| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Wiring for light/ power plug with 2X4 sq. mmFRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 7 | 3 Module (100 mm X 75 mm) |
| 8 | 12 Module (200 mm X150 mm) |
| 9 | 6 Module ( 200 mm x 75 mm ) |
| 10 | 8 Module (125 mm x 125 mm) |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 12 | 5/6 A switch |
| 13 | 15/16 A switch |
| 14 | 3 pin 5/6 A socket outlet |
| 15 | 6 pin 15/16 Amp socket outlet |
| 16 | Supply, Installation, Testing and Commissioning ofceiling fan with Brush LessDirectCurrent(BLDC)Motor,classofinsulation: B,3nos.metal ( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS :374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019fan Supply, earthing etc. complete as req(Buy Back of old fan) |
| 17 | 1400mm,service value≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 18 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 19 | 12 way , Double door |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 21 | Single pole |
| 22 | Single pole and neutral |
| 23 | Supplying and fixing 63 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 24 | 3 mm thick phenolic laminated sheet |
| 25 | Providing and fixing following rating and breakingcapacity and pole MCCB with thermomagneticrelease and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 26 | 125 A,36KA,FPMCCB |