| 1 | Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. (As per HSR 23.7.6.2) PVC pipe of 25 mm dia. Make: D-Plast, Polycab, AKG |
| 2 | Supplying and drawing of 1 no UTP 4 pair CAT 6 LAN Cable in the existing surface/recess MS/PVc conduit as required (As per HSR 23.23.9)Make: Molex, D-Link, AMP,legrand |
| 3 | Supply Installation Testing and Commissioning of Wiring for Fire Alarm system with the following sizes 2 x 1.5 sq.mm of FRLS insulated copper conductor Double core 1100 volts grade cables in existing surface/recessed M.S. conduit etc. as complete as required. Make Finolex /Polycab / Plaza / Havells |
| 4 | Supply Installation Testing and Commissioning with the following sizes 2 x 1.5 sq.mm of FRLS insulated copper conductor Double core 1100 volts grade cables in existing surface/recessed M.S. conduit etc. as complete as required. Make Finolex /Polycab / Plaza / Havells |
| 5 | Supply Installation Testing and Commissioning of Micro processor based Fire Alarm Control Panel (FACP) with required 2 wire fault tolerant loop Cards (each loop should support 120 detector, 120 devices or 240 in any combination). The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFF respective control module when ever any alarm is triggered. Addresses of each Fire Alarm Detector/Module/Hooter/Manual Call Point etc., shall be legibly marked near/on respective sensors. It Should have provision for triggering/integrating the Gas Suppression System, PAVA System & Fire Fighters Telephone System. Panels should have provision of CPU Redudancy, and should work in degrade mode in case of CPU failure.other specifications as per DNIT in PDF. |
| 6 | SITC of Intelligent Addressable Photoelectric smoke Detector with 3600 LED, Electronically addressable complete with Mounting Base. The detector shall share the analog datapoints to the panel. The detector should have strong environmental adaptability by drift compensation with 2 programmable sensitivity levels. Operating Voltage shall be 16 to 28 Vdc. The detector shall operate in -10°C ~ 50°C Temperature and will give alarm in case of smoke detection. The Detector shall meet RoHS standard & shall confirm to IS2189 Standards and Duly Approved by LPCB/UL/FM with relevant IS/EN/NFPA Standard. (Detectors without inbuilt isolators may be considered with an additional isolator module after 20 devices) Make:GST/ Honeywell/ Edward |
| 7 | SITC of Intelligent Addressable Heat/Thermal Detector with 3600 LED view, Electronically addressable complete with Mounting Base. The detector shall share the analog datapoints to the panel. The detector should have strong environmental adaptability by drift compensation with 2 programmable sensitivity levels. The detector shall operate in -10°C ~ 50°C Temperature and will give alarm in case of ROR (Rate of rise +10 ºC in 1 min) or at a Fixed heat temperature at (58 ºC). Operating Voltage shall be 16 to 28 Vdc. The Detector shall meet RoHS standard & shall confirm to IS2189 Standards and Duly Approved by LPCB/UL/FM with relevant IS/EN/NFPA Standard. (Detectors without inbuilt isolators may be considered with an additional isolator module after 20 devices). Make:GST/ Honeywell/ Edward |
| 8 | Supply, Installation, Testing & Commissioning of Active Network Repeater Panel (NRP) with minimum 7\" 800 x480 resolution Color Touch Screen display having controls for reset, mute, accept, silence alarms and self test conforming to IS2189 standards, mapping 250 panels on network and 100000 event History. The NRP shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation. NRP can act as Remote Zone Annunciation panel and should work on 30 VDC & 1A as required to complete the installation and complete as per specification/drawings and as directed by Engineer In Charge and duly approved by LPCB/UL/FM with relevant IS/EN/NFPA Standard.Make:GST/ Honeywell /Edward |
| 9 | SITC of Intelligent Intelligent Addressable Type Manual Call Point having Surface or flush mounting option with Electronically Addressable type. Operating voltage 16 to 28 Vdc and shall complete with Back Box for Mounting Complete as required conforming to IS2189 Standards and Duly Approved by LPCB/UL/FM/relevant NFPA/EN Standard required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make:GST/ Honeywell / Edward |
| 10 | SITC of approved make Addressable Loop Powered Sounders cum Strobes or Sounder Strobe with Control Module and Power Supply with all accessories. Device should be Electronically Addressable type and should support 16 type programmable alarm tones with option to switch off light/sound for special applications. Operating voltage shall be 20 to 28 Vdc. Sound output of 86 dB @ 1m with High output Light technology and superior lens design optimize light outputs conforming to IS2189 Standards and device shall be compatible with the detector base and Duly Approved by LPCB/UL/FM/relevant NFPA/EN Standard Make:GST/Honeywell /Edward |
| 11 | Supply Installation Testing and Commissioning of minimum 1000 Mtr. Range Siren generator provided at the roof of the building with separate power suppl, relay etc.. Make: National/Kheraj/Heinrich |
| 12 | Supply Installation Testing and Commissioning of Co2 type Fire Extinguisher 4.5Kgs. Capacity, made from brand new seamless cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Squeeze Grip type valve with initial Charge as per IS: 15683:2006 specification, bearing ISI Mark Make:Safex / Minimax /Ceasefire |
| 13 | Supply Installation Testing and Commissioning of ABC Stored Pressure type Fire Extinguisher 6kg. Capacity (5 year warranty) bearing ISI Mark for fire fighting ABC class of fire extinguisher will be manufactured strictly as per BIS IS:683:2006 bearing ISI Mark EN3 615 approved powder Make:Safex / Minimax /Ceasefire |
| 14 | Supply Installation Testing and Commissioning of Glow Type Exit Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class - I material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour and material required to complete the job in all respect up to entire satisfaction of Engineer-in-Charge of work. Make Pearl/ Giolite/ Reputated. |
| 15 | Supply Installation Testing and Commissioning of 3 Meter Rubber pipe with EPDM Quality with squzeer grip nozzle for Jet length I.S.I Mark Make: Sunblaze, Handu Indane |
| 16 | Supply Installation Testing and Commissioning of Mechnical foam Type Fire Extinguisher 50 Leter capacity with OUTSIDE CYLINDER, CO2 CYLINDER 1 KG CAPACITY for Above AFFF foam compound for the extinguisher, 3000 mls capacity combine. Make:Safex / Minimax /Ceasefire |
| 17 | Supply Installation Testing and Commissioning of Horn Loudspeaker made with ABS, watered dust protected to IP 65,Sound pressure level at 15W/1W - 115/103 dB (SPL), Effective frequency range 500 Hz to 5 kHz, Rated power 15W to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work Make: Heinrich / Honeywell / Edward /GST |
| 18 | Supply Installation Testing and Commissioning of Class D amplifier high efficient 1000W Power/Booster amplifier Mains power supply 180~250 Volts AC | 50 Hz Power Requirement 800 VA Amplifier topology Class D >90% efficiency Frequency response 70 Hz to 20 KHz THD + N @ 1 KHz 0.1% Signal input / Output Balanced Line in LineOut - Phoeni SNR (dB) 102 Dynamic range 93dB Power Output 1000 watts | 100 Volt speaker output - Phoenix connector Damping factor @ 8 Ohm 300 Protection Output Short-circuit | Thermal shut-down Dimension (mm) 95.2 H x 431.8 W x 304.8 D Operating Temperature & Humidity -10°c to 50°c @ 90% relative humidity (non condensing) Cooling Forced Air cooling with Fan Make: Heinrich / Honeywell / Edward /GST |
| 19 | Supply Installation Testing and Commissioning of Wall Mount/Ceiling Speaker with operation 6 Watts to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. Make: Heinrich / Honeywell / Edward /GST |
| 20 | Supply Installation Testing and Commissioning of Stylish 6-zone call station, Six zone selection keys, all-call key and momentary PTT-key for calls Selectable gain, speech filter and limiter for improved intelligibility LED indications for zone selection, fault and emergency state Voltage range 18 – 24V Nominal sensitivity 85 dB SPL (gain preset 0dB) Gain preset plus 6 / 0 / -15 dB Equivalent input noise level 25 dBSPLA Frequency response 100Hz – 16kHz complete in all respectMake: Heinrich/ Honeywell/ Edward/GST |
| 21 | Supply Installation Testing and Commissioning of 5 Kg ceiling mounted fire extinguisher clean agent HFC 134A zero ODP, stored pressure type, pressure guage gross weight 7.7 Kg empty weight 2.7 Kg, can height 267 MM diameter 230 MM Discharge time less than Bsec, Auto discharge mechinism on temperture rise applicable on class A,B,C and electrically started fire can construction valve construction forging and mechinig internal coating of can expoxy powder coating sheet metal thickness 1.60 Mm Make:Safex / Minimax /Ceasefire |
| 22 | Supply, Installation, Testing & Commissioning of 5MP IP Network TDN Low-Light IR Rugged Bullet Camera, 1/2.8\" CMOS or better, 5MP (2592 x 1944) @ 25fps or better, triple stream at various resolution & Frame Rates, Min. Illumination required 0.005 lux @ F1.6 (color), 0 Lux IR On, 4 IR LEDs Smart IR with upto 50m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265 & H.264 High Profile & MJPEG , Triple stream, 2.7 to 13.5mm 5X motorized focus & zoom lens, BLC, HLC, 3DNR White Balance, Minimum Edge Intelligence Video Analytics : Video Motion Detection, Tampering, Loitering, Intrusion, & People Counting, 4 Privacy Mask, 8 Region Of Intreset, Defog, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, Dual channel Audio, 256GB SD card support, Alarm: In/ 1out, PoE (802.3 af) and 12V DC, Max 6W, IP 66, IK 10 vandal proof with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/T/M Compliant (Can be verified from Onvif Website and T profile must have secure streaming), UL, CE, FCC, EN, RoHS & NDAA Section 889 compliant. Make: Bosch/Axis/Honeywell. |
| 23 | Supply, Installation, Testing & Commissioning of 5MP IP Network TDN Low-Light IR Rugged Dome Camera, 1/2.8\" CMOS or better, 5MP (2592 x 1944) @ 25fps or better, triple stream at various resolution & Frame Rates, Min. Illumination required 0.005 lux @ F1.6 (color), 0 Lux IR On, 4 IR LEDs Smart IR with upto 50m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265 & H.264 High Profile & MJPEG , Triple stream, 2.7 to 13.5mm 5X motorized focus & zoom lens, BLC, HLC, 3DNR White Balance, Minimum Edge Intelligence Video Analytics : Video Motion Detection, Tampering, Loitering, Intrusion, & People Counting, 4 Privacy Mask, 8 Region Of Intreset, Defog, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, Dual channel Audio, 256GB SD card support, Alarm: In/ 1out, PoE (802.3 af) and 12V DC, Max 6W, IP 66, IK 10 vandal proof with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/T/M Compliant (Can be verified from Onvif Website and T profile must have secure streaming), UL, CE, FCC, EN, RoHS & NDAA Section 889 compliant. Make: Bosch/Axis/Honeywell. |
| 24 | Supply, Installation, Testing & Commissioning of 2MP 25X Outdoor IR PTZ Speed Dome, Video Format - PAL, Resolution - 2MP (1920 x 1080), Image Device - 1/2.8” Progressive CMOS sensor or Better, Minimum Illumination - Color: 0.005 Lux @ F1.6; 0 Lux - IR On or better Shutter Speed - 1/1 to 1/30,000 Sec, ONVIF - ONVIF S/G/T/M (Can be verifed from onvif Webiste, T profile must have secure straming), WDR - Minimum 120 dB True WDR, Focal range - Wide: 6 mm & Tele: 125 mm or Better (25x Optical Zoom), Angle of View - FOV H: 57°~3°, V: 33°~1° or Better, Video - Video Encoder - H.265 HEVC, H.264, MJPEG dual stream, Main Stream - 1920 x 1080, 1280 x 720 @ up to 50 fps, Second Stream - 704 x 576/640 x 480, 352 x 288(PAL) @ 25 fps, 3rd Stream - 640 x 480/352 x 288, 320 x 240 @ 25 fps, Protocols - IPv4, IPv6, TCP / IP, HTTP, HTTPS, RTSP / RTP / RTCP, IGMP / Multicast, SMTP, DHCP, NTP, DNS, QoS, SNMP, 802.1X, UDP, ICMP, ARP, TLS, Security - User account and password protection, HTTPS, IP Filter, Digest authentication, TLS1.2 only, Stream encryption, AES128 / 256, SSH / Telnet closed, Region of Interest - 8 ROI, Defog - Yes, EIS - Yes , S/N Ratio - > OTHER SPECIFICATIONS AS PER dnit IN pdf. |
| 25 | Supply , Installation , Testing and commissioning of 32 Channel NVR (Network Video Recorder) Embedded Linux based for recording upto 32CH with 04 nos. SATA HDDs minimum 40TB storage or more (recording requirement all cameras recording at D1, 25fps for 30 days), H.265 HEVC/H.264/MJPEG codec decoding, Front Panel with LEDs Indication for Power & HDDs Status, 3 nos. USB, ONVIF S, Time Sync with NTP, Encrypted Streaming & Control, 2-Way Audio Line & Out, PTZ Operation Pan, Tilt, Zoom, Support, Pre & Post Alarm Recording Support, Recording/ Evidence Clip Export to USB, 16 Channel Synchronous Playback, Playback control i.e Play, Pause, Stop, Fast Forward, Backward, Speed Control, Timeline & Zoom; Snapshot, Web Client, Central Monitoring Software, iPhone; iPad; Android based Mobile clients, 02HDMI & 01VGA Output, 04 On Board HDDS each up to 10TB, Alarm 16 ch alarm inputnos.), 192 Mbps throughput, NDAA Section 889 Compliant, Operating Temperature –10°C to 55°C, Certification : Certifications: ONVIF compliant, CE, FCC, EN, NDAA & RoHS compliant. Including fixing accessories and cable termination with required connectors/Jack, complete in all respect as per instruction of engineer in-charge. Make: Bosch/Axis/Honeywell |
| 26 | Supply , Installation , Testing and commissioning of Hard Drive for storage 8 TB Make: WD / Segate / Toshiba |
| 27 | Supply, Installation, Testing and comissioning of 16 PORT 10/100/1000BASE-T POE ports complete in all respect upto entire satisfaction Engineer in charge of works.Make:Zyxel / Cisco / Netgear |
| 28 | Supply Installation Testing and Commissioning of PoE Switch:- Switch should have total including 8 Nos. of 10/100/1000 Mbps Ethernet PoE Ports complete in all respect upto entire satisfaction Engineer in charge of works.Make: Zyxel /Cisco /Netgear |
| 29 | Supply, Installation, Testing and Commissioning of Wall Mount 9U Rack ,Front Glass Door (tinted,Toughened) with Lock & Key, 2 pairs of 19\" Mounting Rails with U-Marking,Welded Side Walls With Metal Engraved D-Link Logo,1U Cable Manager (1), Hardware Packet (1 Pkt),6 Socket 5 Amp. Power Distribution Unit (1 No)Roof Mounted Fan Unit / 90 CFM /230V AC (1 No).Rack should be as per DIN41494 Standards.OEM must be ISO 9001,14001 certified complete in all respect upto entire satisfaction Engineer in charge of works. Make: Comrack / Valrack/ Dynamic |
| 30 | Supply Installation Testing and Commissioning of 43” LED Monitor, Full HD, HDMI Port, Component Video Inputs, 1 Digital audio Out, VGA Port. to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. Make Samsung / L.G / Panasonic. |
| 31 | Supply Installation Testing and Commissioning of Point to point HDMI extender ( Transmitter / Receiver) set, Supports HDMI 2.0 and IR signals, up to 4K @60Hz 4:4:4, HDR, 18G, HDCP 2.2, Extends 4K or 1080p HDMI signal up to 230 feet (70m) over a single CAT5e/6 cable. HDMI loop out on transmitter. Bi directional IR pass through. Supports video resolution down scaling, the 4K input can be automatically degraded to 1080p output on receiver for compatibility with legacy 1080p display. Make: Extron /Kramer /Heinrich |
| 32 | Supply Installation Testing and Commissioning of L-3 Switch PoE-capable 10/100/1000 24 port and associated accessories will be provided with switch complete etc. as required.Make: Zyxel /Cisco /Netgear |
| 33 | Supply Installation Testing and Commissioning of PoE L-2 Cloud Manageability technology for 28 Port Smart Managed PoE Switch 24x Gigabit Copper PoE and 4x Gigabit dual pers.completes the job in all respect up to the entire satisfaction of Engineer-in-charge of the work. Make: Zyxel /Cisco /Netgear |
| 34 | Supply Installation Testing and Commissioning of 24-port 19` 1 U jack panel which Should Be made of sheet steel 1.5 mm, Should be 19` 1U straight Jack Patch Panel, 24-port,Should have integral cable management Metal shelf, Should accept Shielded as well as Unshielded jacks, Should have rear cable management shelf metallic powder coated.Make: AMP / Molex / R&M |
| 35 | Supply Installation Testing and Commissioning of Wall mounted 12U enclosure of dimension 600W X12UX500D with front sheet steel glass door, top and bottom cCover with cable entryprovision, integrated side walls,1 pair of 19\" angles with wall mounting provision, captivehardware(pack of 20) complete in all respect upto entire satisfaction Engineer in charge ofworks. Make: Comrack /Valrack/Dynamic |
| 36 | Supplying, Installation, Testing and commissioning of CAT6 Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as requiredMake: AMP / Molex / R&M |
| 37 | Supply Installation Testing and Commissioning of UTP Cat - Mounting Patch Cords complete in all respect up to the entire satisfaction of Engineer-in-Charge of the work. Make: AMP / Molex / R&M 3 ft length |
| 38 | 5 ft length |
| 39 | Supply Installation Testing and Commissioning of 6 core mm fiber cable (per meter) complete with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer - in - charge of the work. Make- Molex/ R&M / AMP |
| 40 | Supply Installation Testing and Commissioning of 12F, 1U, LC, LIU Loaded with Pigtails, Splice tray, Couplers as per specification complete in all respects up to the entire satisfaction of Engineer-in-charge of work Make- R&M / Molex/AMP |
| 41 | Supply Installation Testing and Commissioning of PATCH CORD LC-LC SM DUPLEX Lenth- 3mtr. as per specification complete in all respects up to the entire satisfaction of the Engineer-in-charge of work.Make- AMP / R&M / Molex |
| 42 | Supply Installation Testing and Commissioning of 1G SFP module as required (For All Switches) complete in all respect upto the entire satisfaction of Engineer-in-charge of work Make: Zyxel / Cisco / Netgear /Alcatel / Juniper |
| 43 | Supply Installation Testing and Commissioning of 2 Core Power Cable 1.5 sqmm. complete in all respects up to the entire satisfaction of the Engineer-in-charge of work Make: Finolex / Polycab / Havells |
| 44 | Supply Installation Testing and Commissioning of Nurse Call Master Controll Unit with the Display Unit Having Power Supply Either Built in or External. The Display unit indicate the point of call by displaying a Number and Sounding Alarm. The System should be able to Connect upto 24 patient or bed unit Devices in one system in any Combination.The system should come with Complete battery backup, mute and reset buttons. Multiple units can be installed on a system to alert staff where assistance is required. master control unit with 24 bedsMake: Rauland/Heinrich/Randa |
| 45 | Supply Installation Testing and Commissioning of Nurse Call Master Controll Unit with the Display Unit Having Power Supply Either Built in or External. The Display unit indicate the point of call by displaying a Number and Sounding Alarm. The System should be able to Connect upto 60 patient or bed unit Devices in one system in any Combination.The system should come with Complete battery backup, mute and reset buttons. Multiple units can be installed on a system to alert staff where assistance is required.Master controll unnit with 60 bed .Make: Rauland/Heinrich/Randa |
| 46 | Supply Installation Testing and Commissioning of Patient/bed Side Unit unit must comprise with two call buttons both on plate & handle much easier for Patient to Call should have Unique Talk Function, Connect the call button to the Phone, Let Patient Talk Remotely with the nurse directly. Having HD built-in Speakers, high volume & clear voice, Establish a new bridge between nurse & patient. With PC & ABS enclosure.Working Current <18mA, Standby Current <1uA, Power <10m , Max Working Distance 500-700M OR MORE &IP Grad IP44. Make: Rauland/Heinrich/Randa |
| 47 | Supply Installation Testing and Commissioning of Waterproof unit/toilet unit having pull chord which is specially design for toilets that allows patients in health care settings to alert a nurse or other health care staff member remotely of their need for help. When the chord attached to unit is pulled, a signal alerts staff at the nurse\"s station, others simply beep or buzz at the station.Working Current<18mA, Standby Current <1uA, Power <10mW, Max Working distance: 500-700M or more IP Grade: IP44 Make: Rauland/Heinrich/Randa |
| 48 | Supply Installation Testing and Commissioning of door lamp should blink min. 4 differenct colours to indicate the position of caller ward and status of call.Make: Rauland/ Heinrich/ Randa |
| 49 | Supply Installation Testing and Commissioning of 1.5 sq.mm PVC unsheathed copper conductor cable two core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make: Polycab/Havells/ Finolex |
| 50 | SITC of Wall mount heavy duty for 55 inch display with durable finish and high strength supporting the weight and dimensions of the display. Make :Heinrich / AVAIVI/ Promark |
| 51 | Supply Installation Testing and Commissioning of 42U, 800w x 1000d, 19` Comms equipment rack with front 19` rails and dual 8 to 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands complete the job in all respects up to the entire satisfaction of Engineer-in-charge of work Make: Velrack / Comrack / Netrack |
| 52 | Supply Installation Testing and Commissioning of IMS Based Voice Communication System with 200 Port Voicemail,1 PRI Trunk lines (30x1Ch) Circuit with CLIP Facility, Gateway equipped with 16 Port FXS,16 Port FXO, 4 Ethernet ports, 1 OFC Port in same gateway, Server with min Intel quad core processor, 8GB RAM, Dual Power supply, 300 IP users License, 10 Voice logger license, 02 Each IP based Operator Console with 60 hot keys, 64 Party Conference, Speed Dial, Music on Hold, Internal/ External ring difference, Call Barring, Call Pickup, Seamless Audio & Video calling with Captive network over private 4G/5G Network with BLF over IP Phone of mobile users. the server system should be redundant 100%Makes: Siemens /Coral/ Cisco |
| 53 | Supply Installation Testing and Commissioning of Type 2 IP Phone with min 4.3 inch display, 6 VoIP accounts, Bluetooth, Wifi, USB port, HD Voice, Graphic color LCD with backlight. Makes: Siemens / Coral/ Cisco |
| 54 | SITC of a 55\" Industrial Display: The display shall feature a 55\" panel with D-LED backlighting, delivering 4K UHD resolution (3840×2160). It shall offer a minimum brightness of 450 cd/m² (typically 500 cd/m²), a contrast ratio of 1200:1, an 8 ms response time, at a 60 Hz refresh rate and wide 178° viewing angles horizontally and vertically. The display shall have a minimum operational lifespan of 50,000 hours, a 72% NTSC colour gamut, and shall support 1.07 billion colours (8-bit+FRC) to facilitate accurate colour reproduction. The unit shall be further enhanced by an optional OPS slot powered by DC 12V/5A for future modular expansion and shall offer versatile connectivity through dual HDMI 2.0 ports (supporting up to 3840×2160@60Hz), one VGA input (supporting up to 1920×1080@60Hz), one PC audio port via a 3.5mm mini connector, one USB 2.0 Type-A port, one SPDIF port (maximum transfer speed of 16Mbps), and one RS232 port, all integrated within a compact form factor measuring 1243.2 mm (W) × 69.6 mm (D) × 714 mm (H). Additionally, the display shall comply with stringent electrostatic discharge immunity requirements in accordance with GB/T 17626.2, withstanding contact discharges of 4KV and air discharges of 8KV (Level B) to ensure robust performance in environments prone to static electricity.) Make: AVAIVI/ Heinrich / Promark |
| 55 | Supply Installation Testing and Commissioning of Digital signage media player : CPU Octa-core amlogic S912 ARM Cortex-A53, GPU/ Graphics Mali T-820 MP3 OpenGL ES 3.2, OS Android 6.0.1, Memory 4GB DDR3, Storage 64GB, Wi Fi 802.11/b/g/m with 2dB antena, Ethernet 10/100 Mbps, Bluetooth 4.0, O/P Ports HDMI 2.0,USB 2 USB 2.0 ports , SD SD card slot, support up to 32 GB, Resolution 3840 x 2160, complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. Make: Extreme Media / AVAIVI/ Promark /Heinrich |
| 56 | Supply Installation Testing and Commissioning of Workstation capable of running the Device Health Monitoring and Content Management Software for Digital Signage Displays. The workstation shall be built on a quad core Intel® Core™ i7 (or equivalent) processor with a minimum clock speed of 2.0 GHz or better, supported by 16GB DDR4 memory and a 500GB solid state drive for the operating system and application installation. It shall feature integrated graphics suitable for digital signage operations, at least one Gigabit Ethernet port for reliable network connectivity and run on Windows 10/11 Professional or a compatible Linux distribution. The unit shall be designed for continuous 24/7 operation in a compact desktop form factor with effective thermal management and low power consumption. The Contractor shall provide full documentation, a minimum two year warranty, and provisions for on site technical support.. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. Make: HP, Dell, Lenovo. |
| 57 | Supply Installation Testing and Commissioning of Comprehensive Central Content Management Software solution designed for digital signage environments. The software shall be web based and enable centralised scheduling, deployment, and management of multimedia content across a network of displays. It shall provide an intuitive graphical user interface (GUI) with multi user, role based access control and support for real time monitoring, reporting, and remote diagnostics. The solution shall integrate seamlessly with various digital signage hardware platforms and support standard protocols and API integrations for third party systems. Key functionalities shall include content creation tools, scheduling and playback management, digital asset management, automated alerts, and detailed audit trails for user activities. Make: Heinrich / AVAIVI/ Promark |
| 58 | Supply Installation Testing and Commissioning of Premium High Speed HDMI 2.0b flexy cable, Bandwidth up to 18Gbps, Enables transmission of High Dynamic Range (HDR10), Dolby Vision and Hybrid log –gamma (HLG) video, Enables transmission of Consumer Electronics Control (CEC), Audio Return Channel (ARC) and HDMI Ethernet Channel (HEC). Make Stecker/Krammer/Cisco/HONEYWELL/HEINRICH |
| 59 | Supply & erection of On-Line- UPS rating 10 KVA, indicative backup time 90 minutes with isolation transformer suitable for three phase AC input & three phase AC output, floor mounted type complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make Microtek/ Emerson / Delta |
| 60 | Supply & erection of 12 volt 65Ah SMF battery complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make Exide/ Amaron/ Luminious |
| 61 | Supply & erection of 16 mm angle MS stand of 65 kg. weight of dimension 50mm (L) x 60mm (H) x10 mm (W) duly painted used to accommodate 20 nos.12 volt 65Ah SMF batteries complete in all respect upto the entire satisfaction of Engineer in charge of the work. |
| 62 | Supply & erection of interlink connector complete in all respect upto the entire satisfaction of Engineer-in-charge of work Please Enable Macros to View BoQ information |