| 1 | Supply, laying, fixing and testing in replacement of heavy duty 200mm dia (wall thickness 6.0mm) MS Pipe conforming to IS: 1239/3589 including fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc.including welding, cutting, and grindingworks, laidin trenches, or fixing in wall, ceiling andfloor complete and making good the disturbed surface similar to existing excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tapeand painting with two or more coats of synthetic enamel paint of post office red coloras per IS- 10221, in and including disconnected/dismantling and taking out of rusty/damaged MS pipes complete all as specified and as directed. |
| 2 | All as per item srl No. 1 here-in-before but 150 mm. dia (wall thickness5.4 mm) |
| 3 | All as per item srl No. 1 here-in-before but 100 mm. dia (wall thickness5.4 mm) |
| 4 | All as per item srl No. 1 here-in-before but 80 mm. dia (wall thickness4.85 mm) |
| 5 | Supply, laying, fixing and tested in replacement of heavy duty 40 mm dia, GI pipe conforming to IS: 1239 including fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. in and including cutting, welding and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of post office red color in and including disconnected/dismantling and taking out of rusty/damaged GI pipes complete all as specified and as directed. |
| 6 | All as per item srl No. 5 here-in-before but 25 mm dia |
| 7 | All as per item srl No. 5 here-in-before but 20 mm dia |
| 8 | Supplying, fixing and testing in replacement of 200 mm dia double flanged butterfly valve of PN 1.6 rating, CI , gear/hand lever operated,with soft seated wafer, bronze/gunmetal seat and ss 304 shaft duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes complete all as specified and as directed. |
| 9 | All as per item srl No. 8 here-in-before but 150 mm dia |
| 10 | All as per item srl No. 8 here-in-before but 100 mm dia |
| 11 | All as per item srl No. 8 here-in-before but 80 mm dia |
| 12 | Supplying, fixing andtesting in replacement of 200 mm dia double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with matching flange, nuts, bolts, washers, gaskets and conforming to IS: 780 of following sizes complete all as specified and directed. |
| 13 | All as per item srl No. 12 here-in-before but 150 mm dia |
| 14 | Supplying, fixing andtesting in replacement of 200 mm dia CI, double flanged butterfly non return valve (butterfly type) of rating PN 1.6 with Stainless steel disc and nitrel stem, ISI marked complete with matching flange, nuts, bolts, washers, gaskets and complete all as specified and directed. |
| 15 | Supplying, fixing andtesting in replacement of 150 mm dia double flanged butterfly non return valve (sluicetype) of rating PN 1.6 with Stainless steel ball, ISI marked complete with matching flange, nuts, bolts, washers, gaskets and complete all as specified and directed. |
| 16 | Supplying, fixing andtesting in replacement of80 mm dia, CI double flanged butterfly non return valve (butterfly type) of rating PN 1.6 with Stainless steel disc and nitrile stem, ISI marked complete with matching flange, nuts, bolts, washers, gaskets and complete all as specified and as directed. |
| 17 | Supplying, fixing and testing in replacement of unserviceable gun metal branch pipe, short type, instantaneous pattern to suit hose delivery coupling of size 63 mm bore complete with gun metal solid jet nozzle of 20mm nominal size confirming to IS:903 complete all as specified and directed. |
| 18 | Supplying, fixing and testing in replacement of unserviceable fire hydrant flanged type landing valve, oblique type, singleoutlet with hose coupling adaptor of size 63 mm bore made of gun metal with female mouth and cast iron wheel and instantaneous spring lock, blank cap with chain confirming to IS:5290 complete all as specified and as directed. |
| 19 | Supplying, fixing and testing in replacement of unserviceable fire hydrant flanged type landing valve, oblique type, double outlet with hose coupling adaptor of size 63 mm bore made of gun metal with female mouth and cast iron wheel and instantaneous spring lock, blank cap with chain confirming to IS:5290 complete all as specified and as directed. |
| 20 | Supplying, fixing and testing in replacement of unserviceable synthetic fiber circular woven seamless reinforcement jacketed coupling with type- II (reinforced rubber lined type), flexible fire hosemade of 100% synthetic yarn, circular shaped of size 63 mm bore x 15 mtr long, complete with gun metal coupling of 63mm, with multi serrated tail and double instantaneous spring lock arrangement comprising of heavy duty pair of gun metal male and female parts, hydraulically crimped to hose with rubber cap washer and copper binding wire confirming to IS: 903 and ISI markedcomplete all as specified and as directed. |
| 21 | Supplying, fixing and testing in replacement of unserviceable swinging hose reel comprising ofply rubber hose of size 20mm(3/4\"), 15m long tested with 25kg/cm²/350 psi bursting pressure with wall mounted mild steel pressel reel with 180º angle swinging with non-jamming controlling handle which shall stay at the ON/OFF position as set, wall bracket with \"U\" shaped reel carrier made of CI of post office red colour finish in and including gun metal noel and shut off ball valve, heavy duty confirming to IS: 884 and ISI markedcomplete all as specified and as directed. |
| 22 | Supplying, fixing and testing Air vessel made of 450 mm dia, 8 mm thick MS sheet, 1000 mm in height complete with gun metal air release valve on top and flanged connection to riser with gun metal shut off valve at the inlet, drain arrangement with 25 mm dia gun metal drain valve with required accessories,stainless steel pressure gauge and 3 nos mild steel supporting legs in and including painting with synthetic enamel paint of post office red coloured over two coat of red oxide primer on outside and two coat of epoxy coating in inside complete all as specified and as directed. |
| 23 | Supplying and fixing in replacement of unserviceable bourden type with ball valve pressure gauge of 4\" dial duel scale type 0 - 14 kg/cm² & PSI, stainless steel casing, screwed type complete all as specified and as directed. |
| 24 | Supplying and fixing in replacement of unserviceable Pressure switch in and including PVC insulated copper conductor FRLS flexible cable with copper thimble of suitable size upto control panel complete all as specified and as directed. |
| 25 | M&L for fittings for flanged pipes such as Bends, Tapers, Tee Pieces (Single & double branch) any type and angle/radius and straight connecting pieces but all ends flangedcomplete all as specified and as directed. |
| 26 | M&L for dismantling and taking down corroded/worn out base frames/pit covers, any type of water supply/fire fighting installations and supply and fix new base frames/pit covers. MS angle iron frame /MS plates/MS flat or round bars including welding work, duly painted with two coats of synthetic enamel paint over a coat of red oxide primercomplete all as specified and as directed. |
| 27 | M&L for painting up to 200 mm bore New MS/GI pipe with one coat of red oxide primer and two coats of red post office synthetic enamel paints on all external steel surface after thoroughly cleaning/scraping of old paints, rust and scale etc. before applying the primer complete all as specified and as directed. |
| 28 | Supplying and fixing in replacement of unserviceable internal hydrant coupling/ tikki rubber washer 4mm thick of size 12 mm inner diameter and 72 mm outer diameter complete all as specified and as directed. |
| 29 | Supplying and fixing in replacement of unserviceable hydrant PVC valve balanking cap with SS chain of size 63 mm, round shape, pull and push type complete all as specified and as directed. |
| 30 | Supplying and fixing in replacement of unserviceable CI hydrant valve hand wheel, round shape, with bolt, nut & washer as per existing size complete all as specified and as directed. |
| 31 | M&L for painting of Air vessels with one coat of red oxide primer and two coats of red post office synthetic enamel paints on all external steel surface after thoroughly cleaning/scraping of old paints, rust and scale etc. before applying the primer complete all as specified and as directed. |
| 32 | Supplying and fixing in replacement of unserviceable gun metal air release valve with GI coupling of Air vessels of size 25 mm, screwed type complete all as specified and as directed. |
| 33 | Supplying and fixing in replacement of unserviceable forced brass ball valve for inlet & drain of Air vessels of size 20 mm, screwed type complete all as specified and as directed. |
| 34 | Supplying and installin replacementyard fire hydrant box, outdoor type ofinternal size not less than 100 X 115 cm and 75 cm width, made out of 14 SWG thick CRCA mild steel sheet, factory made, totally enclosed with front side hinged openable cover with locking arrangement and pad lock duly painted with two coat of red post office colour synthetic enamel paint on outside surface and white colour paint on inside surface over a coat of red oxide primer comprising 4 mm thick glass window of sizenot less than 76 X 76 cm on front side openable cover inscribed with word \"FIRE\" (5 inch size) with post office red synthetic enamel paint. The box to be installed on brick pillar foundation with suitable size of MS foundation bolt grouting in and including dismantling corroded/worn out yard fire hydrant box from brick pillar foundation complete all as specified and as directed. |
| 35 | All as per Serial No 34 above but indoor type of internal size not less than 105 cm x 142 cm x 84 cmcomplete all as specified and as directed. |
| 36 | All as per Serial No 34 above but out door type of internal size not less than 110 cm x 145 cm x 80 cmcomplete all as specified and as directed. |
| 37 | Supply & fixing in replacement of broken glass windowsize not less than 76 cm x 76 cm x 4 mm thick in yard fire hydrant box inscribed with word \"FIRE\" with red post office colour synthetic enamel paint as per existing patterncomplete all as specified and as directed. |
| 38 | M&L for painting of MS fire hydrant box Indoor/outdoor type of internal size not less than 97x105x60cm after thoroughly cleaning/scraping of old paints, preparation of surfaces with emery paper as per existing colour code duly painted with two coat of red post office colour synthetic enamel paint on front ofoutside surface and white colour paint on inside surface over a coat of red oxide primer comprising 4 mm thick glass windowinscribed with word \"FIRE\" (5 inch size) with red synthetic enamel paint and numbering of box complete all as specified and directed. |
| 39 | M&L for cleaning of fire pipe lineduct/trench size not less than 1.50 m width and 50 cm depth after removing of MS Cover by removing/taking up dirty water along with sludge and disposal the same to a safe distance including scrubbing of the internal surfaces and refixing of MS cover complete all as specified and directed. |
| 40 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m deep in any type of PCC/Hard/Dense soil, complete all as specified and directed. |
| 41 | Returning filling including leveling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed. |
| 42 | Removing the excavated materials not exceeding 50 m and depositing where directed at level not exceeding 1.5 m above the starting level complete all as specified and directed. |
| 43 | M&L for demolition of brick work built in cement mortar of any description and removing rubbishcomplete all as specified and directed.Note:- Demolished materials shall be removed out of Restricted area land on the same day other wise penalty @ Rs. 500 PerDay will be imposed. |
| 44 | M&L brick work in 1:6 using sub class \"B\" brick straight or curved on plan exc 6 m mean radiuscomplete all as specified and directed. |
| 45 | M&L for 150 mm thick with PCC 1:2:4 type B1 using 20mm grade stone aggregate and finishing even and without using extra cement complete all as specified and directed. |
| 46 | M&L for 150 mm thick with PCC 1:4:8 type D2 using 40 mm grade stone aggregate and finishing even and without using extra cement complete all as specified and directed. |
| 47 | M&L for 100 mm thick cement concrete type B-2 1:2:4 (40 mm graded aggregate in sub-based sub-floors, floors and paving etc complete all as specified and directed. |
| 48 | M&L for 15 mm thick rendering on brick surface in cement mortar 1:4 finished even and smooth without using extra cement complete all as specified and directed. |
| 49 | M&L for chequeredcement tiles 20 cm x 20 cm x 25mm thick, set, jointed and pointed in neat cement slurry in floors complete all as specified and directed. |
| 50 | M&L formachine cut kota stone slab flooring 20-25mm thick over cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete all as specified and directed. |
| 51 | S&F in replacement of U/S Sprinkler glass bulb type (Standard response) as per IS:15106/TAC guidelines 68 degree temperature rating concealedtype complete all as specified and as directed. |
| 52 | S&F in replacement of MCCB, four pole, 250 Amps, 36KA,,415 Volts (Ics=100% of Icu) with microprocessorrelease suitable for existing frame size of LT panel.Make: C&S/ L&T / ABB |
| 53 | S&F in replacement of MCCB three pole 125 Amps, 25KA, 415 Volts (Ics=100% of Icu) with thermal magnetic release suitable for existing frame size of LT panel, complete all as specified and directed. |
| 54 | S&F in replacement of MCCB three pole 100 Amps, 16KA, 415 Volts (Ics=100% of Icu) with thermal magnetic release, complete all as specified and directed. |
| 55 | S&F in replacement of MCB Three pole 40 Amps, 10KA, 415 Volts, \"C\" curve complete all as specified and directed. |
| 56 | M&L for making insertion under road without cutting of road for laying of MS/GI pipe line up to 200 mm bore by using mechanically operated machine complete all as specified and directed.Note:- (i) Works are to be carried out in multistoried bldg from basementto 11 th story as and where required.(ii) All T&P item/scap foldingas required at site will be arranged by the contractor at no extra cost. |
| 57 | M&L for taking out/ collected empty Fire Extinguishers of any type and capacity from various locations send to authorized distributor for refilling and re-fixing the same in proper position and location as per the requirement of the location and type of fire extinguisher in and including transportation complete all as specified and as directed. |
| 58 | S&F in replacement of unserviceable threaded GI nipple 15mm dia, \"heavy grade\" length not less than 600mm as per site with GI sockets complete all as specified and as directed. |
| 59 | M&L for refilling of fire extinguishers with ABC dry chemical powder and pressurization of fire extinguisherwith fresh/ sufficient quantity/quality, ABC Dry chemical powder as per IS: 14609:1999and shall contain 90% Mono Ammonium Phosphate and pressurized with Nitrogen Gas in and including painting the cylinder, labeling/marking with date of refilling and expiry date of refilling as per the ISI standards and as per the norms of Fire Authorities, a dry chemical Hydraulic Pressure testing should be as per IS-2190-2010 and test certificate shall be submitted and shall be valid for further three years complete all as directed of 10 Kg capacity cylinder, complete all as specified and as directed. Note:- Any fire extinguisher cylinder will be failing in hydraulic test will be return in AGE E/M Cab Sectt yard and nothing extra will be paid for its to the contractor. |
| 60 | All as per item srl No. 59, here-in-before but 5 Kg ABC Powder type Fire Extinguishers |
| 61 | All as per item srl No. 59, here-in-before but 4 Kg ABC Powder type Fire Extinguishers |
| 62 | M&L for refilling of fire extinguishers with Carbon dioxide (CO2) and pressurization of fire extinguisherwith fresh/sufficient quantity/quality, Carbon dioxide shall be as per IS: 15222:2002 with minimum gas purity shall be 99.5 % in and including painting the cylinder, labeling/marking with date of refilling and expiry date of refilling as per the ISI standards and as per the norms of Fire Authorities, Carbon dioxide fire extinguishers shall be tested as per IS: 5844-1970 and test pressure shall be 250 kg/ cm2 (as per the IS 2190:2010 ) and test certificate shall be submitted and shall be valid for further five years complete all as directed of 4.5 Kg capacity cylinder, complete all as specified and as directed.Note:- Any fire extinguisher cylinder will be failing in hydraulic test will be return in AGE E/M Cab Sectt yard and nothing extra will be paid for its to the contractor. |
| 63 | All as per item srl No. 62, here-in-before but 2 Kg Carbon dioxide (CO2) type Fire Extinguishers |
| 64 | M&L for refilling of fire extinguishers 9 kg with water CO2 type and pressurization of fire extinguisherwith fresh/sufficient quantity/ quality, Carbon dioxide shall be as per IS: 15222:2002 with minimum gas purity shall be 99.5 % in and including painting the cylinder, labeling/marking with date of refilling and expiry date of refilling as per the ISI standards and as per the norms of Fire Authorities, Carbon dioxide fire extinguishers shall be tested as per IS: 5844-1970 and test pressure shall be 250 kg/ cm2 (as per the IS 2190:2010 ) and test certificate shall be submitted and shall be valid for further five years complete all as directed.Note:- Any fire extinguisher cylinder will be failing in hydraulic test will be return in AGE E/M Cab Sectt yard and nothing extra will be paid for its to the contractor. |
| 65 | M&L for refilling of fire extinguishers 9 Kg with AFFF foam type and pressurization of fire extinguisherwith fresh/sufficient quantity/quality, AFFF Foam as per IS: 4989 and shall contain with 95% effective discharge and 15 Kgf/cm² charge pressure in and including painting the cylinder, labeling/marking with date of refilling and expiry date of refilling as per the ISI standards and as per the norms of Fire Authorities, Hydraulic Pressure testing should be as per IS-2190-2010 and test certificate shall be submitted and shall be valid for further three years complete all as specified and as directed.Note:- Any fire extinguisher cylinder failing in hydraulic test will be returned in AGE E/M Cab Sectt yard and nothing extra will be paid for its to the contractor. |
| 66 | S&F in replacement of unserviceable brass discharge valve wheel type with working pressure not less than 150 Kg/cm² confirming to IS: 3224 suitable for CO2 type fire extinguishers of capacity 4.5 Kg and 2 Kg complete all as specified and as directed. |
| 67 | S&F in replacement of unserviceable discharge hose made out of wire braided rubber of ID not less than 10mm and length not less than 1 mtr or as per existing size with horn, confirming to IS: 3224 suitable for CO2 type fire extinguishers of capacity 9 Kg / 4.5 Kg and 2 Kg complete all as specified and as directed. |
| 68 | S&F in replacement of CO₂ fire extinguisher plastic round shape 2mm thick security seal with GI chain and safety pin suitable upto 9 Kg / 4.5 Kg and 2 Kg cylinders complete all as specified and as directed. |
| 69 | S&F in replacement of unserviceable taflon/nylon washer with OD-19mm, ID- 9mm or as per existing size, thickness 3mm including rubber \"O\" ring of size 25 x 3.5 mmcomplete all as specified and as directed. |
| 70 | S&F in replacement of unserviceable squeeze grip type valve, heavy duty with MS control handle and SS lock/pull pin with chain confirming to IS: 15683 (2006) suitable for ABC type fire extinguishers of capacity 10 Kg, 5 Kg and 4 Kg complete all as specified and as directed. |
| 71 | S&F in replacement of unserviceable discharge wire braided rubber hose with brass shut off nozzle, length of the flexible hose not less than 1 mtr or as per existing, confirming toIS: 15683 (2006) suitable for ABC type fire extinguishers of capacity 10 Kg, 5 Kg and 4 Kg complete all as specified and as directed. |
| 72 | S&F in replacement of unserviceable analog type spring brass fire extinguisher pressure gauge, 1\" dial suitable for measuring 0 to 50 bar duly calibrated by standard method confirming to IS: 15683 (2006) suitable for ABC type fire extinguishers of capacity 10 Kg, 5 Kg and 4 Kg complete all as specified and as directed . |
| 73 | M&L for taking out electrical driven fire pump of capacity 60 HP Make: Kirloskar after disconnected all electrical and water connection and disassembling form base and uncoupling motor shaft couplingand taking and transport to work shop & opening carefully and servicing complete with replacing of bushes/bearings, gland packing, seals, oil rings, rubber gasket, nut, bolt & washers in and including re-metaling/machining work for shaftif required and re-fixing it in original position and making out all electrical and water connection including painting to two coats with synthetic enamel paint after necessary preparation including testing & commissioning complete all as specified and as directed. Note :- (i) T&P items and any other minor items required for installation and commissioning of electric motor will deemed to be including in the quoted rates.(ii) Any electric connection, nut, bolts, washers, flanges including welding and cutting work will deemed to be including in quoted rates. (iii) Replacement of damage/warnout impellor & ball bearing shall be measured and paid separately. |
| 74 | All as per item srl No. 73, here-in-before but Jokey pump of capacity 15 HP, complete all as specified and as directed. |
| 75 | Supply only ball bearing (as existing) suitable for centrifugal pump & motor of capacity 60 HP, complete all as specified and as directed. |
| 76 | Supply only ball bearing (as existing) suitable for centrifugal pump & motor of capacity 15 HP, complete all as specified and as directed. |
| 77 | Supply only bronze Impeller (as existing) suitable for centrifugal pump of capacity 60 HP, complete all as specified and as directed. |
| 78 | Supply only Bronze Impeller (as existing) suitable for centrifugal pump of capacity 15 HP, complete all as specified and as directed. |
| 79 | M&L for disconnecting electrically and mechanically defective induction electric motor of capacity 60 HP electrically operated three phase 415 volt, shifting to civil workshop for repair, strip opening for inspection, cutting of unserviceable burnt winding, taking out, cleaning of slots, rewinding with new super enameled ,of existing size of copper conductor winding wire and replacement of unserviceable burnt insulating materials, sleeves etc, varnishing and with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete repainting two cote new andother connected works, re-assembling ,re-fixing at site, electrical connection fixing with pump set with nuts, bolts, washers as per original position and testing complete all as directed for satisfactory operation complete all as specified and as directed.Note :- (i) T&P items and any other minor items required for installation and commissioning of electric motor will deemed to be including in the quoted rates.(ii) Any electric connection, nut, bolts, washers, flanges including welding and cutting work will deemed to be including in quoted rates.(iii) Replacement of damage/warnout ball bearing shall be measured and paid separately. |
| 80 | All as per item srl No. 80, here-in-before but of capacity 15 HP, complete all as specified and as directed. |
| 81 | S&F in replacement of tyre coupling suitable for 60 HP centrifugal Pump set made out of FRAS neoprene rubber tyre and steel hub with nuts & bolts complete all as specified and as as directed.Note:- Contractor should check the existing pump shaft size at site before procurement of tyre coupling. |
| 82 | All as per item srl No. 81 here-in before but suitable for 15 HP centrifugal pump set, complete all as specified and as directed. |
| 83 | S&F in replacement of 3 pole Power contactor, 3 phase, 415 volts, 50 Hzfor star delta starter suitable of 60 HP pump including front mounting add-on auxiliary contact block, Model No. TC1-D8011, Make-C&S or equivalent as approved by GE, complete all as specified and as directed. |
| 84 | S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz including front mounting add-on auxiliary contact block Model No. MNX 50, Make-L&T or equvailent approved by GE, complete all as specified and as directed. |
| 85 | S&F in replacement of overload relay with trip class 30 suitable for range 63-100 Amp, Make: C&S or equivalent as approved by GE, complete all as specified and as directed. |
| 86 | S&F in replacement of Overload relay suitable for range 30-50 Amp, Make: L&T or equivalent as approved by GE, complete all as specified and as directed. |
| 87 | S&F in replacement of electronic timer, 3 phase, 240/415 volts, 50 Hz, 1 to 30 secondMake-C&S or equvailent approved by GE, complete all as specified and as directed. |
| 88 | S&F in replacement of electronic timer, 3 phase, 240/415 volts, 50 Hz, 3 to 30 second Make-L&T or equivalent as approved by GE, complete all as specified and as directed. |
| 89 | S&F in replacement of analog ammeter, 96x96 mm size with measuring range 0-300A , AC, three phase, class accuracy 1.5 suitable for panel mounting complete all as specified and directed. |
| 90 | S&F in replacement of analog ammeter, 96x96 mm size with measuring range 0-150A , AC, three phase, class accuracy 1.5 suitable for panel mounting complete all as specified and directed. |
| 91 | S&F in replacement of analog ammeter, 96x96 mm size with measuring range 0-100A , AC, three phase, class accuracy 1.5 suitable for panel mounting complete all as specified and directed. |
| 92 | S&F in replacement of analog voltmeter, 96x96 mm size with measuring range 0-500VAC, three phase, class accuracy 1.5 suitable for panel mounting complete all as specified and directed. |
| 93 | S&F in replacement of ammeter selector switch , suitable for line current with neutral and OFF (5 position), AC ,three phase suitable for panel mounting complete all as specified and directed. |
| 94 | S&F in replacement of voltmeter selector switch , suitable for voltage between phase to phase and individual phases to neutral with OFF (7 position), AC ,three phase suitable for panel mounting complete all as specified and as directed. |
| 95 | S&F in replacement of current transformer (CT) of capacity 100/5A, cast resin ring type with burden 15 VA and accuracy class 1 suitable for panel mounting complete all as specified and as directed. |
| 96 | S&F in replacement of Phase indicating lamp, LED type, RED/BLUE/YELLOW/GREEN, 22.5 mm Ø, surface mounted, 240VAC suitable for panel mounting complete all as specified and as directed. |
| 97 | S&F in replacement of PVC insulated two core unsheathed, multistrand copper conductor flexible cable 2.5 Sqmm, FRLS conforming to IS-694:1990 in and including copper thimbles as per site requiredsuitable for panel wiring complete all as specified and as directed. |
| 98 | M&L for painting of auditorium curtains, chairs and doors withhigh quality fire retardant paint through sprygun complete all as specified and as directed. |
| 99 | M&L for taking down wall mounted manual brass fire bell of any size from various locations of E, F, D and CRF area and dismantling carefully all connected parts,chrome polished, greasing after proper cleaning of all matel parts and replaced old warnout pull rope with 1\" dia hand- braided red rope, re-assemble and hanging on wall bracket in and including painting of wall bracked withtwo coats of synthetic enamel paint of approved colour and marking on \"FIRE\"complete all as specified and as directed. |
| 100 | S&F in replacement of fire extinguisher mounting bracket suitable upto 2 kg to 10 kg cylinders duly fixed in wall with MS fastener/GI Screw complete all as specified and as directed. |