| 1 | Running maintenence and Operation of fire fighting, Fire Alarm &PASystem and sprinkler system as per additional terms and conditions enclosed by deploying the following staff :-a) Operator – 3 Nos.(1 No. in each shift total 3 shifts i.e. 6 AM to 2 PM & 2 PM to 10 PM & 10PM to 6AM)b) Khallalsi– 1 Nos.(1 No. in in general shift ) |
| 2 | SupplyReplacement installation testing & commissioningof smoke detector with builtin LED mounting base complete with all connection etc. as required. |
| 3 | Painting of fire fighting installation with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade with one or more coats on old work. |
| 4 | Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 5 | 80mm dia. |
| 6 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : |
| 7 | Single headed Stainless steel |
| 8 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 9 | Stainless Steel (Grade 304) |
| 10 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: |
| 11 | Stainless Steel (Grade 304) |
| 12 | Supplyingand fixing ExternalHydrant hose cabinetto accommodate the hose, pipes, branch pipe nozzle and the hydrant outlets.The double door cabinet is made up of LFRP sheet with glass fronted hinged centre opening glazeddoors and lock, painted with scarlet red colour including providing of masonry or MS frame structure. |
| 13 | Size :- 750mm X 600mm X 250mm |
| 14 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. |
| 15 | 4 Zone |
| 16 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 17 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
| 18 | Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 19 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 20 | Supply, Installation Testing & Commissioning of Self illuminating photo luminescent type fire instruction signage of size 12 Inch x 9 Inch in Red/ Green color 2mm Acrylic sheet, including mounting arrangement on celling wall complete as required |
| 21 | Providing and supplying MS Angle Terrace Pump Shed for terace pump framing consists of L-shaped mild steel (MS) angles sizes for the frame include 50x50x5mm angle with cover is typically made from corrugated MESH MASTERS PVC Gate Sheet. A protective to provide corrosion and weather resistance. The frame members are usually welded together, and galvanized fasteners are used to secure the roofing sheets. |
| 22 | Supplying, installation, testing & commissioning of Battery operated smoke detectors with rechargeable battery etc complete as required. |
| 23 | Supplying Erection Testing & Commissioning of wall mounted cubiclepanel with locking arrangement fabricated out of 2mm thick CRCA Sheet duly wired with suitable rating of stranded PVC insulated copper conductor single core cable to MCB with cable lugs & duly spray paintedwith Inter connections and complete with following accessories etc. complete as required:-Incomer1. Main DPMCB 63AMP:- 01 No.2. NO-NC Contactor With Relay 10Amp :- 3 Nos.3. ON/OFF Indicating Lamp :- 3 Nos.4. Auto/ Manual Selector Switch :- 01 No.5. Single Pole MCB 6AMP:- 3 Nos.6. DC Transformer :- 01 No. |