| 1 | Supply, Installation, Testing and Commissioning of 20kVA, TPN 415Volts three phase input, three phase output, true on-line UPS system with 30 minutes back up power at 0.9 pf, including all accessories, SMF batteries VRLA type with powder coated CRCA cabinet including all accessories such as cabling etc. as required complete having following specification. The UPS system shall be microprocessor controlled IGBT based voltage frequency independent technology unit with battery bank mounted in battery racks & connecting cables, Fully digital controlled based on DSP Power factor corrected from end 0.95 pure sine wave output, Full time output voltage & frequency regulation, Auto regulation of battery end voltage Intelligent interface with LED/LCD display, Static bypass switch / manual bypass switch Auto temperature compensation etc. |
| 2 | Supply, Installation, Testing and Commissioning of 10kVA, TPN 415Volts three phase input, three phase output, true on-line UPS system with 30 minutes back up power at 0.9 pf, including all accessories, SMF batteries VRLA type with powder coated CRCA cabinet including all accessories such as cabling etc. as required complete having following specification. The UPS system shall be microprocessor controlled IGBT based voltage frequency independent technology unit with battery bank mounted in battery racks & connecting cables, Fully digital controlled based on DSP Power factor corrected from end 0.95 pure sine wave output, Full time output voltage & frequency regulation, Auto regulation of battery end voltage Intelligent interface with LED/LCD display, Static bypass switch / manual bypass switch Auto temperature compensation etc. |
| 3 | Supply & Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable including surface / recessed medium class PVC conduit pipes, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 5 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm dia size (IS approved make) |
| 6 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm dia size (IS approved make) |
| 7 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm dia size (IS approved make) |
| 8 | Supplying and drawing following sizes of FRLSH PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq.mm |
| 9 | Supplying and drawing following sizes of FRLSH PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 2.5 sq.mm |
| 10 | Supplying and drawing following sizes of FRLSH PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 6.0 sq.mm |
| 11 | Supplying and drawing of 1 x 16.0sqmm size FRLSH PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 12 | Supply and laying of 25mm dia steel wire reinforced corrugated flexible PVC conduit along with accessories as required |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 Amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 15 | Supplying and fixing of following ways surface/ recess mounting, Vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required.4way (4+12), Double door VTPNDB. |
| 16 | Supplying and fixing of following ways surface/ recess mounting, Vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required.6way (4+18), Double door VTPNDB. |
| 17 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, SPNDB Double door |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole MCB. |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 21 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole and neutral |
| 22 | Supplying and fixing of63A, TPN (Triple pole + Neutral) MCB, 415 V, 10 kA, \"C\" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc. as directed by EIC. |
| 23 | Supplying and fixing following rating, double pole, (single phase and neutral) 240V, residual current circuit breaker (RCCB) having a sensitivity current 30 mA in the existing MCB DB complete with connection, testing and commisioning etc. as required. 25A DP RCCB. |
| 24 | Supplying and fixing following rating, four pole, (threephase and neutral) 415V, residual current circuit breaker (RCCB) having a sensitivity current 100 mA in the existing MCB DB complete with connection ,testing and commisioning etc .as required. 25A FP RCCB. |
| 25 | Supplyingof suitable size powder coat painted sheet steel enclosure box with cover, dinrail & accessoriessuitable for installationof63A TPN MCB and fixing of the same box on wall/surface by providing suitable fixing accessories etc as required. |
| 26 | Supplying of outdoor duty IP-65 or IP-66 ratedthermoplastic distribution board (DB-1 to DB-9 as shown in drawing)mounted with suitable din rail & acessories having hinged door/transparent cover,knock out holes for cables etc., complete suitable for installation of MCBs and fixing of the same on wall/surface by providing required clamps, bolt-nuts & accessories as required or as directed.(MCBS shall be measured & paid in separate item)Ref make: Sintex/ Precision/ Legrand |
| 27 | Supplying of outdoor duty IP65 or IP-66 ratedThermoplastic enclosure junction box (JB-1 to JB-55 shown in drawing) having hinged door/ transparent cover, knockout cable holes etc complete including along with suitable rating SP MCB, 6way connector & accessories and fixing of the same on wall/surface by providing suitable fixing accessories, making connections etc as required. (Ref: Sintex / precision/ Legrand) |
| 28 | Supplying of below mentioned specification white LED luminaire and fixing of the same in the ceiling/Wall surface by providing required,clamps screws/ anchor bolt-nuts, washers, TW guttas etc., making electrical connections, earthing etc., as directed by engineer-in-chargeType :- 4ft LED Batten luminaireMounting type :- Surface mountingBody: Extruded aluminium with diffuser coverRated power :- Minimum 18W or 20 WattsRef model :- HAVELLS- LUMILINE PLUS NEO |
| 29 | Supplying of below mentioned specification white LED luminaire with OEM warranty of minimum 03 years and fixing of the same in the ceiling/Wall surface by providing required,clamps screws/ anchor bolt-nuts, washers, TW guttas etc., making electrical connections, earthing etc., as directed by engineer-in-chargeType: IP-66 Bulk head luminaireMounting type :- Surface mountingBody :- PC/AL/ PDC housing IP-66Rated power :- 9watts or 10 WattsRef model :- HAVELLS-HEXA 10W-IP66 |
| 30 | Supplying & Laying of following size LT power cable with Aluminium conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (A2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments, including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC.4C X 25 Sq mm size. |
| 31 | Supplying & Laying of following size LT power cable with Aluminium conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (A2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments, including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC.4C X 10 Sq mm size. |
| 32 | Supplying & Laying of following size LT power cable with Copper conductor, XLPE/PVC insulation, PVC inner sheathed, armoured, extruded PVC outer sheathed, 1.1KVgrade (2XFY) cable, confirming to IS:7098(part-1) & relevant standards with latest amendments including laying of the same in existing trenches/duct/pipe/ on the wall/ cable trays with suitable clamps as directed by EIC.4C X 16 Sq mm size |
| 33 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4C X 25 sq. mm (28mm) |
| 34 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 10 sq. mm (22mm) |
| 35 | Supplying and making end termination of 4or3C x 16 sqmm Copper Cable with Copper Lugs anddouble compression brass gland at one end of cable as directed by EIC. |
| 36 | Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
| 37 | Excavation for cable trenches in narmalsoil, required depth maximum upto 1.2M including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and levelling or disposal of surplus excavated soil as directed. |
| 38 | Supplying of all the required materials & making Earthing pit with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required including associated civil works. |
| 39 | Supplying and fixing of 25 mm X 5 mm G.I strip on surface or in recess as strip earth electrode,including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm. (Earth excavation if any to be consided in separte item) |
| 40 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 41 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 42 | Supplying and spreading of clean & dry river sand or stone crushed M-sand all around the already laid cable in the trench as directed by EIC. |
| 43 | Supplying and laying of approved quality and make well burnt bricks breadthwise on top along the already laid cable/sand inside the trench as directed by the Engineer -in charge.(Approx. 09 nos of bricks will be required per Mtr) |
| 44 | Supplying of 50mm outer diameter HDPE Pipe of PE-100 grade, PN-8 capacity conforming to IS-4984and laying of the same in the existing trench/duct/pipe/ or fixing on the wall by providing suitable clamps, gattas, screws, bolt-nuts etc completeas required and or as directed. |
| 45 | Supplying of 63mm outer diameter HDPE Pipe of PE-100 grade, PN-8 capacity conforming to IS-4984and laying of the same in the existing trench/duct/pipe/ or fixing on the wall by providing suitable clamps, gattas, screws, bolt-nuts etc completeas required and or as directed. |
| 46 | Supplying & making of structural steel work riveted, bolted or welded in built up sections, trusses and frame work, including cutting, hoisting, fabrication, fixing in position and applying synthetic enamel paint over a priming coat of approved steel primer all complete. |