| 1 | Supply, installation, testing and commissioning of 2 loop analog addressable FACP (fire alarm control panel): TCP/IP based, with 100%Hot redundancy-based panel monitoring components including CPU card, loop card, Network card with Ethernet + direct interface input port, Redundant power supply and 48 hrs battery backup up as per EN 54 in normal Condition. (Technical Specification Attached) |
| 2 | Supply ,installation, testing andcommissioning of 4 loopanalog addressable FACP (fire alarm control panel):FACP ( fire alarm control panel).TCP/IP based, with 100%Hot redundancy based panel monitoring components including CPU card, loop card, Network card with Ethernet + direct interface input port , Redundant power supply and 48 hrs battery backup as per EN 54 in normal Condition(Technical Specification attached) |
| 3 | Supply and Installation of Intelligent Addressable loop multi criteria detectors with base with built in short circuit isolator and having Microchip based environment monitoring for false alarm filtering and tested for all types of fires (TF1-TF 8) as per EN 54-29(Technical Specification attached) |
| 4 | Supply and Installation of Conventional MCP for hazardous area (Hydrogen sulphide gas environment) |
| 5 | Supply and installation of loop powered monitor module for integration of conventional MCPs. |
| 6 | Supply and installation single action indoor type intelligent addressable loop powered manual call pointwith built in short circuit isolator with wall mountable base ,Vds approved as per EN54-29( Wall mountable) as per Technical specification attached) |
| 7 | Supply and installation of intelligent addressable loop powered sounder with built in short circuit isolator with wall mountable base Vds as per EN54-11 |
| 8 | Supply and installation of intelligent addressable strobe light with hooter with built in short circuit isolator with wall mountable base |
| 9 | Supply and installation of relay module (4 Relays per module) for damper action with minimum 4 potential free relay outputs |
| 10 | Supply and installation of response indictor( Compatible with the above system ) |
| 11 | Supply and Installation of PC and Display monitor along with GUI with 2500 Software with license. |
| 12 | Supply and Installation of Latest Semi-Conductor based Linear heat sensing system along with controller |
| 13 | Supply and laying of 2 core *1.5 Sq cm twisted pair Armoured, Shielded ,FRLS Cable ( Loop length 3000 to 3500 mtr based on core area selected ) |
| 14 | Supply and installation of PVC cable conduit with accessories. |
| 15 | Supply of Detector testing tool kit |
| 16 | Installation and commissioning of system |