| 1 | WIRING IN STEEL & PVC CONDUIT |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable insurface /recessedmediumclassPVCconduit,withmodular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group C |
| 4 | Wiringforcircuit/submainwiringalongwithearthwirewiththe followingsizesofFRLSPVCinsulatedcopper conductor,single corecableinsurface/recessedmediumclassPVCconduitas required. |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | SupplyinganddrawingfollowingsizesofFRLSPVCinsulated copperconductor, singlecorecableintheexistingsurface/ recessed steel/ PVC conduit as required. |
| 7 | 3 x 2.5 sq. mm |
| 8 | Supplyingand fixingtwo module steppedtypeelectronicfan regulatorontheexistingmodularplateswitch boxincluding connections but excluding modular plate etc. as required. |
| 9 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 10 | Supplyingandfixingfollowingsize/modules,GIboxalongwith modular base & cover plate for modular switches in recess etc. as required. |
| 11 | 6 Module (200mmX75mm) |
| 12 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit,and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 13 | Group A |
| 14 | Supply and fixing following size DLP plastic trunking including all necessory accessories. |
| 15 | wiring accessories suitable for DLP trunking |
| 16 | Supply and fixing following size DLP plastic trunking including all necessory accessories - Supplying and fixing suitable size modular plate and cover in front on existing DLP trunking, including providing and fixing 3 pin 5/6 A modular socket outlet (3 modular) and 5/6 A modular switch, connections etc. as required. |
| 17 | DLP Pastic Trunking150x50mm including all accessories (end cap, junctions, joints, wall crossing, VDI accessories etc. as per site condition)with flexible cover and clipon partition. |
| 18 | MCCB, MCB & DB\"S |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMOBDBcompletewithconnections,testingand commissioning etc. as required. |
| 20 | Single pole |
| 21 | Supplying and fixing followingrating, four pole, (threephase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30mA in the existingMCBDB complete with connections, testing and commissioning etc. as required. |
| 22 | 63A |
| 23 | MISC. CIVIL ITEMS |
| 24 | Supplying and fixing of8/10 mm \"S\" type steel fan hook including chipping,welding, painting making good the damagesetc. as required |
| 25 | LABOUR |
| 26 | Removing of following items and handing over to EMU safely. |
| 27 | Removing tube light and fixture with/with outrad/clamp from cealing/wall handing over to EMU store safely as required. |
| 28 | Removing cealing fan withrad, regulator from switch board, handing over to EMU store safely including stacking of fan leafs as required. |
| 29 | LED LIGHT |
| 30 | LEDDownlighter(SMD Type)(Systemlumenefficacy≥ 105 < 120 lm/Watt ) Supplying, installation, Testing & Commissioning ofLED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD typeof following body materialwith PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 degto40degcentigrade,internalsurgeprotectionof2.5KV withShort&Opencircuit protection ,THD < 10% , P. F.≥0.95,IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%),life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with70% of initial Lumenmaintained tilllife ends , CCT 3000°K /4000°K/ 5700°K / 6000°K / 6500°K (AsperANSIBin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumptionshouldnotmorethan the specified rating and Fixture shall be confirming to relevant BIS standards andtrade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Completeinallrespecti/cconnectionswith1.5sqmmFRLS, PVCinsulatedcopper conductor single core cable and earthing etc. as requiredwith Minimum 5 year OEM warranty.System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test reportfromNABLlab forall testingrequiredforLED fixtures as per BISshall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermalmanagement:heatsinkofaluminumhousing such that LED junction temperature shall not rise above 90°C) Powdercoateddiecast/Extruded aluminum Body including trim |
| 31 | 18 watt |
| 32 | BLDC FAN |
| 33 | Brush Less Direct Current (BLDC) Motor Supply, Installation, Testing and Commissioning ofceiling fan with Brush LessDirectCurrent(BLDC)Motor,classofinsulation: B,3nos.metal ( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation withregulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019fan Supply, earthing etc. complete as req |
| 34 | 1200mm,service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |