| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. a) Group C |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | b)2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required |
| 7 | a)5/6 A switch |
| 8 | b) 3 pin 5/6 A socket outlet |
| 9 | c) 15/16 A switch |
| 10 | d) 6 pin 15/16 A socket outlet |
| 11 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 12 | a) 3 Module (100mmX75mm) |
| 13 | b) 6 Module (200mmX75mm) |
| 14 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 15 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 16 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 17 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 18 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar,neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator) |
| 19 | a) 16 way , Double door |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 21 | a)Single pole |
| 22 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 23 | a)63 A |
| 24 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 25 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 26 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 27 | Supplying of AC Ceiling Fan (1200 mm) Sweep with Socket Type Electronic regulator i/c wiring down rod of standard length (upto 30 cm) with all accessories etc., as required. Similar to makeCrompton Empower50 - 5 Star(ISI Marked) or its equivalent etc., as required as directed by Engineer-in-charge. |
| 28 | Supplying of prewired LED tube lamp 20 W Essential Bright Batten Similar to make Philips Cat :BN170C LED20S-6500 SU L120 or Similar in make :Havels,Syska ,Bajaj,Crompton. etc as required and directed in Engineer-in-charge. |
| 29 | Supplying, Installation, Testing and Commissioning of LED Bulkhead fitting 10W Similar to Havells HEXA 10 W Cat No. HEXAFT10WLED857SSYMBOPC or similar in bajaj, philips, crompton etc as suitable for indoor and outdoor applications as required and directed by Engineer-in-charge. |
| 30 | Supplying and fixing of SMC Sintex box ofinside dimension350 mm x 250mm x 138 mmCode No. GSJB-3425,etc orequivalent make as required and directed by Engineer-in-charge. |