| Sl. No. | Item Description |
| 1 | M&L vacuuming complete system of central air conditioning plant at(3X75TR) with double stage vacuum pump of(-) 2Kg/cm² vacuum pressure after repairs to compressor or repair in refrigeration system, charging the dry nitrogen gas,and hold up to 24 hrs and rectifing the leakage if any by repairing the leakages of service valve/ gas pipe line including top up the compressor oil and charging R-407c refrigerant gas at plant all as specified and directed. Note :- Referigerant Gas R-407c, Nitrogen gas and compressor oil will be measured and paid separately under relevant Items.Once charged the R - 407c gas it should hold in the system minimum six month, if the gas leaked from the system the contractor has to charged gas at his own cost. |
| 2 | Dismantling andtaking up unserviceable electric motors of any size/ capacity and make from foundations after disconnecting electric connections and transportation from site to work shop for carrying out repairs / rewinding of motors as required incluidng re-fixing in position and connectingand testing complete as directed. |
| 3 | M&L opening up short circuited electric induction motor, 5 HP, 3 phase AC 440 Volts, cutting and removing the burnt stator winding coils complete and re-winding the same with super enamelled copper conductor wires of appropriate size as per the existing gauge including cleaning of slots,all necessary insulating materials, varnishing, dryining complete all as specified and directed. |
| 4 | M&L opening up short circuited electric induction motor, 15 HP, 3 phase AC 440 Volts, cutting and removing the burnt stator winding coils complete and re-winding the same with super enamelled copper conductor wires of appropriate size as per the existing gauge including cleaning of slots,all necessary insulating materials, varnishing, dryining complete all as specified and directed. |
| 5 | S&F terminal connector for motors 5 HP complete all as specified and as directed. |
| 6 | S&F terminal connector for motors 15 HP complete all as specified and as directed. |
| 7 | S&F PVC fan blade for motors 5 HP complete all as specified and as directed. |
| 8 | S&F PVC fan blade for motors 15 HP complete all as specified and as directed. |
| 9 | M&L Repairs to squirrel cage induction motor shaft by welding / grinding, polishing to required sizes for motors 5 HP, complete all as specified and directed. |
| 10 | M&L Repairs to squirrel cage induction motor shaft by welding / grinding, polishing to required sizes for motors 15 HP, complete all as specified and directed. |
| 11 | M&L Replacement of end ball bearing suitable for motor 5HP, complete all as specified and directed. |
| 12 | M&L Replacement of end ball bearing suitable for motor 15HP, complete all as specified and directed. |
| 13 | M&L for carrying out repair to Centrifugal pump 15 HP after dismantling the assembly complete for replacement of worn out spares such asimpellers, pump shaft, sleeves, bushes etc; includingfilling, turning & polishing works to pump shaft, GM impellers as necessiated, reassembling the pump after repairs and testingcompleteincluding applying a coat of water proof epoxy paint to the external surfaces of pump all as specified and directed Note : Any spares requires to be replaced will be measured and paid separately |
| 14 | S&F GM impellers for Centrifugal pump15 HP with key and bushes complete all as specified and directed. |
| 15 | S&F Pump Shaft steel for Centrifugal pump15 HP with key and bushes suitable for 15 HP Centrifugal pump, complete all as specified and directed. |
| 16 | S&F Bearing & bushfor Centrifugal pump15 HP with key and bushes suitable for 15 HP Centrifugal pump, complete all as specified and directed. |
| 17 | S&FMotor coupler sleeve with key suitable for Centrifugal pump15 HP, complete all as specified and directed. |
| 18 | S&F PVC insulated and sheathed FRLSH submersible copper cable, 3 core, with multi-stranded copper conductor of 1100 volts grade and size 10 sq mm complete all as specified and directed. |
| 19 | S&F PVC insulated and sheathed FRLSHcopper cable, Twincore, with multi-stranded copper conductor of 1100 volts grade and size 16 sq mm complete all as specified and directed. . |
| 20 | M&L chargingrefrigerant gas R-407c to refrigeration andA/C system and testing for leakage insystem and commissioning complete all as specified and directed. |
| 21 | M&L chargingrefrigerant gas R-410a to refrigeration andA/C system and testing for leakage insystem and commissioning complete all as specified and directed. |
| 22 | M&L chargingrefrigerant gas R-32 to refrigeration andA/C system and testing for leakage insystem and commissioning complete all as specified and directed. |
| 23 | M&L chargingrefrigerant gas R-22 to refrigeration andA/C system and testing for leakage insystem and commissioning complete all as specified and directed. |
| 24 | Supply andchargingof compressor oil N-68 after flushingcompressor and testing commissioning all as directed. |
| 25 | Supply and chargingof nitrogen gas for leak testing of central A/C plant system complete all as directed. |
| 26 | M&L in repair, Pressuregauge 4\" dia suitable for chilled water pipeline as per site withflair nuts/adopter at both ends,range of gauge 0 to 150 Psi complete all as directed. |
| 27 | M&L in repair, wornout / unserviceable\"V\" beltfor powertransmission of size A-95 complete all as directed. |
| 28 | M&L in repair, wornout / unserviceable\"V\" beltfor powertransmission of size A-41 complete all as directed. |
| 29 | M&L in repair, wornout / unserviceable\"V\" beltfor powertransmission of size A-40 complete all as directed. |
| 30 | M&L in repair, wornout / unserviceable\"V\" beltfor powertransmission of size A-43 complete all as directed. |
| 31 | M&L in repair, thermometer to condenser / chiller inlet or outlet pipe including addition alteration to pipe line for fixing thermometer Range 0 F to 100 F complete all as directed. |
| 32 | M&L in repair,pressure relief valve ofcondensor 3/8\" BSPthreaded suitablefor 300 PSI complete all as directed. |
| 33 | M&L in repair,HRC fuse 6 Amps complete all as directed. |
| 34 | M&L in repair,HRC fuse 10 Amps complete all as directed. |
| 35 | M&L in repair,HRC fuse 16 Amps complete all as directed. |
| 36 | M&L in repair,HRC fuse 32 Amps complete all as directed. |
| 37 | M&L in repair,HRC fuse 63 Amps complete all as directed. |
| 38 | M&L in repair,HRC fuse 100 Amps complete all as directed. |
| 39 | M&L in repair, AHU filter of various sizes made of wire mesh for air filteration upto 15 microns complete all as directed. |
| 40 | M&L in repair, single phase preventer in electric panel board at central type AC plants complete all as directed. |
| 41 | S&F in repair, power contactor 4 pole, coil voltage 230/415 Volts, 32 Amps complete all as directed. |
| 42 | S&F in repair, power contactor 4 pole, coil voltage 230/415 Volts, 40 Amps complete all as directed. |
| 43 | S&F in repair, power contactor 4 pole, coil voltage 230/415 Volts, 63 Amps complete all as directed. |
| 44 | S&F in repair, bimetal over load relay, 16 Amps complete all as directed. |
| 45 | S&F in repair, bimetal over load relay, 20 Amps complete all as directed. |
| 46 | S&F in repair, bimetal over load relay, 32 Amps complete all as directed. |
| 47 | S&F in repair, MCCB 4 Pole, 100 Amps,thermal magnetic release,adjustable overload and short circuit setting 415V ,50 Hz ,breaking capacity 50 KAcomplete all as specified and as directed |
| 48 | S&F in repair, MCCB 4 Pole, 63 Amps,thermal magnetic release,adjustable overload and short circuit setting 415V ,50 Hz ,breaking capacity 50 KAcomplete all as specified and as directed |
| 49 | S&F in repair, MCCB 4 Pole, 250 Amps,thermal magnetic release,adjustable overload and short circuit setting 415V ,50 Hz ,breaking capacity 50 KAcomplete all as specified and as directed |
| 50 | S&F in repair, MCCB 4 Pole, 200 Amps,thermal magnetic release,adjustable overload and short circuit setting 415V ,50 Hz ,breaking capacity 50 KAcomplete all as specified and as directed |
| 51 | S&F in repair, MCCB 4 Pole, 160 Amps,thermal magnetic release,adjustable overload and short circuit setting 415V ,50 Hz ,breaking capacity 50 KAcomplete all as specified and as directed |
| 52 | S&F in repair, Digital LED Volt meter Meter (50-520 Volts) 3 Phase, Class 1, 4W suitable for measuring Alternating Voltagecomplete all as specified and as directed |
| 53 | S&F in repair, Digital LED Ammeter Meter 3 Phase, Class 1, 4W suitable for measuring Alternating Currentcomplete all as specified and as directed |
| 54 | S&F in repair, CT of suitable ratio fot LT 3 Phase system, 1.1 KV grade, single burden, general purpose, of CT ratio as per site requirement complete all as specified and as directed |
| 55 | S&F in repair, LEDIndicator Lamps for each phasesincluding holders and of colours red / yellow / blue etccomplete all as specified and as directed |
| 56 | S&F in repair, Timer Switch of startercomplete all as specified and as directed |
| 57 | S&F in repair, MCB 4 Pole, 63 Amps,C Curve, breaking capacity 10KAcomplete all as specified and as directed |
| 58 | S&F in repair, Push button assembly in green or red colourcomplete all as specified and as directed |
| 59 | S&F in repair, add-on block with 2NO - 2NC contacts complete all as specified and as directed |
| 60 | S&F in repair, butterfly valve of dia 100mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washer complete all as specified and as directed |
| 61 | S&F in repair, NRV of dia 100 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washer complete all as specified and as directed. |
| 62 | S&F in repair, communication cables 4 core and electric cables 1.5 sqmm size including necessary accessories duly fixed from outdoor to indooras per existing at site complete all as specified and as directed. |
| 63 | S&F in repair,outdoor fan motor as per sample of CentralAC plant 75 TRModel No. AM160MXVAGC of make Samsung including making connections as per existing at site complete all as specified and directed . |
| 64 | S&F in repair, Out Fan Board as per sample of CentralAC plant 75 TRModel No.AM160MXVAGC of Make Samsungincluding making connections as per existing at site complete all as specified and directed . |
| 65 | S&F in repair, Outdoor Mother Board as per Sample of CentralAC plant 75 TRModel No.AM160MXVAGCof Make Samsungincluding making connections as per existing at site complete all as specified and directed . |
| 66 | S&F in repair,Outdoor Main PowerBoard as per Sample of CentralAC plant 75 TRModel No.AM160MXVAGC of Make Samsungincluding making connections as per existing at site complete all as specified and directed . |
| 67 | S&F in repair,DLT Sensor as per suitable size as per sample of CentralAC plant 75 TRModel No.AM160MXVAGC of Make Samsungincluding making connections as per existing at site complete all as specified and directed . |
| 68 | S&F in repair,Compressor for 75 TR Central AC Plant working Voltage 380-400 Volts , andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes, hand shut off valves, relays, starting and running capacitorsetc. complete all as specified and as directed. |
| 69 | S&F in repair,Expansion Valve for CentralAC Plant 75 TRModel No.AM160MXVAGC of Samsung complete all as specified and directed |
| 70 | S&F in repair, Solenoid Coil for Expansion valve complete all as specified and as directed. |
| 71 | S&F in repair, Compressor for 8.5 TR Ductable AC Plant working Voltage 380-400 Volts, andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes, hand shut off valves, relays, starting and running capacitorsetc.complete all as specified and as directed. |
| 72 | S&F in repair, Room Sensor for 8.5 TR Ductable AC Plant working Voltage 380-400 Volts, including making connections as per existing at sitecomplete all as specified and as directed. |
| 73 | S&F in repair, Coil Sensor for 8.5 TR Ductable AC Plant working Voltage 380-400 V,including making connections as per existing at site complete all as specified and as directed. |
| 74 | S&F in repair, Remote Control Unitfor 8.5 TR Ductable AC Plant working Voltage 380-400 V, including making connections as per existing at site complete all as specified and as directed. |
| 75 | S&F in repair, OutdoorFan Motorfor 8.5 TR Ductable AC Plant working Voltage 380-400 V,including making connections as per existing at site complete all as specified. |
| 76 | Dismantling of defective worn out wiring of Indoor unit of split AC of capacity 8.5 TR including unserviceable cordless electronic remote control, supply and fixing PCB (Printed circuit Board) & Visual Eye demo plateto suit /match the existing system complete all as specified and directed. |
| 77 | M&L Servicing,Cleaning Condensor Coil with chemicals, Caliberation of dampers, testing of control wiring, greasing of movable parts, and checking all safety valves and relays andperiodical maintenance including supply of all consumable lubricants and repair or replacement of all minor components (spare parts) which may occur due to wear and tear except part are specified in relevant items of BOQfor entire package air condition unit 1x 8.50 TR at 180 MH including cleanning entire installation monthly andmaintenance of necessary records & documents all as specified and directed. Make of above unit:-Blue Star.Note :- AnyRepairs doneduring servicing will be measured and paid under respective item . |
| 78 | M&L Servicing,Cleaning Condensor Coil with chemicals, Caliberation of dampers, testing of control wiring, greasing of movable parts , and checking all safety valves and relays andperiodical maintenance including supply of all consumable lubricants and repair or replacement of all minor components (spare parts) which may occur due to wear and tear except part are specified in relevant items of BOQ here-in-after for entire package air condition unit 3 X 75 TR at 11 Paraincluding cleanning entire installation monthly andmaintenance of necessary records & documents all as specified and directed. Make of above unit:-Blue Star.Note :- AnyRepairs doneduring servicing will be measured and paid under respective item . |
| 79 | M&L Servicing Cleaning Condensor Coil with chemicals, Caliberation of dampers, testing of control wiring, greasing of movable parts , and checking all safety valves and relays andperiodical maintenance including supply of all consumable lubricants and repair or replacement of all minor components (spare parts) which may occur due to wear and tear except part are specified in relevant items of BOQ here-in-after for VRF AC 120 TR Air Cooled VRF type including 10 Nos Cassettes type AC of capacity 4 TR , 2 Nos AHU, 02 Nos Outdoor unit Model No. AM160MXVAGC of capacity 45KW and04 Nos Outdoor unit model No. AM300MXVAGC of capacity 84 KW including cleanning entire installation monthly andmaintenance of necessary records & documents all as specified and directed. Make of above unit:- Samsung Note :- AnyRepairs doneduring servicing will be measured and paid under respective item . |
| 80 | Notesfor item no. 77to79(a) The contractor shall provide of high skilled AC mechanic/Special engineer required for fault occured during currency of contract period if required. The cost of the same shall be deem to be included above quoted rate(b) Make and model of part to be replaced shall be same as existing at site or as per OEM .(c) Contractor shall maintain the temp of AC Plant as per the direction of GE/AGE/user or his rep within design limit.(d) During the entire contract period any defective components to be repair/replace to make plant/machinery fully functional. (e) Make and model of part to be replaced shall be same as existing at site or as per OEM .(f) The cost of transportation and other necessary equipments shall be arranged/brought by contractor in this effect (g)In case any experts technical /Engineer require for major faults of plants shall be provided by the contractor without any extra cost of the department. (h) The compressorshall be checked for its proper functioning and if any defect is found the same will be reapaired/ replacedby the contractor and will be measured and paid under respective item..(j) Safety controls such as pressure cut outs shall be tested or proper functioning and in case of any malfunctioning they will be either repaired or replaced accordingly by the contractor and will be measured and paid under respective schedule.(k) Condenser Coil & Evaporator coil.(Cooling coil ) shall be inspected and cleaned, if necessary and for any defect found , the same shall be repaired/replaced by contractor and will be paid under respective schedule.(l) Repairs to refrigerant piping/ducting line due to system problems shallbe repaired by contractor and will be measured and paid under respective item.(m) Refrigerant gas shall be topped up in the system as and when necessary by the contractor. and will be measured and paid under respective item (n) The cost of transportation and other necessary equipment shall be arranged/brought by the contractor in this effect , hence the bidder/tenderer is advised to visit the site and assess the quantum of the work to be carried out in the contract and quoted there rate accordingly |
| 81 | Supply, fabrication , installation and testing of GSS sheet metal of 22 Gauge (0.8 mm thick) factory /Site made rectangular ducts, complete with MS frame structure and necessary supports using thread roads and anchor bolts, supply air collars, vanes complete with splitterdamper, duct damper, vanes etc fabricated outof galvanized sheet class VIII conforming to IS 277. The duct fabrication and installation shall confirm to IS 655-2006 all dampers, splitters shall be fabricated out of GS sheet of two gauges higher than the duct piece having these fittings complete all as specified and directed . Note :- Angle iron used for fabrication will be measured and paid under respective item of schedule. |
| 82 | S&F thermal insulation on the sheet metal duct wrapped with Aluminium foil faced class \"O\" 25 mm thick closed cell nitrile rubber onducts installed inside the rooms complete all as specified and directed. |
| 83 | Dismantling carefully of Indoor unit of Capacity 4TR from its existing position including opening of copper pipes ,control wiring, PCB ,SMPS Board Sensors ,Expansion Valves, runner and connected items and refixing after repair complete with all accessories Complete all as specified and directed . Note:-(a) Required tools & plant required shall be included in the rate quoted.(b) Any damage occurred during lifting/ transporting, the firm will be responsible to rectify such defect free of cost |
| 84 | S&F in repair, defective VRF indoor motors of capacity 4 TRas per existing at site of Model Model No.AM160MXVAGC of Samsung complete all as specified and as directed. . |
| 85 | S&F in repair, defective indoor PCB of casatte AC of capacity 4 TR and necessarycontrol wiringcomplete all as specified and as directed |
| 86 | S&F in repair, indoor SMPS Board of Casatte AC ofcapacity 4TR, complete and necessary control wiring all complete all as specified and as directed |
| 87 | S&F in repair,indoor Runnerof Casatte AC ofcapacity 4 TR, complete all as specified and as directed |
| 88 | S&F in repair, VRF outdoor fan motor as per sample of VRF AC plant 45 KW Model No. AM160MXVAGC of make Samsung including making connections as per existing at site complete all as specified and directed . |
| 89 | S&F in repair, Out Fan Board as per sample of VRF AC Plant 45 KW Model No.AM160MXVAGC of Make Samsung including making connections as per existing at site complete all as specified and directed |
| 90 | S&F in repair, Outdoor Mother Board as per Sample of VRF AC Plant 45 KW Model No.AM160MXVAGCof Make Samsung including making connections as per existing at site complete all as specified and directed |
| 91 | S&F in repair, Outdoor MainBoard as per Sample of VRF AC Plant 45 KW Model No.AM160MXVAGC of Make Samsungincluding making connections as per existing at site complete all as specified and directed . |
| 92 | S&F in repair, DLT Sensor as per suitable size as per sample of VRF AC Plant 45 KW Model No.AM160MXVAGC of Make Samsungincluding making connections as per existing at site complete all as specified and directed |
| 93 | S&F in repair, Room Sensor of indoor ofCassate AC of 4TR capcity Model No.AM160MXVAGC of Make samsung including making connections as per existing at site complete all as specified and directed . |
| 94 | S&F in repair, remote control unit of the Casatte AC of 4 TR capacity ofVRF unit of 45 KW including making connections as per existing at site Model No.AM160MXVAGCAC Plant of Make Samsung |
| 95 | S&F in repair, Drain water motor of Casette AC4 TRincluding making connections as per existing at siteof Model No.AM160MXVAGC of Samsung complete all as specified and directed |
| 96 | S&F in repair,AHU Kit PCBof indoor motor of Casatte AC 4 TR of Model No. of VRF AC Plant 45 TRincluding making connections as per existing at site complete all as specified and directed |
| 97 | S&F in repair, DC inverter Compressor for 45 TR VRF AC Plant working Voltage 90-400V, 36-480 HzunderDC Volts andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes, hand shut off valves, relays, starting and running capacitorsetc. complete all as specified and directed |
| 98 | S&F in repair, Expansion Valve for AC Plantincluding making connections as per existing at siteModel No.AM160MXVAGC of Samsung complete all as specified and directed |
| 99 | S&F in repair, Solenoid Coil for Expansion valve for AC plantincluding making connections as per existing at siteModel No. AM160MXVAGC of Samsungcomplete all as specified and directed |
| 100 | S&F in repair, VRF outdoor fan motor as per sample of VRF AC plant 84 KW Model No. AM300MXVAGC of make Samsung complete all as specified and directed |
| 101 | S&F in repair, Out Fan Board as per sample of VRF AC Plant84 KW Model No. AM300MXVAGC of make Samsung complete all as specified and directed |
| 102 | S&F in repair, Outdoor Mother Board as per Sample of VRF AC Plant84 KWincluding making connections as per existing at site ofModel No. AM300MXVAGC of make Samsung complete all as specified and directed |
| 103 | S&F in repair, Outdoor MainBoard as per Sample of VRF AC Plant84 KWincluding making connections as per existing at site ofModel No. AM300MXVAGC of make Samsung complete all as specified and directed |
| 104 | S&F in repair, DLT Sensor as per suitable size as per sample of VRF AC Plant84 KWincluding making connections as per existing at site ofModel No. AM300MXVAGC of make Samsung complete all as specified and directed |
| 105 | S&F in repair, of Contactors of size 105 Amps as per sample of VRF AC Plant84 KW including making connections as per existing at site of Model No. AM300MXVAGC of make Samsung complete all as specified and directed |
| 106 | S&F in repair, DC inverter Compressor for 84 KW Model No. AM300MXVAGC of make Samsung working Voltage 90-400V, 36-480 HzunderDC Volts andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes, hand shut off valves, relays, starting and running capacitorsetc. complete all as specified and directed |
| 107 | S&F in repair, Expansion Valve for AC Plant 84 KW including making connections as per existing at site of Model No. AM300MXVAGC of make Samsung complete all as specified and directed |
| 108 | S&F in repair, Solenoid Coil for Expansion valve for AC plant 84 KWincluding making connections as per existing at site of Model No. AM300MXVAGC of make Samsungcomplete all as specified and directed |
| 109 | Dismantling of defective worn out wiring of Outdoor unit of split AC of capacity 1.5 TR inverter typeincluding unserviceable cordless electronic remote control, supply and fixing PCB (Printed circuit Board) & Visual Eye demo plateto suit /match the existing system complete all as specified and directed. |
| 110 | Dismantling of defective worn out wiring of Indoor unit of split AC of capacity 1.5 TR inverter type including unserviceable cordless electronic remote control, supply and fixing PCB (Printed circuit Board) & Visual Eye demo plateto suit /match the existing system complete all as specified and directed. |
| 111 | Dismantling of defective worn out wiring of Outdoor unit of split AC of capacity 2.0 TR inverter type including unserviceable cordless electronic remote control, supply and fixing PCB (Printed circuit Board) & Visual Eye demo plateto suit /match the existing system complete all as specified and directed. |
| 112 | Dismantling of defective worn out wiring of Indoor unit of split AC of capacity 2.0 TR inverter type including unserviceable cordless electronic remote control, supply and fixing PCB (Printed circuit Board) & Visual Eye demo plateto suit /match the existing system complete all as specified and directed. |
| 113 | Taking down unserviceable inverter Outdoor Condensor motor of 1.5 TR capacity split AC and supply and fixing new inverter blower motor and aligning the motor complete all as directed. |
| 114 | Taking down unserviceable inverter indoor blower motor of 1.5 TR capacity split AC and supply and fixing new inverter blower motor and aligning the motor complete all as directed. |
| 115 | Taking down unserviceable inverter Outdoor Condensor motor of 2.0 TR capacity split AC and supply and fixing new inverter blower motor and aligning the motor complete all as directed. |
| 116 | Taking down unserviceable inverter indoor blower motor of 2.0 TR capacity split AC and supply and fixing new inverter blower motor and aligning the motor complete all as directed. |
| 117 | Taking down unserviceable inverter compressor and S&F Compressor sealed unit for Inverter Split type Air Conditioner of capacity 1.5 ton inverter compressor by removing of old burnt compressor andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes, hand shut off valves, relays, starting and running capacitorsetccomplete all as directed. |
| 118 | Taking down unserviceable inverter compressor and S&F Compressor sealed unit for Inverter Split type Air Conditioner of capacity 2.0 ton inverter compressor by removing of old burnt compressor andfixing as per manufacturer instruction including providing connections of gas line, fixing of copper tubes of suitable sizes, hand shut off valves, relays, starting and running capacitorsetc.complete all as directed. |
| 119 | M&L fully automatic star delta starter, 5 HP capacity with voltmeter/ Ammeter and Indication lamp for Submersible pump set, 3 phase 440 volt complete with over load protection with adjustable relay range, electronic timer relayandprovision of MS flat strips of suitable size and shape duly drilled and embedded to wallincluding making good disturbed surfaces complete all as specified. |
| 120 | M&L fully automatic star delta starter, 15 HP capacity with voltmeter/ Ammeter and Indication lamp for Submersible pump set, 3 phase 440 volt complete with over load protection with adjustable relay range, electronic timer relayandprovision of MS flat strips of suitable size and shape duly drilled and embedded to wallincluding making good disturbed surfaces complete all as specified. |
| 121 | Supply, laying, jointing and testing LT cable in trenches or on poles / walls, XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 Core complete all as specified and as direcred. |
| 122 | Supply, laying, jointing and testing LT cable in trenches or on poles / walls, XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 Core complete all as specified and as direcred. |
| 123 | Supply, laying, jointing and testing LT cable in trenches or on poles / walls, XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 Core complete all as specified and as direcred. |
| 124 | Taking down Unserviceable Feeder Pillar box by diconnectiong all electric cables and Supply, installing, testing and commisioning and design of factory made powder coated (CPRI approved) out door type,IP54 , dust & vermin proof, LT feeder piller box made out of 3.15mm thick CRCA steel sheet ofsize 1500X1200X500mmand and angle iron 50x50x6mm, grouted in PCC M-10 using 20mm graded stone aggregate including bus bar, internal wiring with PVC insulated, single core copper conductor cable of suitable size duly numbered with tags for the circuits with hinged double door shutters (front & rear), cubical type with locking arrangement and slanted roof. The size of panel board shall be 3 phase, 440VAC, 50Hz supply system. the panel board shall comprise of following items and all specified in SSR part -I clause No 19.21 and connecting all existing LT Cables testing complete all as specified.Busbar:400 Amps rated copper busbar TPN duly insulated with PVC Sleave asper standard colour code and rigidly mounted on backalite/ DMC insulated bus bar support ((square/ round) insulators of suitable size and good insulation resistance.Incoming: (a) MCCB, 4 pole, 415 volts,50 Hz, 250Amps 50KA breaking capacity with thermal magnetic release, adjustable Over load and short circuit settings. -1No(b) Digital ammeter with 3 Nos CTs & selector switch -01Set(c) Digital Voltmeter with selector switch - 1 set.(d) Indicator lamp LED type R-Y-B-1 set.Outgoing: (a) MCCB, 4 pole, 415 volts,50 Hz, 125 Amps 30KA with thermal magnetic release, adjustable Over load and short circuit settings,-2 Nos(b) MCCB, 4 pole, 415 volts,50 Hz, 100 Amps18KA with thermal magnetic release, adjustable Over load and short circuit settings-2 Nos , (c) MCB FP -32 Amps, 10 KAC Curve -02 NosNote:- The feeder pillar box shall be manufactured by CPRI approved Manufacturer only having typed test certificate to be submitted. |
| 125 | S&F sheet metal enclosure MCBVTPN 04 wayDouble door IP 54 Ready to use DBs - Provided with insulated vertical phase bus-bars |neutral bar/s with shroud/s earth bar(s) sticking saddles cement spill protector color-coded interconnecting wire set cable ties blanking plates and circuit identification labels With provision upto4 Pole MCCB 250 A as incomer and SP/SPN MCBs as outgoing complete all as specified and directed. |
| 126 | M&L PCC(1:4:8) type D2 using 40 mm graded aggregate as inhardstanding for AC plantscomplete all as specified and directed |
| 127 | M&L in repair, angle ironsupports, clamps, straps D-clamps, back plates and MS frames fabricated from structural steel sections such as MS channel, angle iron and flats of suitable size etc including nuts, ,bolts, washers eye hooks, welding, bending cold or hot drilling holes for bolts in any shape or size including two coats of synthetic aluminium paint over a coat of red oxide primer after preparation of steel surface complete all as specified. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail