Supply, erection, testing and commissioning of 300mm Dia. - Butterfly damper should constructed with not less than 0.8mm thick galvanized steel sheet, with single flap, necessary stopper, flanges for fastening on to the duct surface and with grooves for clamping the flexible ducts securely all as specified and/ or directed etc., complete |
| 60 | Supply, erection testing and commissioning of Aluminium flexible duct of 350mm dia with insulation all as specified and/or directed etc., complete |
| 61 | Supply, erection testing and commissioning of Aluminium flexible duct of 300mm dia with insulation all as specified and/or directed etc., complete |
| 62 | Supply, Erection, testing of Utility SS 316 piping of 35 mm nominal bore for Nitrogen, Compressed air, Dry air by laying the piping through paneling all as specified and/or directed etc., complete. |
| 63 | Supply, Erection, testing of Utility SS 316 piping of 15 mm nominal bore for Nitrogen, Compressed air, Dry air by laying the piping through paneling all as specified and/or directed etc., complete. |
| 64 | Supply, erection, testing of SS body ball valves 35mm size screwed end all as specified and/or directed etc., complete. |
| 65 | Supply, erection, testing of SS body ball valves 15mm size screwed end all as specified and/or directed etc., complete. |
| 66 | Supply, erection testing and commissioning of fresh/ exhaust airlouvers made of extruded aluminium with bird/ insect screen including volume control damper made of aluminium. Note : The lowest louvers of the assembly shall extend out slightly to facilitate disposal of rain water without falling on the door/ wall on which it is mounted all as specified and/or directed etc., complete. |
| 67 | Supply installation testing and commissioning of precoated GI sheet (22 Gauge ).Pre coating should not be less than 180 GSM. Note: This item shall be used to cover the height deifference forexisting false ceiling or ceiling and Cleanroom false ceiling. |
| 68 | Supply and installation of ISI marked ABC Stored pressure type Fire Extinguisher 6 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder for Fighting ABC Class of Fire, stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall conform to IS:15683, have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal abd wall bracket completein all respect as per technical specification. |
| 69 | Supply and installation of ISI marked Carbon-dioxide extinguisher of 4.5 Kg capacity made of high pressure seamless steel cylinder complete with wheel type valve with one meter long braided high pressure discharge hose completein all respect as per technical specification including initial fill with CO2 gas. Other components, design, performance, anticorrosive treatment Shall conform to IS:15683. |
| 70 | Supply and installation of ISI marked Clean agent type fire extinguisher of 4kg capacity conforming to IS 15683. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, and wall bracket completein all respect as per technical specification. |
| 71 | Design,fabrication,supply,installation,testingand commissioningof AHU PANEL conforming to IEC-61439 & IEC-61641 standard complete as per enclosed drawing (SLD) & detailed technical specifications suitable for 440Volts,50Hz,3phase, 4wire AC supply with fault current 50kA/0.3sec. In general the panel shall be of modular type, floor mounting, free standing, vermin proof, indoor/outdoor duty, made out of CRCA sheet steel with powder coat painting having aluminium busbars,DMC/ SMC/ FRP insulators etc with copper cables forinterconnections as shown in drawing & DTS. Incomer & buscoupler feeders shall haveMCCBs of appropriate rating with interlocking, digital metering, protection systems, SPDs,LED indication lamps etc as applicable and as shown in drawing.The outgoing feeders shall have MCCBs/ MCBs/ Motor Starters/Contactors/VFDs as applicable of appropriate rating along with digital meters, LED indication lamps etc as applicable and as shown in the drawing. The item includes providing of required fixing accessories such as grouting bolt-nuts, C-channel base/ MS stand, welding etc for coupling of already laid cables/conduits and associated civil works complete as directed by EIC.Note:- Please refer drawing/SLD and DTS for complete Panel details. GA drawing of the panel is to be approved from the EIC before commencement of fabrication. |
| 72 | Supplying, installation, testing and commissioning of 200A rating 25kA MCCB along with Energy Meter & CTs as per local electricity board/ authority norms fittedinside 1.5mm thicknessCRCA/Sheet steel powder coat painted enclosure of suitable size on the wall surface, including required busbars, insulator supports, terminal spreader, phase barriers, inter connection wires and other necessary accessories etc complete conforming to statutory norms and drawing.The item shall also include any additional liasoning charges required with the local EB authorities. Please refer drawing for details. |
| 73 | Supplying & Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable including surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 74 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 75 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm outer dia pipe. |
| 76 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm outer dia pipe. |
| 77 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm outer dia pipe. |
| 78 | Supplying & Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable including surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 79 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 80 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.20 mm outer dia pipe. |
| 81 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.25 mm outer dia pipe. |
| 82 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.32 mm outer dia pipe. |
| 83 | Supplying and fixing 20 mm dia GI flexible pipe along with all ancillaries and accessories like coupler etc. as required. |
| 84 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq. mm |
| 85 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 86 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 87 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 88 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.5 x 6 sq. mm |
| 89 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 90 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 91 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch modular. |
| 92 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 A switch modular. |
| 93 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet modular. |
| 94 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 A socket outlet modular. |
| 95 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 96 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mmX75mm) |
| 97 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 3 Module (100mmX75mm) |
| 98 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 4 Module (125mmX75mm) |
| 99 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 6 Module (200mmX75mm) |
| 100 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 8 Module (125mmX125mm) |
| 101 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 12 Module (200mmX150mm) |
| 102 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 103 | Supply and laying of 20mm dia steel wire reinforced corrugated flexible PVC conduit along with accessories as required.. |
| 104 | Supply and laying of 25mm dia steel wire reinforced corrugated flexible PVC conduit along with accessories as required. |
| 105 | Supply and fixing of oversized PVC cover on junction box with screws as directed by EIC. |
| 106 | Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required. |
| 107 | Supplying and fixing of following ways, Vertical type, 415 V, TPN MCB distribution board made of sheet steel, dust protected and duly powder painted,on surface/ recess complete with 250 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs and slot with screws for mounting MCCB incomer, including earthing etc. as directed by EIC. (but without MCBs and MCCB ) 6way (MCCB+18) VTPN DB, IP-43 withMetal door |
| 108 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 6 way (4 + 18), Double door |
| 109 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 4 way (4 + 12), Double door |
| 110 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole MCB |
| 111 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole MCB |
| 112 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 113 | Supplying and fixing of63 A, TPN (Triple pole + Neutral) MCB, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc. as directed by EIC. |
| 114 | Supplying and fixingof 63 A, TP (Triple pole) MCB, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc. as directed by EIC. |
| 115 | Supplying and fixing following rating and breaking capacity MCCB with thermomagnetic release, phase barriers and terminal spreaders in existing VTPN Distribution board, making connections, including accessories etc. as directed by EIC. 100A, 25kA, TM based TPN MCCB |
| 116 | Supplying of non-metalic IP-65or66 grade 63A, 440V, TPN+E socket outlet along with suitable Plug top & 63A, 10KA-Curve TPN MCB, including suitable outdoor duty non corrosive enclosure and fixing of the same on surface or in recess, with complete accessories, connections, testing and commissioning etc. as required. |
| 117 | Supplying of non-metalic IP-65or66 grade 32A, 440V, TPN+E socket outlet along with suitable Plug top & 32A, 10KA-Curve TPN MCB, including suitable outdoor duty non corrosive enclosure and fixing of the same on surface or in recess, with complete accessories, connections, testing and commissioning etc. as required. |
| 118 | Supplying of non-metalic IP-42 grade 32A, 440V, TPN+E socket outlet along with suitable Plug top & 32A, 10KA-Curve TPN MCB, including suitable non corrosive enclosure and fixing of the same on surface or in recess, with complete accessories, connections, testing and commissioning etc. as required. |
| 119 | Supplying of non-metalic IP-42 grade 32A, 240V, SPN+E socket outlet along with suitable Plug top & 32A, 10KA-Curve SPN MCB, including suitable non corrosive enclosure and fixing of the same on surface or in recess, with complete accessories, connections, testing and commissioning etc. as required. |
| 120 | Supplying and fixing of following rating and breaking capacity MCB with suitable powder coat painted sheet steel enclosure along with accessories, making connections etc. as directed by EIC.63A, 4 Pole, 10kA MCB with enclosure. |
| 121 | Supplying of below mentioned specification White LED luminaire & fixing of the same as recess in false ceiling/ surface type by providing required down rod/ chainlinks, clamps, screws/ anchor bolt-nuts, washers etc., making electrical connections, earthing etc., as directed by engineer-in-charge. Type: 2ftx2ft/1ftx2ft size Clean room Luminaire Mounting type :- Recess in false ceilingBody :- CRCA/PDC IP-65 or IP-54 grade housing.Input power :- Minimum 40 Watts.Opening :- Bottom Opening variantRef model :- Havells- LED CLEAN ROOM BOTTOM OPENING MS EXE |
| 122 | Supplying of below mentioned specification LED luminaire & fixing of the same as recess in false ceiling by providing required down rod/ chainlinks/ pipe, clamps, screws/ anchor bolt-nuts, washers etc., making electrical connections, earthing etc., as directed by engineer-in-charge. Type :- 4ft LED industrial luminaireMounting :- Surface mounting type.Body: Polycarbonate housing with IP-66 Protection.Input power :- Minimum 18 or 20 WattsRef model :- Havells- MAGNUM GRAND GOLD |
| 123 | Supplying & Laying of following size LT power cable with Aluminium conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (A2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments, including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC.3.5C X 95 Sq mm size. |
| 124 | Supplying & Laying of following size LT power cable with Aluminium conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (A2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments, including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC. 3.5C X 35 Sq mm size. |
| 125 | Supplying & Laying of following size LT power cable with Copper conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC. 4C X 16 Sq mm size |
| 126 | Supplying & Laying of following size LT power cable with Copper conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC. 4C X 10 Sq mm size. |
| 127 | Supplying & Laying of following size LT power cable with Copper conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC. 4C X 6 Sq mm size. |
| 128 | Supplying & Laying of following size LT power cable with Copper conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC. 3C X 10 Sq mm size |
| 129 | Supplying & Laying of following size LT power cable with Copper conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC. 3C X 6 Sq mm size. |
| 130 | Supplying and making end termination of 4C x 16 sqmm Copper Cable with Copper Lugs anddouble compression brass gland at one end of cable as directed by EIC. |
| 131 | Supplying and making end termination of 4C x 10 sqmm Copper Cable with tinned Copper Lugs anddouble compression brass gland at one end of cable as directed by EIC. |
| 132 | Supplying and making end termination of 4C x 6 sqmm Copper Cable with tinned Copper Lugs anddouble compression brass gland at one end of cable as directed by EIC. |
| 133 | Supplying and making end termination of 3C x 10 sqmm Copper Cable with Copper Lugs anddouble compression brass gland at one end of cable as directed by EIC. |
| 134 | Supplying and making end termination of 3C x 6 sqmm Copper Cable with tinned Copper Lugs anddouble compression brass gland at one end of cable as directed by EIC. |
| 135 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1KV grade as required.3½ X 95 sq. mm (45mm) |
| 136 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1KV grade as required.3½ X 35 sq. mm (32mm) |
| 137 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 138 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 139 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 140 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness |
| 141 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 142 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 143 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 144 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 145 | Supplying of DLP PVC adaptable trunking system of size 105 mm X 50mmalong withbase, flexible covers, Partitions (Dividers), endcaps, joints (coupler) , bends,Tees, mounting accessories etc. suitable for fixing of mounting boxes, modular switches & sockets, as required at site and installation of the same on the wall by providing required bolt-nuts/ screws with TW gutties/ fixing accessories as per manufacturers recommendation etc. complete as directed by EIC.Ref make- Legrand: 0104 22 |
| 146 | Supplying of all the required materials & making of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as requiredincluding associated civil works. |
| 147 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 148 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)Note: Associated earth excavation shall be measured & paid separatly. |
| 149 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) Note: Associated earth excavation shall be measured & paid separatly. |
| 150 | Supplying of 25x3mm size electrolytic coppertape and laying/fixing of the same on the wall by providing suitable accessoriesand terminating the ends with brass bolts and nuts etc. The flat shall be joined by hexothermic welding/ brazing as directed. |
| 151 | Supplying and installation of 4mm busbar mount type banana socket adapter connector having insulated base&knobs suitable for making temporary electrical connections to busbars with wires/cables (Banana sockets) |
| 152 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 153 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 154 | Excavation for cable trenches in normalsoil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 155 | Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
| 156 | Supplying and laying of approved quality and make well burnt bricks breadthwise on top along the already laid cable/sand inside the trench as directed by the Engineer -in charge.(Approx. 09 nos of bricks will be required per Mtr) |
| 157 | Supplying and spreading of clean & dry river sand /M-2 sand all around the already laid cable in the trench as directed by EIC. |
| 158 | Cutting/Breaking of concrete road/flooring to a required width and depth suitable by machine/manually for laying of pipe/cable. The work includes refilling of excavated earth after the pipes/cables have been laid, laying of available stone , borders, watering, ramming and providing of 150mm thickness1:2:4 cement concrete( PCC).The surface shall be rough plastered suitable for movement of vehicles and required curing to be done. Removed debries shall be cleared from the site immediately as directed. (Note: Excavation and refilling below PCC slab & stone borders shall be measured and paid separately) |
| 159 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 150 mm dia |
| 160 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 161 | Supply, installation, testing and commissioning of Microprocessor controlled One loop analogue addressable Fire Alarm Control Panel with 1 loop card for all loops, alarm facilities, hooter, fire / fault indications, audio visual signals, battery charger, printer and public address system interface system software, auto-dialer etc all as specified and or required complete. |
| 162 | Supplying, installation, testing & commissioning of addressable Multi-criteria smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 163 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 164 | Supplying, installation, testing & commissioning of intelligent addressable programmable sounder complete as required. |
| 165 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 166 | Supplying, installation, testing & commissioning of 7W, Exit Signage with 90 minutes Battery backup |
| 167 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 168 | Supplying, installation, testing & commissioning of voice alarm controller 6zone with suitable Amplifier, MP4 player (including button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. (PA CONSOL PANEL) |
| 169 | Supplying, installation, testing & commissioning of 6inches dia, 6wattsceiling speaker complete as required. |
| 170 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. speaker cable Single pair, 2-core, 1.5 sqmm |
| 171 | Supplying and drawing of 01 run of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required, with .23 AWG solid bare copper, flame retardant pvc jacket, in a box, and in compliance with ISO/IEC 11801, IEC 61156-5 standards.Make: Comscope/Panduit-Pannet/Dlink/Belden/Legrand |
| 172 | Supplying and fixing of following sizes of medium class 25 mm PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.Make: Universal/Supreme/Classic |
| 173 | Supplying and fixing of following sizes of medium class 50 mm PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. Make: Universal/Supreme/Classic |
| 174 | Supplying and laying of following size of HDPE pipe 63mm OD with ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II, complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 63 mm HDPE Pipe in duct/ trench as directed by engineer in charge.Make: prime/Reliance /Apollo/Rishi |
| 175 | Supplying, Installation, and labelling of dual (2) port flush type face plate with shutter suitable for Cat 6 cable termination with all necessary accessories as required.Make: Comscope/Panduit-Pannet/Dlink/Belden/Legrand |
| 176 | Supplying, Installation, Termination, Labelling& Testing of RJ-45 modular jacks, compliant with ISO/IEC 11801 Class E, ANSI/TIA - 568.2-D. It shall be compatible for solid 22-24 AWG diameter conductors for Data/Voice application. The RJ45 jacks shall also support power over LAN cabling as per IEEE 802.3bt Type-4 (Hi-PoE). The item shall cover all necessary accessories as required and directed by Engineer-in-charge.Make: Comscope/Panduit-Pannet/Dlink/Belden/Legrand |
| 177 | Supplying, Installation, Termination, Testing, Commissioning and Labelling of 24-port Patch Panel fully loaded with modular jacks, UTP Category 6, in compliance with ANSI/TIA-568-C.2 and ISO/IEC 11801 Class E transmitting standards. The patch panel shall have reliability for min. 1000 mating cycles, with metal rear cable manager to properly guide cables to point of termination and shall be supplied with Velcro straps for tying the cables. The patch panel shall have UL 94 V-0 rating and shall be complete with all necessary accessories as required.Make: Comscope/Panduit-Pannet/Dlink/Belden/Legrand |
| 178 | Supplying, Laying, Labelling& Testing of UTP Category 6 patch cords 2 mtrs, in compliance with TIA / EIA 568-8.2 and IEEE 802.3bt Type 4. The complete patch cord shall be LSZH - Low Smoke Zero Halogen compliant with plycarbonate RJ 45 plug.Make: Comscope/Panduit-Pannet/Dlink/Belden/Legrand |
| 179 | Supplying, Laying, Labelling & Testing of Armoured 12-core Single Mode Outdoor Fiber Optic Cable of Corrugated steel tape armoured and rodent protection,with gel-filled water-blocking technology, compliant with ANSI/TIA-568.E-3 anIEC 60794-1. It shall be laid in HDPE Pipe or in PVC pipes with all accessories and as directed by engineer-in-charge.Make: Comscope/Panduit-Pannet/Dlink/Belden |
| 180 | Supplying, Installation, Configuration and Testing of SFP Optical transceiver module suitable for 1G single mode fiber, hot plugable, with 1310nm wavelength capacity.Make : Cisco / HP / Juniper |
| 181 | Supplying, Installation, Splicing of pigtail & Testing of 12 Port LIU single modewith Fully Loaded LC Couplers and plates ,Sliding Model, Rack mountable, mounting kit, with Single mode LC PIG Tails of 1 mtrs.Make: Comscope/Panduit-Pannet/Dlink/Belden/Legrand |
| 182 | Supplying and Installation of LC to LC Single Mode Fiber Patch Cable 3 mtrs.Make: Comscope/Panduit-Pannet/Dlink/Belden |
| 183 | Supplying and laying of 150 X 50 MM GI cable raceways with top press cover and 10 mm threading rods clamps without powder coat. |
| 184 | Supplying, Installation, cabling, and labeling of 6Urack with bolted construction with the following details. 1) Bolted construction & suitable to assemble easility at site. 2) fully adjustable 19\" equipment mounting angles, 3) Front glass toughened with easy detachable hinges, 4) 1 nos. of PDU with plug sockets, 5) Lock with common Key, 6) Suitable fan for ventilation. MAKE :APW President/RITTAL/ legrande/ Netrack |
| 185 | Supplying, Installation, Configuration and Testingof managed L2 PoE Data switch for POE/Non POE deployments with 24-port 100/1000 MBPS RJ45 ports switch with Min of 2 x1Gb/10 Gb SFP/ SFP+ Interface ports, Switching Capacity of 128 GBPS (Including Switching frame + Stacking BW of 40GBPS) or higher, Forwarding packet throughput of min. 95 Mpps or higher, RAM 2GB or higher, Power supply of 370 Watts or higher ,stacking BW 40 GBPS or higher including stacking cable and connector or DAC , Including Power supply, fan, IPV6 certified logo,EAL or NDPP Certified.The item shall be supplied with OEM warranty of 1 year and service contracts for 1 year and OEM Authorization for the intended application and configuration.Make :Cisco / HP / Juniper |
| 186 | Supply, Installation, Testing, Commissioning and Integration of NATIVE BACNET/IP based DDC controllerwith embedded web application along with necessary I/O module, Power supply module etc., for monitoring and control of 04 Nos. of AHU with the tentative total I/O requirements of AI - 06; DI - 12; AO - 02; DO - 05. Soft integration of VFD and Energy parameters from the AHU Electrical panel(meters and switchgear) shall also be considered.The DDC controller shall be 32 bit microprocessor based networkable type controller with real time clock, historical database and with Minimum 8 MB RAM and 2 MB flash with Peer to Peer Communication. DDC controller should be able to be monitored and controlled in standalone mode through IP based web application independently as well has to be compatible for integration with the existing BMS software as avilable at the project site as necessary. The IP controller with in built RS 485 compatibility shall be provided. The controller with all accessories shall be housed in a suitableIP 42 rated enclosure. The quote shall include all system components and integration costs as specified and/or directed etc., complete. Controller shall be suitable to communicate with IP based HMI display to monitor & control the parameters as per the user requirement. The Control Panel shall be with lockable MS mounting cabinets duly powder coated connector strip, with necessary internal wiring and space to house controller & relays, connector strip current transformer, MCB, internal wiring etc., Note: 1. Min 20 % Spare I/Os to be considered in addition to the I/O requirements mentioned above.2. The power supplyfor all the components of DDC control system shall be provided by the contractor from the electrical control panel. 3. The controllers shall have ability to be integrated with the exisiting BMS software (if available) as per site conditions.4. The contractor shall submit detailed IO list, system architecture, technical data sheets of all the system components and GA drawing with wiring of the enclosure for approval form Engineer-in-charge before execution.5. Any slight changes in the IO requirements is deemed to be considered in the item and no additoinal charges shall be paid separately. |
| 187 | Engineering, Programming, Supply, Installation, testing & commissioning of IP based min. 10\" HMI touch screen display suitable to mount on wall with following features. a) DC power supply module required to power up.b) Min. 48 MB memory for application & min. 128 MB for internal memory. c) One no. of Ethernet port. d) Programming suitable for DDC operations. e) Graphics requirement as per the user requirement.Note: The HMI display has to be preferrably of the DDC controller make offered to have seamless integration and compatible for integration with the BMS software when required.The HMI shall be installed on the face plate of the BMS DDC panel enclosure made out of CRCA sheet. |
| 188 | Supply, Installation, Testing and integration of Differential Air flow switch to monitor filter status, fan run status with complete accessories required based on the HVAC system requirements and in complete as directed by Engineer-in-charge. |
| 189 | Supply, Installation, Testing and integration of Differential Pressure Transmitter for duct static pressure monitoring with a pressure range as required for the HVAC system with complete accessories as required in complete and as directed by Engineer-in-charge. |
| 190 | Supply, Installation, Testing and Integration of Duct type temperature and relative humidity (RH) sensor with all necessary mounting accessories as required and in complete as directed by Engineer-in-charge. |
| 191 | Supply, laying and end termination of 2C x 1.0 Sq.mm, unarmoured,multistrand,twisted,screened PVC cables in already laid conduit. The item shall also include end terminations as required as per site conditions. |
| 192 | Supply, laying and end termination of 2C x 1.5 Sq.mm, unarmoured,multistrand,twisted,screened PVC cables in already laid conduit. The item shall also include end terminations as required as per site conditions. |
| 193 | Supply, laying and end termination of 4C x 1.0 Sq.mm, unarmoured,multistrand,twisted,screened PVC cables in already laid conduit. The item shall also include end terminations as required as per site conditions. |
| 194 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete(i/c equivalent design mix) |
| 195 | Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50 metres lead. |
| 196 | Demolishing R.C.C. work manually/ by mechanical means including tacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in-charge. |
| 197 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar |
| 198 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 199 | Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. |
| 200 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size). |
| 201 | Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters,columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 202 | 12mm cement plaster of mix1:4 (1 cement : 4 fine sand)including cost and conveyance of all materials, labour charges, scaffolding, sundries etc complete as directed by the Engineer-in-Charge at all levels. |
| 203 | 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 204 | Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge. |
| 205 | Providing and making core cutting in RCC / concrete wall, slab/beam/column junction of size 100 to 200 mm dia with necessary specialisedequipment etc., complete |
| 206 | Providing and applying Two or more coats of Wall painting with premium acrylic emulsion paint of interior grade for Old work, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre,wall surfaces to be prepared by scraping away any loose particles, dust, etc., by washing and scrubbing and 1 coat of primer approved by manufacturer. The wall surfaces are smoothened by providing touchup putty of approved make and smoothened surfaces by sandpapered to achieve a smooth finish and two or more coats of Plastic emulsion paint are applied as per manufacturer specification.The rate shall include for finishing the paintingto obtainanevenanduniform shade as directedbythe Engineer-in-charge |
| 207 | Finishing walls with Acrylic Smooth exterior paint of required shade :Old work (Two or more coat applied @ 1.67 ltr/ 10 sqm) on existing cement paint surface |
| 208 | Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coats applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 209 | Providing and applying Two or more coats of Wall painting on new surfaces with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre,wall surfaces to be prepared by scraping away any loose particles, dust, etc., by washing and scrubbing and 1 coat of primer approved by manufacturer. The wall surfaces are smoothened by 2 to 3 coat of putty of approved make and smoothened surfaces by sandpapered to achieve a smooth finish and two or more coats of Plastic emulsion paint are applied as per manufacturer specification.The rate shall include for finishing the paintingto obtainanevenanduniform shade as directedbythe Engineer-in-charge |
| 210 | Structural steel work riveted, bolted or welded in built up sections, trusses and frame work, like angles, channels, plates, pipe, tuble, beams,flats etc. including cutting, hoisting, fixing in position with necessary wooden/steel scaffolding including providing applying two or more coats of synthetic enamel painting over a coat of approved steel primer all complete. |
| 211 | Preventive maintenance to be carried out during stipulated guarantee / warranty / defect liability period of 12 months from the date of commissioning and handing over. Servicing to be done for all the equipment and components once in a six months including all types of consumables. The agency should submit maintenance report of all the individual equipments duly signed by BEL engineer and agency. Necessary tools and tackles required for maintenance to be arranged by the agency including housekeeping of AHURoom, Electrical Room, ODU\"s, defects / failure occurred due to rodent shall be included in the scope etc., all as specified and/or directed etc., complete. |
| 212 | Comprehensive Annual Maintenance Contract (which means Repair / Replacement of defective parts supplied under this contract) for complete physical work including all systems / equipments / items provided under this contract covering all the equipments and components including all spares, compressors, refrigerant, oil, consumables, electrical components, cables, wires, tools, tackles etc. This CAMC Includes Validation of clean room once in a year and Maintenance activities of the entire system once in six months. The agency should submit Validation reports and maintenance report of all the individual equipment duly signed by BEL engineer and agency and Naval Dockyard. Agency should attend the major complaint / should repair/replace the defective parts of the system supplied under this contract within 2 working days and sort out any issues related to the systems under this contract. Agency should attend the minor complaint withing 3 working days. The agency shall attend the breakdown calls at any number of items during the CAMC period. Necessary tools and tackles required for maintenance to be arranged by the agency including housekeeping of Electrical Room, AHU room, ODU\"S, defects / failure occurred due to rodent shall be included in the scope etc, FOR FIRST YEAR OF CAMC period after the expiry of stipulated guarantee/ warranty/ defect liability period of the contract all as specified and/or directed etc., complete. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail