| 1 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying cables / poles foundation / stay assembly and getting out in hard / dense soil complete all as specified and as directed by Engineer-in-Charge. |
| 2 | Removing excavated material not exceeding 50m and deposting where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and as directed by Engineer-in-Charge. |
| 4 | Supply and spread dry river sand duly filtered thesand in trenches for cable cushioning onboth top and bottom of cable including ramming complete all as specified and as directed. |
| 5 | Material and labour for un-reinforced pre cast concrete covers class HV type 300mmx 180mm x 40mm size factorymade for cable protection complete all as specified and as directed. |
| 6 | Material and labour for un-reinforced pre cast concrete covers, class LV type 250mm x 150mm x 40mm size factory made for cable protection complete all as specified and as directed. |
| 7 | Supply, laying, testing, jointing and commissioning XLPE insulated cable screened PVC bedded, galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor of size 120 sq.mm 3 core 11000 Volts grade (11 KV earthed) laid in trenches / fixed on pole including taking out existing defective cable complete all as specified and as directed. NOTE: - Earth work, sand cushioning, cable protection cover, pipe and joint shall be measured and paid separately. |
| 8 | Supply, laying, testing, jointing and commissioning XLPE insulated cable screened PVC bedded, galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor of size 95 Sq.mm 3 core 11000 Volt grade (11 KV earthed) laid in trenches / fixed on pole including taking out existing defective cable complete all as specified and as directed. NOTE : - Earth work, sand cushioning, cable protection cover, pipe and joint shall be measured and paid separately. |
| 9 | Supply and fixing GI pipe light grade 80mm diafor protection of HT cable under road or on wall complete all as specified and as directed by Engineer-in-Charge. |
| 10 | Material and labour in repairs Moulded Case Circuit Breakers for Distribution Network with thermal magnetic release type DPX 250, 3 pole 100 Amps capacity, 16 KA rupturing capacity in existing panel board including modification on existing panel if required, necessary connectioning with copper strips / suitable size of copper conductor wire from bus bar, provision of suitable size of copper lugs as per the out going cable complete all as specified and as directed. |
| 11 | All as per Ser item No 10.00 above but 3 pole 125 Amps 16 KA complete all as specified and as directed. |
| 12 | All as per Ser item No 10.00 above but 4 pole 160 Amps 36 KA complete all as specified and as directed. |
| 13 | All as per Ser item No 10.00 above but 4 pole 200 Amp 36 KA complete all as specified and as directed. |
| 14 | All as per Ser item No 10.00 above but 4pole 250 Amps 36 KA complete all as specified and as directed. |
| 15 | Material and labour for steel MCCB enclosure on wall suitable for fixing of MCCB of 3 pole / 4 poleupto 250 Amps capacity complete all as specified and as directed by Engineer-in-Charge. |
| 16 | Material and labour for steel MCCB enclosure suitable for fixing of MCCB of 3 pole/4 pole cap upto 315 Amps to 630 Amps complete all as specified and as directed by Engineer-in-Charge. |
| 17 | Material and labour for laying, jointing and testingXLPE insulated, armoured heavy duty under ground electric cable with stranded aluminium conductor 1100 voltage grade cross-sectional area 50 sq.mm 3.5 corecomplete connection with proper through cable lugs including taking out / down old existing unserviceable LT UG Cable complete all as specified and as directed.NOTE :-Excavation, sand cushioning and bricks shall be measured and paid separately under respective items of Schedule. |
| 18 | All as per Ser item No 17.00 above but of size 70 sq.mm, 3.5core complete all as specified and as directed. |
| 19 | All as per Ser item No 17.00 above but of size 95 sq.mm, 3.5core complete all as specified and as directed. |
| 20 | All as per Ser item No 17.00 above but of size 120 sq.mm, 3.5core complete all as specified and as directed. |
| 21 | All as per Ser item No 17.00 above but of size 185 sq.mm, 3.5core complete all as specified and as directed. |
| 22 | Material and labour for earthing complete with copper earth plate electrode 60cm x 60cm x 3.15mm thick buried directly in ground (earth pit not less than 3 mtr deep below ground level) with top edge of the plate not less than2.10 mtr below normal ground level, connected to and including copper earth strip of 32x6 mm by means of riveting and brazingand protected by GI pipe light grade of suitable size up to the test point i.e. up to 7.5 mtr, including providing alternate layers up to full volume of pit by charcoal dust and common salt, all around the plate 15 cm depth and width minimum including PCC pit chamber, watering pipe of 50mm dia medium grade GI pipe up to the top of the plate having funnel complete and RCC cover, connecting to the test point and testing on ground complete andincluding excavation and earth workin any type of strata and cleaning of site all as specified in MES SSR Part-I and directed by Engineer-in-Charge. |
| 23 | Material and labour for copper earth continuity main earthing Strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit of size 20 x 3 mm complete all as specified and as directed. |
| 24 | Supply and fixing cable jointing kit for 11 KV grade cable for in door termination joint kit heat shrinkable type with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of95 Sq.mm including taking out unserviceable joint kitcomplete all as specified and as directed. |
| 25 | Supply and fixing cable jointing kit for 11 KV grade cable for in door termination joint kit heat shrinkable type with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of120 Sq.mm including taking out unserviceable joint kitcomplete all as specified and as directed. |
| 26 | Supply and fixing cable jointing kit for 11 KV grade cable for out door termination joint kit heat shrinkable type with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of95 Sq.mm including taking out unserviceable joint kitcomplete all as specified and as directed. |
| 27 | Supply and fixing cable jointing kit for 11 KV grade cable for out door termination joint kit heat shrinkable type with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of120 Sq.mm including taking out unserviceable joint kitcomplete all as specified and as directed. |
| 28 | Supply and fixing cable jointing kit for 11 KV grade cable for straight through joint kit heat shrinkable type with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of95 Sq.mm including taking out unserviceable joint kitcomplete all as specified and as directed. |
| 29 | Supply and fixing cable jointing kit for 11 KV grade cable for straight through joint kit heat shrinkable type with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of120 Sq.mm including taking out unserviceable joint kitcomplete all as specified and as directed. |
| 30 | Material and labour for finding out the cable fault of any size of cable upto 11 KV underground cable (HT and LT and of any capacity of cable with the help of cable fault locator mounting on vehicle and with necessary disconnection of cable from two ends andmaking connection by jointing after repairs and having the following items with electrician at site to findfault ofup to length of 10 KM cable complete all as specified and as directed by Engineer-in-Charge with help of the following accessories- (a) Surge Generator with accessories (b) Head Phone.(c) Pin Point Set T-505 with accessories.(d) Earthing cable with clamp.(e) Cable fault Locator T-905 with accessories. (f) TC-808 with accessories.(g) Soldering Iron /wire / capacitor unit / capacitor connecting cables/ power cable / nose plier. NOTE:- Excavation for the cable fault shall be done by the contractor and the same is deemed to be included in the quoted rate. |
| 31 | Material and labour for cutting of black top cover of existing road up to 1 mtr depth and 60 cm wide for laying of UG cable and pipe line, refilling and making good after laying UG cable and pipe line with PCC 1:3:6 upto 30 cm from top of the road surface complete all as specified and as directed by Engineer-in-Charge. |
| 32 | Material and labour for graded gravel/coarse stone aggregate 20 to 40 mm spread and levelled in layers complete all as specified and as directed by Engineer-in-Charge. |
| 33 | Material and labour for Palin Cement Concrete (1:3:6) type C-2 using 40mm graded stone aggregate as in foundation for poles,stays and mass concrete including necessary form work and fair finishing complete all as specified and as directed by Engineer-in-Charge. |
| 34 | Material and labour for Palin Cement Concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of poles etcincluding weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and as directed by Engineer-in-Charge. |
| 35 | Cutting the burnt out portion of the HT 11 KV grade underground XLPE cable of size95/120 sq.mm 3 core, supplyand jointing HT cable straight throughjoint (Heat shrinkable) 11KV grade of size 95/120 Sq.mm 3 core including testing complete all as specified and as directed. |
| 36 | Cutting the burnt out portion of the HT 11 KV grade underground XLPE cable of size150/185 Sq.mm 3 core, supplyand jointing HT cable straight throughjoint (Heat shrinkable)11kV grade of size 150/185 sq.mm 3 core including testing complete all as specified and as directed. |
| 37 | Material and labour for site clearance around 3mtrs of transformer plat form/3mtrs around of fencing of transformer plat form,including surface dressing not exceeding averaging 15cm deep in soft / loose soil and getting out including cutting of grass roots, bushes, tree branches and tree not exceeding 15 cm girthif any and filling of lower portion with soil obtained from cuttingor dressing complete all as specified and as directed by Engineer-in-Charge. |
| 38 | Material and labour for Palin Cement Concrete (1:4:8) type D2 using 40mm graded stone aggregate as in foundation for poles,stays, mass concrete, Pathway including necessary form work and fair finishing complete all as specified and as directed by Engineer-in-Charge. |
| 39 | Supply and fix brickwork with subclass ‘B’ bricks, straight or curved on plan exc. 6m mean radius built in with CM (1:3) complete all as specified and as directed. |
| 40 | Material and labour for fabrication of gates of angle/pipes or any other section with gusset plates, rails, braces etc, complete, drilling for fixing of steel sheeting ot other covering etc to be preprepared for hanging or sliding with and including either hooks hinges or steel hanging door fitting also fastening and fixing complete including painting with two coats of approved colour over a coat of red oxide primer complete all as specified and as directed. |
| 41 | Material and labour for chain link MS galvanised fencing of any size and type including lines wires, straining bolts and binding wires etc complete all as specified and as directed by Engineer-in-Charge. |
| 42 | Material and labour for Galvanised, 2 strand, steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails straining bolts, including, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc. as directed NOTE:Each line wire to be measured. |
| 43 | Material and labour for galvasiedmild steel channel, angle section etc for post of chain link fencingincluding notching for wire etc confirming to Fe 290 grade complete,embedded in Palin Cement Concrete complete all as specified and as directed. NOTE:- Palin Cement Concrete shall be measured and paid separately under respective items. |
| 44 | Supply only 10mm dia MS round bar for fixing of chain fencing with post including painting with two coats of approved colour over a coat of red oxide primer complete all as specified and as directed. |
| 45 | Supply and fix 12mm dia 60mm long @450mm centre to centre MS scew bolt machine made with hexagonal or square head at one end and screwed the other screwed end fixed with washer complete all as specified and as directed. |
| 46 | Maintenance and complete overhauling with calibrationofAPFCcapacity 100 KVAR having burnt out copper wiring , replacement of new copper wiring suitable size including lugs, connected auxiliary relay, display of indicatoretc complete all as specified and as directed. |
| 47 | All as per Ser item No 46.00 above but 150 KVARto 200 KVAR capacity complete all as specified and as directed. |
| 48 | Supply and fix in replacement of APFC relay 8 stage complete all as specified and as directed. |
| 49 | Supply and fix in replacement of APFC relay 12 stage complete all as specified and as directed. |
| 50 | Supply and fix in replacement of capacitor cylindrical type of the following capacities :- |
| 51 | (a) 5 KVAR |
| 52 | (b) 10 KVAR |
| 53 | (c) 12.5 KVAR |
| 54 | (d) 25 KVAR |
| 55 | (e) 25 KVAR |
| 56 | Material and labour for maintenance, servicing and repair of Vaccum Circuit Breakers/Oil circuit breaker HT 11KV 400 Amps/800Amps 50 cycles, breaking capacity 13.5 KA of any make, by opening and checking the internal moving, fixed parts, contacts/wiring, cleaning, decarbonising, tightening loosened parts, operational checking of closing/tripping system, lubricating greasing all moving parts, replacing worn out part, copper studs, bolts, nuts, washers, Checking control wiring, oil, busbar, Fixed contacts or moving contacts, HT Bushes, Gaskets including unserviceable coil,replacing of defective minor items such as indicators lamps, push buttons, selector switch etc as and when required complete all as specified and as directed.NOTE:- The item spare parts, oil to be replaced shall be measured and paid separately, however minor items such as indicator, push button, selector switch, gasket, wiring cable shall be deemed to be included in the unit rate. VCB to be serviced twice in the contract period, rate is deemed to to be quoted for each servicing job. |
| 57 | Material and labour for maintenance, servicing and repair of 2 Way RMU Panel SF6 Breaker / Load Break Switch HT 11KV 400 Amps/800Amps 50 cycles, internal moving and fixed parts, contacts/wiring, cleaning, dusting, decarbonising, tightening loosened parts, checking of closing/tripping system, lubricating greasing all moving parts, including replacing worn out part copper studs, bolts nuts and washers replacing control wiring, replacing oil, busbar contacts fixed or moving contacts, HT bush, gasket including unserviceable coil,replacing of defective minor items such as indicators lamp, push button, selector switch etc as and when required complete all as specified and as directed.NOTE :- The item spare partsto be replaced shall be measured and paid separately, however minor items such as indicator, push button, selector switch, gasket, wiring cable shall be deemed to be included in the unit rate quoted. |
| 58 | All as per Ser item No 52.00 above but 3 way RMU complete all as specified and as directed. |
| 59 | All as per Ser item No 52.00 above but 4 way RMU complete all as specified and as directed. |
| 60 | Material and labour for maintenance, servicing and oil leakage arresting upto 250 KVA, 11KV rating, distribution transformer, providing necessary gaskets, oil seals,cleaning, dusting, decarbonising, tightening loosened parts, including replacing worn out part copper studs, bolts nuts and washers replacing oil Seals, HT bush, gasket including unserviceable coil, replacing of defective minor items asand when required complete all as specified and as directed.NOTE :- The item of spare parts and oil to be replaced shall be measured and paid separately, however minor items such as gaskets, nutsand boltsshall be deemed to be included in the unit rate. The rates are inclusive of crane charges for lifting and re assembling from the structure. |
| 61 | All as per Ser item No 55.00 above, but of capacity above250 KVA to 500 KVA, 11 KV rating complete all as specified and as directed. |
| 62 | All as per Ser item No 55.00 above, but of capacity above 500KVA to 1000 KVA, 11KV rating complete all as specified and as directed. |
| 63 | Supply and fix in repair HT bushing rod complete with insulator and packing suitable for outdoor / Indoortype 63 KVA to 500 KVA, 11KV rating transformers confirming to IS-334 complete with nut bolts brass studs and gasket of synthetic rubber bonded cork sheet complete all as specified and as directed by Engineer-in-Charge. |
| 64 | All as per Ser item No 58.00 above but for capacity above 500 KVA and upto 1000 KVA, 11KV rating complete all as specified and as directed. |
| 65 | Supply and fix inrepair LT bushing complete with insulator and packing suitable for 1100 volt grade complete with nut, bolts, brass studs, insulator and gasket etc suitable for 63 to 500 KVA, 11 KV rating out door / Indoor transformer complete all as specified and as directed. |
| 66 | All as per Ser item No 60.00 above,but for above 500 KVA to 1000 KVA, 11KV rating complete all as specified and as directed. |
| 67 | NOTE for Sl Item No. 55.00 to 61.00 :- (i)Rate quoted by the contractor shall be deem to include for opening of top plate of transformer / decanning of oil from transformer up the level as per requirement and assemble the same after replacement of bushing rod.(ii) Bushing rod shall be replaced at site.transformer will not be allowed to send to workshop at any cost and all bushing replacement work shall be executed at site only. |
| 68 | Material and labour for filtration of transformer oil through stream line filtration plant for extracting moisture content in the oil and carbon deposits and bringing the di-electric strength not less than 60 KV for one minute with sphere gap of 2.5 mm including checking the value of acidity of oil with a acidity test kit and submitting test report for Die electric strength and acidity of transformer oil before / after filtration complete all as specified and as directed.NOTE : - The contractor should submit the Test sheet for all transformers in which dehydration of transformer oil carried out. |
| 69 | Supply and filling of New transformer oil confirming to IS 335-1963 as amended and die electric strength not less than 60 KV for topping up/replacement of unserviceable transformer oil complete all as specified and as directed. |
| 70 | Supply and fix in replacement ofsilica gel in existing breather assyof any capacity of transformer Schneider / ABB /L&T etc complete all as specified and as directed. |
| 71 | Material and labour for spray painting of distribution transformer with two coats of synthetic enamel paint of smoke grey colour after neatly cleaning and preparing the surfacefor spray paintingthe transformer of the following capacity including writing SM / MES No (5 cm height) with white enamel paintof capacity upto 250 KVA, 11KV rating transformer complete all as specified and as directed. |
| 72 | All as per Ser item No 65.00 above but of capacityabove 250 KVA and upto 500 KVA, 11 KV rating complete all as specified and as directed. |
| 73 | All as per Ser item No 65.00 above but of capacity above 500 and upto 1000 KVA, 11 KV rating complete all as specified and as directed. |
| 74 | Supply and refilling ofSF6 (Sulfur hexafluoride gas ) for 66 KV SF6 outdoor circuit breaker to cool and Quenchthe arc on opening of circuit transmission classdischarge capacity of 69KVfor normal operationto maintain the desired pressure in SF6 and RMU as per OEM design and testing the pressure of each SF6 breaker of 66 KV and 11 KV RMU complete all as specified and as directed. |
| 75 | Supply and fix in replacement Digital Ammeter, 11 KV, size 96 x 96 mm including taking down the existing one complete all as specified and as directed. MAKE: SCHNEIDER / L&T / ELMEASURE |
| 76 | Supply and fix in replacement Digital Voltmeter, 11 KV, size 96 x 96 mm including taking down the existing one complete all as specified and as directed.MAKE: SCHNEIDER / L&T / ELMEASURE |
| 77 | Supply and fix RED, YELLOW, GREEN, BLUE, AMBER & WHITE LED Indication Lamps Range (24 - 240 V ac/dc) for the existing HT VCB/OCB/RMU 11 KV Panels for including taking out old unserviceable Lamps complete all as specified and as directed. |
| 78 | Supply and fixing of HT current transformer 11 KV rating of capacity 200 / 100 / 5-5 including testing commissioning of through primary injection method with suitable testing kit and also checking the control panel wiring including setting the CT range with relays setting for proper functioning/tripping and taking out old unserviceable CT complete all as specified and as directed. MAKE:KALPA / KAPPA |
| 79 | Supply and fixing in replacement of Potential Transformer moulded in epoxy compound with dual ration 50 / 25 / 5 Amps complete connection with copper wire including beading as per existing VCB 11 KV at site complete all as specified and as directed by Engineer-in-Charge. MAKE : ABB / KALPA / KAPPA |
| 80 | Replacement of unserviceable existing make and model IDMT relay numerical non directional over current and earth fault relay with communication feature (RS 485) with full automation system type Argus, LT, Aux voltage 110 volt DC should comprise of the following features:-(a)Three phase over current and one earth fault(b)High set - low set(c)RS-485 with full communication system(d)Multi characteristic for both over current and earth fault,Make: L&T / SCHNEIDER / SEIMENS / ABB / C&S |
| 81 | Material and labour for calibration of IDMT relays set of 11KV rating of three through relay test kitincluding other required measuring equipment to the site by secondary injection method and testing for proper functioning / tripping systems of relays complete all as specified and as directed.NOTE : - The rate quoted by the contractor is deemed to be included for quarterly checking of relays in VCB/OBC for its proper setting / functioning and tripping of VCB/OCB during over load/earth fault. |
| 82 | Supply and laying sealing compound bitumen for arresting of holes at VCB/OCB/ SF6 breaker panels 11 KV rating etc complete all as specified and as directed. |
| 83 | Supply and fix in replacement ofspring charge universal motor suitable for 11 KV, VCB,working on 230 volt of existing make i.e CG / Schneider / ABB / L&T etc complete all as specified and as directed. |
| 84 | Supply and fix of Master Tripping Relay rating of 24 / 30 / 110 V dc for the existing HT VCB/OCB/RMU 11 KV Panels complete all as specified and as directed. MAKE: EASUN REYROLLE / C&S |
| 85 | Supply and fix tripping and closing coil with complete assembly for 11 KV SF6 breaker DC 24/30 V 1 including taking out old unserviceable coil assembly, complete all as specified and as directed. |
| 86 | Supply and fix Trip-Neutral-Close (TNC) Switch, fixing with the existing HT VCB/OCB 11 KV Panel for including taking out old unserviceable TNC Switch complete all as specified and as directed. MAKE:KAYCEE OR EQUIVALENT |
| 87 | Supply and fix HT spout bushing for VCB HT 11 KV, busbar sideincluding taking out old unserviceable bushing complete all as specified and as directed. |
| 88 | Supply and fix moving contactor assembly suitable for HT OCB 11 KV 400 Amps to 800 Amps OCB including dismantling the old unserviceable contactor assembly complete all as specified and as directed. |
| 89 | Supply and fix copper bushing made out from hard copper suitable for 11 KV 2 Way SF6 breaker complete testing all as specified and as directed. |
| 90 | Supply and fix of tripping coil for 11 KV 400 / 800 Amp VCB 30 / 10 V DC inlcuding taking out old unserviceable coil complete all as specified and as directed. |
| 91 | Dismantling existing 11 KV 2 way SF-6 breaker complete alongwith bus chamber bushing assembly transported to authorised service centre for repair cutting opening the SF-6 gas chamber remove the unserviceable burntout copper bushing assembly fixing the new copper bushing assembly 3 Nos and charging the SF-6 gas retransported to original position refixing the breaker complete testing all as specified and as directed. |
| 92 | NOTE for item No 85.00: Supply of SF-6 gas and copper bushing will be measured and paid separately under relevant item of Schedule \"A\" |
| 93 | Supply and fix boot suitable for 11 KV SF-6 bushing as per existing complete all as specified and as directed. |
| 94 | Supply and fixing of Closing coil for 11 KV 400/800 Amp VCB 30/110 V DC including taking out old unserviceable coil complete all as specified and as directed. |
| 95 | Material and labour light weight IP55 protection square shape paint coated FRP earthing pit cover of size 308 x 308 x 214 mm weight 1.28 kg, black colour earth pit cover of durable and reliable product that can be used to protect electronic equipment, made from FRP which is fire retardant and resistant to impact, shock and corrosion complete all as specified and as directed. |